background image

.58.

10. Appendices

.59.

10. Appendices

Installation method

Enclosure protection level

Vertical Mounting

IP65

Ue:1500V DC, In: 20A,30KA

Rated voltage(V DC)

Max. input current per string(A)

Max. continuous output current(A)

Output wire (mm²)

Fuse

SPD

Communication SPD

Monitor power supply

Input

Output/Ground/Communication

Model

Product Name

Enclosure material

Ambient temperature (°C)

Ambient humidity

Altitude (m)

Weight (KG)

Enclosure (width × height × depth)

1500

250(MCCB 315A)

40*(4~6)

2*(120~185)

In:5KA, Imax:10KA, Up:≤30V, Uc:≥18V

Self-powered

Input voltage:450~1500VDC

Cable connectors,IP67

Glands,IP68

1.5mm cold rolling steel,powder coating RAL7035

-

25~+50 (

50

, components will be derated)

0~95%

2000 (

3000m, components will be derated)

About 40(Final subject to drawings)

850 × 600 × 200mm(Final subject to drawings)

Ground wire (mm²)

Communication wire (mm²)

Molded case circuit breaker(MCCB)

20

1*(16~25)

2*2*1

Ue:1500V DC, In:315A,Icu:≥20KA

Type II,In:20KA, Imax:40KA, Up:≤5.0KV, Uc:≥1500V

LM-PVSZ-CV-G20

Monitor

Bus voltage, current of per string, power, status 

of SPD, output DC MCCB status(on/off/trip), 

product internal temperature, MODBUS-RTU 

protocol, RS 485 communication.

Number of DC output

Strings wire (mm²)

Max. Number of DC input strings

Power of monitor

12.5(20A Fuse)

1

PV Combiner Box

Recommended Combiner Model and Specifications.

Figure 10.2 Inverter output power by input voltage

P(%)

100%

50%

860

1300

1500

1450

Input Voltage(V)

Figure 10.1 For all models of inverter

Comments:

A thermal sensor inside the inverter is calibrated to determine ambient temperature. 

All inverters will begin a sloped derate at 45

°

C ending at 78% output power at 60

°

C. 

Temperatures above 60

°

C and below -25

°

C will derate to 0% output power.

Ambient Temperature [

 ]

O

u

tp

u

t p

o

w

e

r / R

a

te

d p

o

w

e

r

0

0.8

1.2

0

60

1.0

45

35

0.2

0.4

0.6

40

50

55

0.78

Содержание CSI-125K-T600GL02-E

Страница 1: ...sales au csisolar com Customer Support Email service au csisolar com South East Asia 101 Thompson Road 15 03 United Square Singapore 307591 P 65 6572 905 F 65 6559 4690 Sales Inquires Email sales sg c...

Страница 2: ...tions 5 4 2 AC Connections 5 4 3 DC configuration 32 32 33 34 34 34 34 5 4 4 AC configuration 36 6 Normal operation 6 1 Start up procedure 6 2 Shutdown procedure 37 37 37 6 3 Main Menu 38 38 6 4 Infor...

Страница 3: ...r ships with all accessories in one carton When unpacking please verify all the parts listed below are included 3 4 Fastening screw 2 User manual 1 1 2 3 4 4 Vent COM LED lights LCD display 4 buttons...

Страница 4: ...inverter is not installed immediately storage instructions and environmental conditions are below DO NOT STACK MORE THAN HIGH Figure 1 3 2 2 Safety Instructions WARNING To reduce the risk of fire bran...

Страница 5: ...s required between inverters NOTE Nothing should be stored on or placed against the inverter 3 Installation 2 4 Protection Circuitry and Controls WARNING Risk of fire Despite careful construction elec...

Страница 6: ...ity of the electricity supply the sound level from the inverter can be quite high 3 2 Product handling Figure 3 3 Handles used to move the inverter shown circled in red 3 1 2 4 Air circulation Do not...

Страница 7: ...vertically The steps to mount the inverter are listed below 1 Refer to Figure 3 6 drill holes for mounting screws based on the hole diameter of bracket using a precision drill keeping the drill perpen...

Страница 8: ...gle Please install the inverter vertically If the inverter cannot be mounted vertically it may be tilted backward to 15 degrees from vertical Vertical 15 Backward Figure 3 9 Correct installation Angle...

Страница 9: ...he DC Isolator OFF 3 Connect the AC wires 4 Connect the DC wires Table 3 1 Electrical connection Parts Connection Cable size Torque DC terminal Ground terminal Grid terminal RS 485 terminal RJ45 termi...

Страница 10: ...rounding 2 Prepare OT terminals M10 To effectively protect the inverter two grounding methods must be performed Connect the AC grounding cable Please refer to section 3 4 3 Connect the external ground...

Страница 11: ...insulation of the wire past the cable crimping area of the OT terminal then use a hydraulic crimp tool to crimp the terminal The crimped portion of the terminal must be insulated with heat shrinkable...

Страница 12: ...o a single MPPT must consist of the same number of series connected PV modules 1 Connect the three 3 AC conductors to the three 3 AC terminals marked L1 L2 and L3 Refer to local code and voltage drop...

Страница 13: ...nd remove the junction box cover 2 Strip the insulation of the wire past the cable crimping area of the OT terminal then use a hydraulic crimp tool to crimp the terminal The crimped portion of the ter...

Страница 14: ...onnection See figure 4 2 CAT 5E outdoor rated cable outer diameter 9mm internal resistance 1 5 10m and shielded RJ45 connectors are recommended 4 1 RS485 communication 485 IN 485 OUT Figure 4 2 RJ45 p...

Страница 15: ...er communication through ethernet as shown below Address 01 Address 01 Address 01 NOTE Laptop is required for onsite Ethernet communication commissioning If the router doesn t support automatic IP add...

Страница 16: ...inking indicates it is trying to connect OFF indicates connection failed Constantly ON but blinking sometimes indicates it is transferring data between the server D3 Green LED Module power light Const...

Страница 17: ...he inverter not operating at all 5 2 Changing the grid standard 5 2 1 Procedure to set the grid standard NOTE This operation is for service technicians only The inverter is customized according to the...

Страница 18: ...he voltage present between the positive and negative wires of each string If the open circuit voltage of the string is near the maximum value accepted by the inverter verify the string length Low ambi...

Страница 19: ...ower that is within start up and operating ranges the inverter will turn on After turn on the inverter will check internal parameters sense and monitor AC voltage hertz rate and the stability of the s...

Страница 20: ...hows the reactive power of the inverter App_Power Shows the apparent power of the inverter Work Mode Volt watt DRM NO 08 10 sec Work Mode Shows current working mode DRM NO Shows DRM Number VPV_Total 1...

Страница 21: ...00 manually by pressing the UP DOWN keys Press the ESC key to return to the previous menu Alm000 OV G V T 00 00 00 00 D 0000 Figure 6 6 Alarm Message The following submenus are displayed when the Sett...

Страница 22: ...d 6 6 7 Daily Records The screen shows history of changing settings Only for maintance personel 6 6 3 Version The screen shows the model version of the inverter And the screen will show the software v...

Страница 23: ...e setting range for User Def Using this function the limits can be changed manually These voltage values are the phase voltage For different countries the grid standard needs to be set as different ac...

Страница 24: ...n see Figure 6 19 Figure 6 19 Set new password YES ENT NO ESC Password 0000 Enter the right password before set new password Press the DOWN key to move the cursor Press the UP key to revise the value...

Страница 25: ...000 S16DAT6 0000 S16DAT7 0000 S16DAT8 0000 49 48 Figure 6 24 Selecting Fan Test displays the sub menu shown below Are you sure YES ENT NO ESC Fan Test is a factory test function Press the ENTER key to...

Страница 26: ...can be removed with a soft brush 7 1 Anti PID Function Inverter integrates optional Anti PID module and it can recover the PID effect during night thus protect the PV system from degradation Figure 7...

Страница 27: ...the fan Assemble the fan on the rack 8 Connect the electrical wire and reinstall the fan assembly Restart the inverter 7 3 Surge Protection Device Maintenance If surge protection device is damaged it...

Страница 28: ...t 1 Restart inverter 2 Identify and remove the string to the fault MPPT 2 Change power board IGFOL F Grid current tracking fail OV G I Over grid current OV DCA I IGBT OV I Over IGBT current 1 Restart...

Страница 29: ...solar irradiance reduces and confirm the string current is less than 0 5A with a clip on ammeter and then turn off the DC switches 3 Please note that any damages due to wrong operations are not covere...

Страница 30: ...Ground wire mm Communication wire mm Molded case circuit breaker MCCB 20 1 16 25 2 2 1 Ue 1500V DC In 315A Icu 20KA Type II In 20KA Imax 40KA Up 5 0KV Uc 1500V LM PVSZ CV G20 Monitor Bus voltage curre...

Страница 31: ...ances and are properly ventilated Completed 5 Serial number Record the product serial numbers located on the side label Serial Numbers attached list 6 Solar modules Confirm PV module installation comp...

Страница 32: ...in Notes 1 Switch the grid supply main Switch AC ON first 2 Switch the DC switch ON If the voltages of PV arrays are higher than start up voltage the inverter will turn on The red LED power will be co...

Страница 33: ...e front panel interface Completed Record current date time in Notes 6 Communication setting if avail Set communication with a unique address for each inverter Completed Record address in Notes 7 Machi...

Страница 34: ...Output power Input DC voltage Insulation limit K PV start up voltage Grid V Max V Min Frequency Max Min Reactive compensation PF Configuration MPPT Individual MPPT Parallel Monitoring RS485 Ethernet...

Страница 35: ...r to inverter site selection and installation 3 PHASE STRING INVERTERS CSIF ST 016 A 0 INSTALLER S NAME INSTALLER S SIGNATURE COMPANY DATE Inverter serial numbers 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 1...

Страница 36: ......

Отзывы: