Enables this contact to be used as a shutdown.
Two contact inputs are available for shutdown purposes. These are tagged as “High Fuel Pressure #2” and
“Low Fuel Pressure #2”.
• None: Both inputs are disabled
• Hi Press: High Fuel Pressure Burner #2 is enabled
• Hi & Low Press: High Fuel Pressure Burner #2 and Low Fuel Pressure Burner #2 are enabled.
This item configures the spare #1 thermocouple input.
• None: Controller will disable this input.
• Indicate Only: Temperature will be displayed on page five.
• Numeric Value: Temperature will be displayed and the unit will shut down when this configured
numeric temperature setting is crossed.
This applies the label to the previous thermocouple input. Whatever tag is chosen is displayed on page
five. The “Bath” tag here should not be confused with the dedicated bath thermocouple input.
This item configures the spare #2 thermocouple input.
• None: Controller will disable this input.
• Indicate Only: Temperature will be displayed on page five.
• Numeric Value: Temperature will be displayed and the unit will shut down when this configured
numeric temperature setting is crossed.
This applies the label to the previous thermocouple input. Whatever tag is chosen is displayed on page
five. The “Bath” tag here should not be confused with the dedicated bath thermocouple input.
21
Fuel High Pressure #1
Yes / No
22
Fuel Pressure #2
None / Hi Press / Hi & Low Press
23
Spare Temp T/C #1
None / Indicate Only /
0 - 800°C (32 - 1472°F)
24
Spare Temp T/C #1 Label
Stack #1 / Bath / Process
26
Spare Temp T/C #2 Label
Stack #2 / Bath / Process
25
Spare Temp T/C #2
None / Indicate Only /
0 - 800°C (32 - 1472°F)