Page 2 of 11

0 9 / 9 6

  INSTALLING THE FIREPLACE

The Econo Plus 36DV-RV clearances  to  combustible materials  are
0"  back, 1" sides, 0" floor and 4" top.  The Econo Plus 36DV-RV must
not be installed any closer than 8 inches to any unprotected
combustible wall perpendicular to the fireplace opening.

For protection against freezing temperatures, it is recommended  that
the outer walls of the chase be insulated with a vapour barrier.  This
will reduce the possibility of a cold-air convection current on the
fireplace.

THE FRAMING DIMENSIONS ARE SHOWN BELOW:

   INTRODUCTION

The Econo Plus 36DV-RV is rated at 16,000 BTUs. (4.16  Kilowatts)
for Natural & Propane gas.
The Econo Plus  warranty will be voided by, and Econo Plus
disclaims any responsibility for, the following actions:

- Modification of the fireplace and/or components including

Direct-Vent assembly or glass doors.

- Use of any component part not manufactured or approved by

Econo Plus in combination with a Econo Plus fireplace system.

- Installation other than as instructed in this manual.

Consult your local Gas Inspection Branch about the particular
requirements concerning installation of factory-built gas fireplaces.
Installation & repairs should be done by a qualified  contractor,
and installation must conform with the current CAN/CGA
B-149.1 and .2 Gas Installation Code and local regulations.

  

CAUTIONS

  * Due to its high operating temperatures, the appliance should  be

located out of traffic & away from furniture and draperies.

  * Children and adults should be alerted to the hazards of the high

surface temperature, which could cause burns or clothing ignition.

  * Young children should be carefully supervised when they are in

the same room as the appliance.

  * Clothing or other flammable materials should not be placed on

or near the appliance.

  SELECTING YOUR FIREPLACE LOCATION

The fireplace may be installed in any location that is free of air
condition ducts, electrical wiring and plumbing.  Safety, as well as
efficiency of operation, must be considered when selecting the
fireplace location.  Try to select a location that does not interfere
with room traffic, has adequate ventilation, and offers an accessible
pathway for Direct Vent & Combustion Air Kit installation.

The fireplace dimensions are shown below:
NOTE:  SEE FIGURE 2 FOR FRAMING DIMENSIONS

FIGURE 1.  FIREPLACE DIMENSIONS

19

16 1/4

10 1/4

37 1/2

3 3

39 1/2

17

36

25 1/2

12

12

37 1/2

12

12

36

25 1/2

17

37 1/2

FIGURE 2.  FRAMING DIMENSIONS

37 1/2

59

16 1/4

19

12

42

Содержание Econo-Plus 36DV-RV

Страница 1: ...BEFORE INSTALLING MODEL ECONO PLUS36DV RV ECONO PLUS36DV RV FOR YOUR SAFETY FOR YOUR SAFETY IF YOU SMELL GAS 1 OPENWINDOWS DONOTSTOREORUSEANYFLAMMABLE 2 DON TTOUCHELECTRICALSWITCHES VAPOURSORLIQUIDSN...

Страница 2: ...y builtgasfireplaces Installation repairs should be done by a qualified contractor andinstallationmustconformwiththecurrentCAN CGA B 149 1 and 2 Gas Installation Code and local regulations CAUTIONS Du...

Страница 3: ...tion Code After gas line is connected it is a CAN CGA B149 1 2 code requirement Section 8 25 3 e that each appliance connection valve valve train shall be checked while under normal operating pressure...

Страница 4: ...UTIONS AND REQUIREMENTS 2 Extended vent kit For extended vent use a stucco frame 20 extended vent and a termination Note 20 kit may be cut to desired length but must never exceed 20 see figure 6 ETK 5...

Страница 5: ...linterferewith the access to retainers for removal of glass panel and combustion door NOTE National Canadian Gas Association mantel test requirements are for fire hazard prevention to combustible mate...

Страница 6: ...o install simply place log A s rectangular shaped extension into the log mounting slot located on rear wall of the burner assembly Place log B onto front log slots Place log C and log D onto pins on t...

Страница 7: ...be cleaned periodically Film can easily be removed by removing inner and outer doors handling carefully and cleaning with normal liquid household products WARNING Do not attempt to clean glass when h...

Страница 8: ...denial of certification by recognized national safety agencies and could be in violation of local building codes This warranty does not cover any damages occurring from the use of any components not m...

Отзывы: