Canadian Solar CS Series Скачать руководство пользователя страница 8

12

ANNEX C: ALTERNATIVE MOUNTING METHODS

·

All the requirements of paragraph 6.0 should apply to the alternative mounting methods, unless otherwise specified.

·

Each Claw to Support, Claw to Claw, and Claw to module connection has been certified by UL to 120A. Determine the 

    quantity of strings that a bonding jumper connection can accommodate based on the module series fuse rating and 
    bonding jumper size as below. Verify that all devices used in connecting this bonding jumper can accommodate the 
    conductor being used.

C.1 MOUNTING METHOD A: CLAMPING

·
·

Top or bottom clamping methods will vary and are dependent on the mounting structures. Follow mounting 

    guidelines recommended by the mounting system supplier.

·

Each module must be securely fastened at a minimum of 4 points on two opposite sides. The clamps should be 

    positioned according to the authorized position ranges defined in table B-1. Install and tighten the module clamps to 
    the mounting rails using the torque stated by the mounting hardware manufacturer. System designer and installer are 
    responsible for load calculations and for proper design of support structure. 

·

Canadian Solar Inc. warranty may be void in cases where improper clamps or unsuitable installation methods are 

    found. When installing inter-modules or end type clamps, take measures so as:
      1.Not to bend the module frame
      2.Not to touch or cast shadow on the front glass
      3.Not to damage the surface of the frame
      4.To ensure the clamps overlap the module frame by at least 5 mm.
      5.To ensure the clamps overlap length is at least 40 mm.

·

Clamp material should be anodized aluminum alloy. Floating type 

    clamps are not authorized.

·

Clamp positions are of crucial importance for the reliability of the 

    installation, the clamp centerlines must only be positioned within 
    the ranges indicated in table C-1, depending on the configuration and load as verified by the test method in IEC 61215. 

·

For configurations where the mounting rails run parallel to the clamps installation side, precautions should be taken 

    to ensure the module frame (C-shape) overlap the rail by 15mm or more.

The mounting method has been qualified by Canadian Solar Inc and certified by CSA.

Table C-1: Authorized attachments for clamping method

Clamping on 

short side frame

Uplift load 

 2400 Pa

Downforce load 

 2400 Pa

Uplift load 

 2400 Pa

2400 Pa 

 Downforce load 

 5400 Pa

Use 4 clamps on the short side, the allowed 

range depends on the module type. Mounting 

rails may run parallel or perpendicularly to 

the short side frame

Use 4 clamps on the short side, the allowed 

range depends on the module type. An 

additional support bar should be placed 

below the module.

Mounting rails should run parallel to the 

short side frame

 

A2 

A2 

A2 

A2 

13

·

note

 from Canadian Solar for more information. Always follow safety procedures when installing any mounting system. 

Failure to follow SolarMount Rail System latest regulatory instructions will void Canadian Solar Inc. module warranty

Refer to the latest 

SolarMount Rail System installation manual

 from UNIRAC or to 

UL-SM_En-A0 Technical 

B.4 GROUNDING METHOD D: Grounding Middle Clamps

Used in conjonction with any Schletter module mounting rail (INTERTEK certified)

2+

Schletter Rapid  Grounding Clamps are used to create a grounding path 

    between the module frame and the mounting rail. An integrated grounding 
    pin ensures bonding to the module frame by penetrating the frame coating. 

2+

    The Rapid  Clamp includes integrated grounding as a standard feature.

2+

·

Rapid  Grounding Clamps arrive fully assembled and ready to use. The 

15

3

    clamps have overall dimensions of 100mm x 35.5mm (3 /  in x 1 /  in, 

16

8

    respectively length by width) and are rated to 10 AWG solid copper 
    conductor wire. 

·

To install, simply position the clamp over the mounting rail and insert the pointed clamp end into the rail groove. 

    Next, tighten the Rapid Grounding Clamp using a standard drill, using a torque of no more than 14.3 Nm (10.5 ft-
    lbs) to fasten the clamp hardware (M8x55 Torx and M8 nut). Use of a hammer drill is not recommended.

2+

·

There are always two Rapid  Grounding Clamps in contact with any given module, thus ensuring proper and 

    reliable bonding between the module frame and the mounting rail.  

·

    

2+

·

The quantity of Rapid  Grounding Clamps is determined solely by the 

    module layout. Clamp positions should be strictly determined according 
    to instructions provided in Annex C of this manual.

2+

·

Refer to 

Schletter Rapid  Clamp latest installation instructions

 for more 

    information and always follow safety procedures when installing any 

2+

    mounting system. Failure to follow Rapid  Clamp latest regulatory 
    instructions will void Canadian Solar Inc. module warranty.

B.5 GROUNDING METHOD E: Grounding for Grizzly Bear® FR Gen II SYSTEM

Only for PanelClaw Grizzly Bear® FR Gen II mounting system (INTERTEK certified)

·

   are certified under UL Subject 2703 to act as a module and racking equipment 
   grounding conductor (EGC) device. This certification allows for the Claw to 
   module and Claw to Support connection to serve the purpose of a copper EGC 
   that would typically run to each module and Support. When grounding devices 
   are installed according with the approved methodology and capacity below, 
   the connections described above meet all the requirements outlined in NEC 
   690.43.

All PanelClaw mounting attachments or “Claws” have been tested to and 

·

A Tyco solid wire grounding assembly, part number 2106831, manufactured by Tyco Electronics Corporation 

   has been pre-installed on each Grizzly Bear® Support. As you run the copper wire necessary to ground each module 
   (not provided), ensure the same copper wire is run through every Tyco solid wire grounding assembly and secured 
   per Tyco Electronics Corporation, LLC specifications (www.te.com). Tighten Tyco solid wire grounding assembly to 
   torque of 5.08 Nm (45 ft-lb).

·

Locating and Determining the Capacity of an EGC Bonding Jumper: Support locations within the array are 

   required to be electrically bonded to other DC grounding paths via the use of up to a #6AWG Cu bonding jumper and a 
   compatible UL 467 listed grounding device.

EN-Rev 2.3 Copyright     20

 Canadian Solar Inc.

12 Sep.

EN-Rev 2.3 Copyright     20

 Canadian Solar Inc.

12 Sep.

QUALITY  I  VALUE  I  INNOVATION  

QUALITY  I  VALUE  I  INNOVATION  

Содержание CS Series

Страница 1: ... 12657 Alcosta Blvd Suite 140 San Ramon CA 94583 Tel 1 925 866 2700 Fax 1 925 866 2704 Email inquire us canadiansolar com Japan Round Cross Shinjuku 5 Chome 8F 5 17 Shinjuku Shinjuku ku Tokyo Japan 160 0022 Tel 03 5291 8591 Fax 03 5291 8596 Email inquire jp canadiansolar com Korea 201 SK HUB Officetel 708 26 Yeoksam Dong Kangnam gu Seoul Korea Tel 02 539 7541 Fax 02 539 7505 Email inquire kr canad...

Страница 2: ...thes etc to prevent direct contact with 30VDC or greater and to protect your hands from sharp edges during the installation Use electrical insulated tools to reduce the risk of electric shock Remove all metallic jewelry prior to installation to reduce the chance of accidental exposure to live circuits Cover the front of the modules in the PV array with an opaque material to halt production of elec...

Страница 3: ...tand all expected loads including wind and snow loads A minimum clearance of 6 5 mm 1 4 of an inch or more between modules is required to allow for thermal expansion of the frames Small openings for water draining on the underside of the module should not be blocked after mounting Optimum orientation and tilt Find out the optimum orientation and tilt of the PV modules for your region to achieve th...

Страница 4: ...er from the specifications then there is a wiring fault Correct connection of plug connectors Make sure that the connection is safe and tight The plug connector should not receive outer stress The connector should only be used to connect the circuit It should never be used to turn the circuit on and off Use of suitable materials Use special solar cable and suitable plugs only wiring should be plac...

Страница 5: ...dditional mounting points should be used System designer and installer are responsible for load calculations and for proper support structure design Modules should be bolted at the following hole locations depending on the configuration and load as verified by the test method in IEC 61215 Table 6 1 Authorized attachments for bolting method Bolting on short side frame except for 6X series Uplift lo...

Страница 6: ... PX CS6P 245P PM PX CS6P 250P PM PX Model Type Maximum power Pmax W Max Series Fuse Rating A Weight Kg Overall Dimension mm Operating Voltage Vmp V Open Circuit Voltage Voc V Short Circuit Current Isc A Operating current Imp A 20 30 1602X1061X40 10 00 20 30 1602X1061X40 10 00 10 00 19 00 1638 982 40 3 00 3 00 2 40 534 350 25 2 40 534 350 25 5 00 5 00 10 00 10 00 5 10 608 666 35 5 10 608 666 35 6 5...

Страница 7: ... copper conductor wire and allow connecting the system to equipment ground connector Model Type Maximum power Pmax W Max Series Fuse Rating A Weight Kg Overall Dimension mm Operating Voltage Vmp V Open Circuit Voltage Voc V Short Circuit Current Isc A Operating current Imp A CS6P 255P PM PX CS6P 260P PM PX CS6P 265PM CS6P 270PM CS6P 275PM CS6A 160M CS6A 165M CS6A 170M CS6A 175M CS6A 180M CS6A 185M...

Страница 8: ...n manual from UNIRAC or to UL SM_En A0 Technical B 4 GROUNDING METHOD D Rapid2 Grounding Middle Clamps Used in conjonction with any Schletter module mounting rail INTERTEK certified 2 Schletter Rapid Grounding Clamps are used to create a grounding path between the module frame and the mounting rail An integrated grounding pin ensures bonding to the module frame by penetrating the frame coating 2 T...

Страница 9: ...clamps on the long side the allowed range depends on the module type Authorized range for clamping as a function of model type Model type CS5A CS5P CS6A CS6P CS5T CS6X A1 range mm 220 380 220 390 220 340 240 410 340 550 B1 range mm 330 400 330 400 270 330 340 410 410 490 A2 range mm 170 200 220 270 200 250 200 250 200 250 A1 A1 A1 A1 B1 B1 B1 B1 Mounting rails may run perpendicularly or parallel t...

Страница 10: ... used for PV modules that are not compatible with flange clamp style Claws The Long Claw attaches at the module mounting holes using standard bolting method Refer to paragraph 6 1 for suitable torque and fastening requirements Step 4 Mount Modules to Supports Step 5 Electrical Grounding Refer to B 5 GROUNDING METHOD E Grounding for Grizzly Bear FR Gen II SYSTEM for grounding assembly and requireme...

Отзывы: