6. Normal operation
6. Normal operation
.45.
.44.
OV-G-V1:
300---480V
OV-G-V1-T: 0.01---9S
OV-G-V2:
300---490V
OV-G-V2-T: 0.01---1S
UN-G-V1:
173---336V
UN-G-V1-T: 0.01---9S
UN-G-V2:
132---319V
UN-G-V2-T: 0.01---1S
Startup-T: 10-600S
OV-G-F1: 50.2-63Hz
OV-G-F1-T: 0.01---9S
OV-G-F2: 51-63Hz
OV-G-F2-T: 0.01---9S
UN-G-F1: 47-59.5Hz
UN-G-F1-T: 0.01---9S
UN-G-F2: 47-59Hz
UN-G-F2-T: 0.01---9S
Restore-T: 10-600S
Table 6.2 Setting ranges for User-Def (L-N)
NOTE
The initial value of the User-Def standard is for reference only. It does
not represent a correct value suitable for use.
6.7 Advanced Settings - Technicians Only
NOTE:
To access to this area is for fully qualified and accredited technicians only.
Please follow 6.4 to enter password to access this menu.
6.7
.
1 Selecting Standard
This function is used to select the grid's reference standard (see Figure 6.16).
YES=<ENT> NO=<ESC>
Standard:G99
Figure 6.16
Selecting the “User-Def” menu will access to the following submenu (see Figure 6.17),
Figure 6.17
OV-G-V1: 400V
OV-G-V1-T: 1.0S
Below is the setting range for “User-Def”. Using this function, the limits can be changed
manually. (These voltage values are the phase voltage)
For different countries, the grid standard needs to be set as different according to local
requirements. If there is any doubt, please consult Canadian Solar service technicians
for details.
NOTE
6.7.2 Grid ON/OFF
This function is used to start up or stop the power generation of Canadian Solar Three Phase
Inverter (see Figure 6.18).
Grid ON
Grid OFF
Figure 6.18 Set Grid ON/OFF
Screens can be scrolled manually by pressing the UP/DOWN keys. Press the ENTER key
to save the setting. Press the ESC key to return to the previous menu.
6.7.3 Clear Energy
Clear Energy can reset the history yield of inverter
These two functions are applicable by maintenance personnel only, wrong
operation will prevent the inverter from working properly.
Select Advanced Settings from the Main Menu to access the following options:
1. Select Standard
2. Grid ON/OFF
3. Clear Energy
4. Reset Password
5. Power Control
6. Calibrate Energy
7. Special Settings
8. STD. Mode Settings
9
.
Restore Settings
10. HMI Update
11. Restart HMI
12. Debug Parameter
13.DSP Update
14.Compensation Set
15.I/V Curve