29
INST
BLOW PRET
–
READ ONLY
– Duraiton of the blower pre-purge cycle.
Default: 5 seconds
INST
BLOW PRER
–
READ ONLY
– Blower modulaiton rate during pre-purge.
Default: 50%
INST
BLOW POST
–
READ ONLY
– Duraiton of the blower post-purge cycle.
Default 30 seconds
INST
BLOW POSR
–
READ ONLY
– Blower modulaiton rate during post-purge.
Default: 50%
INST
MIN MOD
–
Minimum blower modulation speed, as percent of full firing rate.
Set at factory.
INST
START MOD
–
Blower modulaiton speed at light off. Set at factory.
INST
MAX MOD
–
Maximum blower modulation speed, as percent of full firing
rate. Set at factory.
INST
FLAME CURRENT
– READ ONLY – Actual real-time flame sensor reading,
varies form 0.5 to 5.0.
INST
IGN TYP
–
READ ONLY
– Not used,
MOD
(or “modulating blower”) is the
only option.
BLOW PRET
0:05
BLOW PRER
50
MIN MOD
20
START MOD
45
MAX MOD
100
FLAME CUR
0.0
IGN TYP
MOD
BLOW POST
0:30
BLOW POSR
50