background image

* Model Dependent

Network Type 

3 Phase - 3 Wire / 3 Phase - 4 Wire

Aux-Supply 

140 - 265V AC / DC, 50 / 60Hz, 12VA

Sensing/Measurement 

True RMS

Operating Voltage 

Voltage input : L-N or L-L

 

Range : 50 to 500V AC; 50/60 Hz

Operating Current 

40mA - 7.5A ( /5A Current Transformer)

Relay Output Contact 

Type : N/O, Rating: 5A @250V AC,1250VA

(*)

Capacitor Steps   

12 Steps (Max)

Power Consumption 

<0.2VA (Current Circuit)

 

<5VA (Voltage Circuit)

Target Cos  setting 

0.80 Lag - 1.00 - 0.8 Lead

Ø

CT Ratio 

Configurable (Max 9999)

Compliance / Standard 

IEC 61000

0

0

Operating Temperature Range 

0 C to +55 C

0

0

Storage Temperature Range 

-10 C to +70 C

Humidity Range 

5% to 95% non condensing

Installation 

Panel mounting & fitted by side screw

 

clamp

Dimension (H x W x D) 

(144 x 144 x 80) mm

Packing Weight 

900 gms (Approx)

Technical Data

C/k = Power Of First Capacitor in kVAr (Q) / Current Transformer Ratio (CT Ratio)

C/k Ratio

This setting is a threshold value for switching on/off capacitors steps. It is calculated 
based on the smallest size capacitor.

13

Содержание CSPF-100

Страница 1: ...is the same as the one ordered For the safe use of CSPF 100 it is vital that those persons installing or handling it follow the usual safety procedures as well as specific warnings contained in the Q...

Страница 2: ...nder compensation over voltage over under current etc u FAN control output over temp alarm based on a built in temp sensing u Field accessible test mode for relay contact check u Automatic C K set up...

Страница 3: ...11 12 1 2 3 4 5 6 7 8 K M CSPF 100 ONTROLLER C ACTOR F OWER P AUTO MANUAL ON Manual OFF Auto Operation mode Auto Manual Cos indication Voltage indication Current indication Active Power indication Re...

Страница 4: ...6 Steps 8 Steps 12 Steps CSPF 100 R06 220 CSPF 100 R08 220 CSPF 100 R12 220 04...

Страница 5: ...Panel cut out 138 0 138 0 Back view of CSPF All the dim are in mm Gen Tol 1 0mm Front View Side View 144 0 144 0 Dimension Details Mounting Clamp Clamp fixing screw 69 0 80 0 63 0 137 0 05...

Страница 6: ...sure that correct discharge resistors are fitted to capacitor bank terminals for safety reason They are required for discharging capacitor voltage 1 2 10 3 6 5 7 8 9 11 12 21 22 23 24 25 26 27 AUX SUP...

Страница 7: ...2 24 K3 N O Contact for Cap Bank 3 25 K4 N O Contact for Cap Bank 4 26 K5 N O Contact for Cap Bank 5 27 K6 N O Contact for Cap Bank 6 28 COMM Common Terminal for Relay contact K7 K12 29 K7 N O Contac...

Страница 8: ...nnection scheme 2 Model Dependent 2 Refer C K Ratio section to set proper value 3 Switching program determines the power kVAr ratio sequence of the capacitor Bank steps connected A Common Parameters A...

Страница 9: ...1 In OFF Under current Alarm delay DELY 1 999 1 Sec 5 2 Capacitor Bank Trip selection on Under current CAP OFF ON OFF 1 Over compensation oCo 1 600 1 Sec 5 1 Under compensation vCo 1 600 1 Sec 5 1 0 T...

Страница 10: ...ill be edited or viewed going through different screens using keys Below are the brief overview of the menu structure AUTO Manual mode will be indicated by Auto Manual LED Use keys to scroll view the...

Страница 11: ...nt trip Cap Bank ON OFF selection for High Temp trip oURU Over Voltage setting DELY CAP Return to Prev Menu DELY Temp High Trip Delay DELY Over current Delay Under current Delay Over voltage Delay DEL...

Страница 12: ...ntact Test will be blocked when load is connected C Relay Contact Test Test Menu tt Short Press Sub menu screens for B C Press to see the below shown screen B YES AvTo CA Short Press CA Note C k ratio...

Страница 13: ...Circuit Target Cos setting 0 80 Lag 1 00 0 8 Lead CT Ratio Configurable Max 9999 Compliance Standard IEC 61000 0 0 Operating Temperature Range 0 C to 55 C 0 0 Storage Temperature Range 10 C to 70 C Hu...

Страница 14: ...7 0 83 1 00 200 5 40 0 06 0 13 0 25 0 31 0 38 0 50 0 63 0 75 1 00 300 5 60 0 04 0 08 0 17 0 21 0 25 0 33 0 42 0 50 0 67 0 83 1 00 400 5 80 0 03 0 06 0 13 0 16 0 19 0 25 0 31 0 38 0 50 0 63 0 75 500 5...

Страница 15: ...5 6 L1 L2 L3 N S1 S2 AUX SUPPLY FUSE P N 11 12 1 2 0 PHASE ANGLE 60 AnEL CURRENT VOLTAGE Vin 5 6 L1 L2 L3 N AUX SUPPLY FUSE P N S1 S2 0 PHASE ANGLE 120 AnEL CURRENT VOLTAGE Vin 5 6 L1 L2 L3 N S1 S2 1...

Страница 16: ...ction to be taken Over Compensation Alarm Under Compensation Alarm Target Cos phi is within limit Conn scheme is not as per phase angle set All the capacitor steps were switched On But target cos phi...

Отзывы: