background image

| 7

·  Do not immerse modules in water or constantly expose 

modules to water (either fresh or salt)  (i.e. from fountains, 
sea spray).  

·  Exposing modules to salt (i.e. marine environments) or 

sulfur (i.e. sulfur sources, volcanoes) incurs the risk of 
module corrosion. 

·  Failure to comply with these instructions will void 

Canadian Solar Inc. warranty.

INSTALLATION REQUIREMENTS   

·  Ensure that the module meets the general technical 

system requirements. 

·  Ensure that other systems components do not damage 

modules mechanically or electrically.

·  Modules can be wired in series to increase voltage or in 

parallel to increase current. To connect modules in series, 
connect the positive terminal of one module to the nega-
tive terminal of the next module. To connect in parallel, 
connect the positive terminal of one module to the positi-
ve terminal of the next module.  

·  Only connect the quantity of modules that corresponds 

to the voltage specifications of the inverters used in the 
system. In addition modules must NOT be connected 
together to create a voltage higher than the maximum 
permitted system voltage stated on the module name-
plate, even under the worst local temperature conditions 
(see Table 1 for the correction coefficients that apply to 
open-circuit voltage).

·  A maximum of two strings can be connected in parallel wi-

thout using an over-current protection device (fuses, etc.) 
incorporated in series within each string. Three or more 
strings can be connected in parallel if an appropriate and 
certified over-current protection device is installed in se-
ries with each string.

·  Only modules with similar electrical parameters should 

be connected in the same string to avoid or minimize mis-
match effects in arrays.

·  To minimize risk in the event of an indirect lightning strike, 

avoid forming loops with the wiring when designing the 
system.

·  The recommended maximum series fuse rating is stated 

in table 1 in the Annex A.

·  Modules should be safely fixed to bear all expected loads, 

including wind and snow loads. 

·  After the installation of double glass modules, a maximum 

40 mm deflection for frameless module, and a 30 mm 
deflection for framed module is allowed.

·  For frameless modules, a minimum clearance of 10 mm 

(0.394 in) or more between modules is required to allow 
the thermal expansion of the modules. The clearance is 
measured from one plastic corner protector to the adja-
cent plastic corner protector.

·  For framed modules, a minimum clearance of 6.5 mm (0.25 

in) between modules is required to allow thermal expansi-
on of the frames and modules. 

OPTIMUM ORIENTATION AND TILT  

·  To maximize the annual yield, please calculate the opti-

mum orientation and tilt for PV modules in that specific 
installation site. The highest yields are achieved when sun-
light shines perpendicularly onto the PV modules. 

AVOID SHADING 

·  Even minor partial shading (e.g. from dirt deposits) re-

duces the yield. A module can be considered to be unsha-
ded if its entire surface is free from shading all year round. 
Sunlight should be able to reach at least the front side of 
the module even on the shortest day of the year.

·  For optimizing the power generation of the rear side of 

bifacial modules, obstacles between modules and the 
mounting ground should be avoided as much as possible.

·  Constant shading conditions can affect module service 

lifetime, due to accelerated ageing of the encapsulation 
material and thermal stress on the bypass diodes.

RELIABLE VENTILATION

·  Bifacial modules use direct, reflected, or diffuse sunlight 

on the backside to generate additional power. Therefore, 
bifacial modules are not suggested to be used in building 
attached photovoltaic systems (BAPV). If BAPV, or similar 
mounting is still required, sufficient clearance of at least 
10 cm (3.94 in) between the module and the mounting 
surface needs to be provided to allow cooling air to circu-
late around the back of the module. This also allows con-
densation or moisture to dissipate.

·  According to UL 1703, if any other specific clearance re-

quired for maintaining a system fire rating should prevail. 

Содержание CS3U-MB-FG

Страница 1: ...1 INSTALLATION MANUAL OF BIFACIAL MODULE For professional use only...

Страница 2: ...NTING METHODS FOR FRAMELESS BIFACIAL MODULE CLAMPING 12 6 2MOUNTING METHODS FOR FRAMELESS BIFACIAL MODULE SINGLE AXIS TRACKERS 14 6 3 MOUNTING METHODS FOR FRAMED BIFACIAL MODULE BOLTING 15 6 4 MOUNTIN...

Страница 3: ...to property in connection with handling PV modules system installation or compliance or non compliance with the instructions set forth in this manual 2 0 SAFETY PRECAUTIONS Warning Before attempting t...

Страница 4: ...e fer tility or the unborn child causes damage to organs through prolonged or repeated exposure is very toxic to aquatic life with long lasting effects may cause cancer is very toxic to aquatic life a...

Страница 5: ...V module datasheet or nameplate label An assembly together with its overcurrent device s that is listed for continuous operation at 100 percent of its rating shall be permitted to be used at 100 perce...

Страница 6: ...ding to IEC 61730 2 please refer to the datasheet or the product nameplate for the detailed types Consult your local authority for guidelines and require ments for building or structural fire safety U...

Страница 7: ...uld be safely fixed to bear all expected loads including wind and snow loads After the installation of double glass modules a maximum 40 mm deflection for frameless module and a 30 mm deflection for f...

Страница 8: ...ort circuit current Isc differ substantially from the spe cifications this indicates that there is a wiring fault Do not connect different connectors brand and model together When modules have been pr...

Страница 9: ...400 mm 280 mm 1400 mm jumper cable Modules in adjacent rows should be rotated 180 degrees for proper installation Portrait installation one row Leap frog for single axis tracker CS3U Cable length 167...

Страница 10: ...sible to use standard grounding methods for certain module ranges CORRECT CONNECTION OF PLUG CONNECTORS Make sure that all connections are safe and properly mated The PV connectors should not be subje...

Страница 11: ...e cup washer concave side up between the frame and the wire 2 Then tighten the bolt using the toothed nut GROUNDING METHOD BOLT TOOTHED NUT CUP WASHER and UL 1703 a safety factor of 1 5 should be appl...

Страница 12: ...t shadow on the cells 3 Not to damage or scratch the surface of the glass 4 To ensure the clamps overlap the module by 13 mm to 15 mm 5 To ensure the minimum clamping clearance of the clamps 4 mm 6 To...

Страница 13: ...20 mm Maximum Load Uplift load 2400 Pa Downforce load 3600 Pa Use 6 clamps on the long side Mounting rails run parallel to the long side frame Use 4 clamps on the long side Mounting rails run perpend...

Страница 14: ...0 Pa Clamp length 200 mm A 390 20 mm Maximum Load Uplift load 2400 Pa Downforce load 5400 Pa 6 2 MOUNTING METHODS FOR FRAMELESS BIFACIAL MODULE SINGLE AXIS TRACKERS These mounting methods have been qu...

Страница 15: ...Clamp A A A A A A A A Tube Clamp Rail Clamp A A A A Tube Rail A A Use 4 clamps on the long side Mounting rails run parallel to the long side frame Mounting rails fixed on torque tube Clamp length 130...

Страница 16: ...nal mounting points should be used The system designer and the in staller are responsible for calculating the load and ensu ring that the support structure meets the requirements Modules should be bol...

Страница 17: ...limit as much as possible shade on module rear side cells Canadian Solar Inc s warranty may be void in cases where improper clamps or unsuitable installation methods are found When installing inter m...

Страница 18: ...s run perpendicular to the long side fra me Clamp length 40 mm A 270 380 mm C 10 2 mm Maximum Load Uplift load 2400 Pa Downforce load 3600 Pa Clamp length 80mm A 270 380 mm Maximum Load Uplift load 36...

Страница 19: ...Mounting rails fixed on torque tube tracker Two modules share one tube portrait installation Bolting on long frame side using 400 mm 1300 mm mounting holes as shown at arrow location Mounting rails ru...

Страница 20: ...rce load 2400 Pa A A Mounting Rail Clamp Use 2 long center clamps on the long side of each module or bolting on the center holes of the long side frame Overlap length of clamp and frame 400 mm Maximum...

Страница 21: ...st mounting holes Mounting rails run parallel to the long side frame Mounting rails fixed on torque tube tracker Overlap support length of between rail and frame A 730 mm Center distance between clamp...

Страница 22: ...M6 plain washer O D 18 mm 1300 mm 400 mm holes position Drawing No SF7 MR 04 039_Drbiku 1800Pa 30mm Uplift load 1800 Pa Downforce load 1800 Pa SF7QG 1500V en revision 1 0 CS3U MB AG CS3U PB AG Soltec...

Страница 23: ...uire cleaning rain will have a self cleaning effect If the module has become soiled it shall be washed with water and a non abrasive cleaning brush or sponge du ring the cool part of the day Do not sc...

Страница 24: ...and corner protector 24 3 kg 53 6 lbs CS3K 285MB FG 285 31 9 8 94 38 7 9 57 25 CS3K 290MB FG 290 32 1 9 04 38 9 9 65 25 CS3K 295MB FG 295 32 3 9 14 39 1 9 73 25 CS3K 300MB FG 300 32 5 9 24 39 3 9 82 2...

Страница 25: ...310PB FG 310 33 1 9 37 39 7 9 81 25 CS3K 315PB FG 315 33 3 9 46 39 9 9 89 25 CS3K 320PB FG 320 33 5 9 56 40 1 9 97 25 CS3K 325PB FG 325 33 7 9 65 40 9 10 21 25 CS3U 350PB AG 350 39 2 8 94 46 6 9 51 2...

Страница 26: ...ent Imp A Open Circuit Voltage Voc V Short Circuit Current Isc A Max Series Fuse Rating A Overall Dimension mm Weight Kg CS3W 420PB AG 420 39 5 10 64 48 0 11 26 25 CS3W 425PB AG 425 39 7 10 71 48 2 11...

Страница 27: ...covers the requirements for the cleaning pro cedure of Canadian Solar Inc s photovoltaic modules The purpose of these cleaning guidelines is to provide general information for cleaning Canadian Solar...

Страница 28: ...re that brushes or agitating tools are not abrasive to glass EPDM silicone aluminum or steel Conduct the cleaning activities avoiding the hottest hours of the day in order to avoid thermal stress on t...

Отзывы: