background image

REV 2022 0610

SPECIFICATIONS AND DETAILS ARE SUBJECT TO CHANGE WITHOUT NOTIFICATION. CONTACT CANDELA LIGHTING FOR UP TO DATE DETAILS.

CANDELA LIGHTING

 • CANDELA.LIGHTING

ELE EDGE-LIT EXIT SIGN LED

Installation Manual

SAVE THESE INSTRUCTIONS

2

ELECTRICAL CONNECTIONS

A)

 Battery Backup Wiring Diagram

B)

 AC Only Wiring Diagram

LED BOARD

RED 277VAC

BAT

BLACK 120VAC

WHITE COM

PC BOARD

TRANSFORMER

PC BOARD

LED BOARD

RED 277VAC

BLACK 120VAC

WHITE COM

TRANSFORMER

MOUNTING TYPE

Back Mount

Top Mount

End Mount

GENERAL INSTALLATION INSTRUCTIONS

Choose mounting configuration (end, top or back mount). Plug remaining holes with the appropriate color plugs.

A)

 Secure canopy bracket to ceiling or wall.

B)

 Open the housing cover.

C)

 Secure housing and canopy with screws (see mounting configuration).

D)

 Feed the AC input leads (red, black, white) through the housing and canopy’s center hole. Connect AC input leads to AC power supply leads. Connect the red lead to a 

277VAC power supply or the black lead to a 120VAC power supply and the white lead to neutral.

E)

 Secure canopy into canopy bracket with 1-1/2” long #8-32 screws, then insert battery terminal wire into two-pin male connector.

F)

 Connect battery (battery backup model only) only after continuous AC power can be provided to the unit.

G)

 Snap housing cover into place.

H)

 Apply chevron directional indicators as required. Remove application templates when finished.

END MOUNT INSTALLATION INSTRUCTIONS

A)

 Secure canopy to end plate of fixture using mounting holes C and E with (2) 3/4” #10-24 screws (included). 

B)

 Run connection wires through large hole between mounting holes C and D.

C)

 Make electrical connections and mount canopy to junction box (or spider plate if required) using the two recessed mounting holes and (2) 1-1/2” #8-32 screws (included).

TOP MOUNT INSTALLATION INSTRUCTIONS

A)

 Secure canopy to top of fixture using mounting hole A with 3/4“ #8-32 screw and hex nut, and 1/2” center hole (between mounting holes B and C) with threaded nipple and hex 

nuts (included).

B)

 Run connection wires through threaded nipple.

C)

 Make electrical connections and mount canopy to junction box (or spider plate if required) using the two recessed mounting holes and (2) 1-1/2” #8-32 screws (included).

BACK MOUNT INSTALLATION INSTRUCTIONS

A)

 Mount canopy to junction box (or spider plate if required) using the two recessed mounting holes and (2) 1-1/2” #8-32 screws.

B)

  Run connection wires through large hole in center of canopy.

C)

 Secure fixture to canopy with (2) 3/4” #10-24 screws (included) by going directly into mounting holes A and C.

D)

 Make electrical connections.

Отзывы: