PERFORMANCE CONSIDERATIONS 

C

orrect

i

on

 F

actors

The actual performance of the plenum is based upon the overall design of the plenum system.  Two correction factors 
must be applied to all plenum fans. 

1.  Outlet duct loss 
2.  Influence of adjacent plenum walls 

ESTIMATED LOSSES DUE TO PLENUM OUTLETS 

Outlet losses based on the outlet configuration and duct velocity must be included in the systems external static pressure 
requirements.  Outlet losses are dependent on the direction of the outlet, shape of the outlet and size of the Plenum.  On 
Plenum’s with more than one discharge, select the configuration that has the greatest loss. 

CORRECTION FACTOR CALCULATIONS INCLUDED 

 IN 

DELAIR

 SOFTWARE PACKA

G

E AVAILABLE

FOR DOWNLOAD OR ON CD AT: 

WWW.DELHI-INDUSTRIES.COM

Содержание DPL-12

Страница 1: ...jury and or property damage Retain instructions for future reference Fig 1 MODEL MAX H P SHAFT DIA WEIGHT DPL 12 7 1 2 1 51 DPL 13 7 1 2 1 57 DPL 15 7 1 2 1 68 DPL 16 10 1 3 16 80 DPL DPL AF 18 7 1 2 10 1 3 16 91 81 DPL DPL AF 20 10 15 1 3 16 104 96 DPL DPL AF 22 10 15 1 7 16 148 139 DPL DPL AF 24 15 20 1 7 16 185 162 DPL DPL AF 27 15 25 1 7 16 205 185 DPL DPL AF 30 20 30 1 11 16 236 248 DPL DPL A...

Страница 2: ...d the motor end bell Tighten the set screws on the key of the motor shaft 6 When using the 10 30 HP motor platform with the slide base in its minimum position install the V belt within the sheave grooves Adjust the sheave on the blower shaft to ensure proper pulley alignment see Figure 3 and secure in place A straight edge across the face of the driven pulley should be parallel to the belt once pr...

Страница 3: ...oss 2 Influence of adjacent plenum walls ESTIMATED LOSSES DUE TO PLENUM OUTLETS Outlet losses based on the outlet configuration and duct velocity must be included in the systems external static pressure requirements Outlet losses are dependent on the direction of the outlet shape of the outlet and size of the Plenum On Plenum s with more than one discharge select the configuration that has the gre...

Страница 4: ...Oct 07 Delhi Industries Inc 523 James Street Delhi Ontario N4B 2Z3 Tel 519 582 2440 Fax 519 582 0581 www delhi industries com CORRECTION FACTORS DUE TO INFLUENCE OF ADJACENT PLENUM WALLS ...

Страница 5: ... thereafter 2 Follow the motor manufacturer s instructions for motor lubrication Remove any excess lubrication 3 Drives A Check belt tension and alignment replace cracked or worn belts If it is necessary to replace one belt on a multiple belt drive replace all the belts with a matched set B Under normal conditions no re lubrication is the rule The bearing lubricant cavity is 1 3 1 2 filled as ship...

Страница 6: ... one year against manufacturing defects in material and workmanship when operating under normal conditions Liability is limited to the replacement of defective parts Labour and transportation costs are not included 5 PARTS LIST 1 PLENUM INLET WALL 2 DETACHABLE INLET VENTURI 3 C SHAPED FRAME 4 T BAR 5 PILLOW BLOCK BEARING 6 SHAFT 7 BACKWARDLY INCLINED FLAT BLADE STEEL WHEEL OR BACKWARDLY INCLINED A...

Отзывы: