areas  (i.e.  IEC  62930:  2017  approved),  with  proper 

insulation which is able to withstand the maximum possible 

system open-circuit voltage. For CS7N and CS7L modules, 

Canadian Solar recommends the use of a copper wire of at 

least 6 mm

2

 (10AWG) section. 

 

Only copper conductor material should be used. Select a 

suitable  conductor  gauge  to  minimize  voltage  drop  and 

ensure  that  the  conductor  ampacity  complies  with  local 

regulations (i.e. NEC 690.8(D)). 

CABLE AND CONNECTOR PROTECTION 

 

Secure  the  cables  to  the  mounting  system  using  UV-

resistant cable ties. Protect exposed cables from damage 

by taking appropriate precautions (e.g. placing them inside 

a  metallic  raceway  like  EMT  conduit). Avoid  exposure  to 

direct sunlight. 

 

A minimum bending radius of 60 mm (2.36 in) is required 

when  securing  the  junction  box  cables  to  the  racking 

system. 

 

Protect  exposed  connectors  from  weathering  damage  by 

taking  appropriate  precautions.  Avoid  exposure  to  direct 

sunlight. 

 

Do  not  place  connectors  in  locations  where  water  could 

easily accumulate. 

5.2 GROUNDING 

 

For  grounding  requirements  in  North America,  a  module 

with exposed conductive parts is considered to comply with 

UL  61730  only  when  it  is  electrically  grounded  in 

accordance with both the instructions presented below and 

the  requirements  of  the  National  Electrical  Code.  Any 

grounding  means  used  with  Canadian  Solar  modules 

should be NRTL certified to UL 467 and UL 2703 standards. 

Please  consult  our  technical  service  team  for  the  formal 

approval process. 

 

For  grounding  requirements  in  other  areas,  although  the 

modules  are  certified  to  Safety  Class  II,  we  recommend 

them  to  be  grounded  and  that  module  installation  should 

comply  with  all  applicable  local  electrical  codes  and 

regulations.  Minimum  size  of  equipment  grounding 

conductors for ground raceway and equipment from NEC 

690.8(D)  should  be  considered.  Grounding  connections 

should  be  installed  by  a  qualified  electrician.  Connect 

module frames together using adequate grounding cables: 

we recommend using 4-14 mm² (AWG 6-12) copper wire. 

Holes  provided  for  this  purpose  are  identified  with  a 

grounding  symbol 

  (IEC  61730-1).  All  conductive 

connection junctions must be firmly fixed. 

 

Do not drill any extra ground holes for convenience as this 

will void the module’s warranty. 

 

All  bolts,  nuts,  flat  washers,  lock  washers  and  other 

relevant  hardware  should  be  made  of  stainless  steel, 

unless otherwise specified.   

 

Canadian Solar does not provide grounding hardware. 

 

The grounding method  described below  is recommended 

for Canadian Solar. 

 

GROUNDING METHOD: BOLT + TOOTHED NUT + CUP WASHER. 

 

To  fix  the  wire  between  the 

flat  washer  and  cup  washer, 

place 

the 

cup 

washer 

(concave  side  up)  between 

the frame and the wire. 

Then tighten the bolt using 

the toothed nut. 

Содержание CS6R-MS Series

Страница 1: ...For professional use only INSTALLATION MANUAL OF PHOTOVOLTAIC MODULE...

Страница 2: ...NPACKING AND STORAGE 5 5 MODULE INSTALLATION 7 5 1 MODULE WIRING 9 5 2 GROUNDING 12 6 MOUNTING INSTRUCTIONS 13 6 1 MOUNTING METHOD BOLTING 14 6 2 MOUNTING METHOD CLAMPING 16 6 3 INSERTION SYSTEM 23 6...

Страница 3: ...nguage versions of this document the English version shall prevail Please refer to our product lists and documents published on our website at www csisolar com as these lists are updated on a regular...

Страница 4: ...C No 793 93 and Commission Regulation EC No 1488 94 as well as Council Directive 76 769 EEC and Commission Directives 91 155 EEC 93 67 EEC 93 105 EC and 2000 21 EC the REACH Regulation we inform you t...

Страница 5: ...x 1 25 x Max 1 175 Impp ImppSTC Impp the highest 3 hour current average resulting from the simulated local simultaneous irradiances on the front and rear sides of the PV array accounting for elevation...

Страница 6: ...anti tipping structure Such structure can be built with the pallet s own wooden frame or with the spare parts provided in the pallets During unpacking the unpacked modules should be properly fixed Aft...

Страница 7: ...ation Class A equivalent to Safety Class II requirements Modules rated under this class should be used in systems operating at voltage above 50V or power above 240W where general contact access is ant...

Страница 8: ...general technical system requirements Ensure that other systems components do not damage the module mechanically or electrically Modules can be wired in series to increase voltage or in parallel to in...

Страница 9: ...A module can be considered to be unshaded if its entire surface is free from shading all year round including on the shortest day of the year For optimizing the power generation of the rear side of b...

Страница 10: ...dian Solar sales representative Cables should always be fastened on module frames or mounting rails in order to avoid shading on the rear side of bifacial modules In case where a cable connection meth...

Страница 11: ...g connector endcaps should be taken to avoid moisture and dust penetrating into the connector If end caps are present on un mated connectors carefully remove by hand the end caps before connecting the...

Страница 12: ...structions presented below and the requirements of the National Electrical Code Any grounding means used with Canadian Solar modules should be NRTL certified to UL 467 and UL 2703 standards Please con...

Страница 13: ...standing equal or greater mechanical loads The mounting system supplier is responsible for the strength and stability of the mounting structure which must meet the requirements of the relevant design...

Страница 14: ...ill lead to more severe deflection 6 1 MOUNTING METHOD BOLTING The mechanical load test with these mounting methods were performed according to IEC 61215 Modules should be bolted to supporting structu...

Страница 15: ...3200Pa 5400Pa 3200Pa CS6W MS CS7L MS CS7N MS 5400Pa 2400Pa CS6W T Preliminary 5400Pa 2400Pa CS6R T Preliminary 5400Pa 2400Pa 5400Pa 2400Pa CS6R H AG CS6RA H AG 5400Pa 2400Pa 3600Pa 2400Pa CS6W MB AG...

Страница 16: ...When installing inter modules or end type clamps please take the following measures into account 1 Do not bend the module frame 2 Do not touch or cast shadows on the front glass 3 Do not damage the su...

Страница 17: ...0 100 100 600 250 550 400 500 CS6W MS CS7L MS 300 600 400 500 CS7N MS 300 600 450 550 CS6W T Preliminary 400 500 CS6R T Preliminary 300 400 CS6L MS Preliminary 400 500 CS6R H AG 400 550 400 500 CS6RA...

Страница 18: ...long side frame Module Types Max Mechanical Load Pa 1600 1600 2800 2400 3200 2400 3600 2400 4000 2400 4000 3200 5400 2400 A1 Range mm CS6R MS CS6RB MS 200 600 200 300 CS6RA MS 200 400 CS6R MS HL 100 6...

Страница 19: ...de of frame and rails perpendicular to the long side frame Module Types Max Mechanical Load Pa 5400 2400 5400 2800 6000 3600 6000 4000 8100 5000 A3 A5 Range mm CS6R MS CS6RA MS CS6RB MS 80 380 CS6R MS...

Страница 20: ...0 100 300 CS6R H AG 400 600 200 250 CS6W MB AG F42 Frames 600 700 200 250 with 35mm height frame 6 2 7 Four clamps mounting on short side of frame Module Types Max Mechanical Load Pa 1200 1200 2200 22...

Страница 21: ...r single glass monofacial modules Note that clamp overlap length of 40mm or 1 50 in when uplift load 2400 Pa is allowed Landscape installation clamping on long side frame Modyle Type Max Span Max Cant...

Страница 22: ...Solar Co Ltd www csisolar com Modyle Type Max Span Max Cantilever length Downforce Uplift CS6R MS HL 48 inches 1 22 m 16 inches 0 41 m 1800 Pa 1800 Pa 32 inches 0 81 m 10 7 inches 0 27 m 1800 Pa 1800...

Страница 23: ...ule frame 2 Do not touch the front glass or cast shadows onto it 3 Do not damage the surface of the frame 4 Ensure that the insertion profiles overlap the module frame by at least 10 mm 0 39 in 5 Ensu...

Страница 24: ...le clamps to the mounting rails using the torque stated by the mounting hardware manufacturer M6 X 1 1 4 or M8 X 1 25 5 16 bolt and nut are used for this bolting method The tightening torques should b...

Страница 25: ...6 1900 1900 B1 B2 B3 B4 16 2600 2200 CS6W TB AG A1 A3 400 B1 B3 790 B1 B2 A3 A4 16 1900 1900 B1 B2 B3 B4 16 2600 2200 CS6W MB AG F42 Frame A1 A3 400 B1 B3 790 B1 B2 A3 A4 16 1800 1600 B1 B2 B3 B4 16 2...

Страница 26: ...the potential electric shock hazard Cracked or broken modules represent an electric shock hazard due to leakage currents and the risk of shock is increased when modules are wet Before cleaning thoroug...

Страница 27: ...n Solar technical support department for information on the use of cleaning solutions and loading specifications OPERATION PREPARATION Noticeable dirt must be rubbed away by gentle cleaning implement...

Страница 28: ...to roof array size array spacing and anti nesting features as it may allow a more efficient ventilation The graphics below from IEC 63126 show this influence the maps presented here are a general guid...

Страница 29: ...29 EN Rev IM GN EN 1 0 Copyright January 2023 CSI Solar Co Ltd www csisolar com Figure A 3 Spatial distribution of the K ppen climate types for the period from 1901 to 2010...

Страница 30: ...electrical parameters and limitations of the MLPE devices and the Canadian Solar modules are suitable for one another Failure to comply with these instructions will void the Canadian Solar warranty I...

Страница 31: ...their distance from the coastline Different coastal land areas are defined according to how far away from the coastline they are Canadian Solar generally classifies seashore PV installations according...

Страница 32: ...n These washers are made in a process called explosion welding Concerning insulation gaskets we recommend mica laminate or other silicone or fluoride based insulating materials C 2 3 ANTI CORROSION ME...

Страница 33: ...eas Process specifications for the different components must comply with relevant international anti corrosion standards Minimum coating thicknesses for hot dip galvanized and anodizing oxide componen...

Страница 34: ...CSI Solar Co Ltd www csisolar com of any kind including but not limited to bodily harm injury and damage to property as a result of handling modules installing systems or compliance or non compliance...

Страница 35: ...Copyright January 2023 CSI Solar Co Ltd www csisolar com AMENDED EDITIONS AND DATES Rev 1 0 integrated version first release in January 2023 CSI Solar Co Ltd 199 Lushan Road SND Suzhou Jiangsu China...

Отзывы: