22
8.3
CONTROL DEVICES
Ignition Module
There is one ignition module provided per burner. The ignition module is mounted on a rail just behind the
outer jacket front access door. The ignition module provide ignition sequence, flame monitoring and
safety shutoff for the pilot.
Fan Manager
There is one fan manager provided in the control box per fan. The fan manager provides start and stop
time delay for pre-purge and post-purge duties.
8.4
MODE 1 & 2: SETPOINT OPERATION: VIEW DISPLAY
From the Home display;
1) Press [ITEM] to view the following parameters:
Display
Parameter
Name
Parameter Description
Parameter
Range
Boiler
System
Temperature
(Mode 2
ONLY)
Real-time System Temperature to
Boiler
14 to 266
o
F
(-10
to 130
o
C)
Boiler Outlet
Temperature
Real-time Outlet Temperature to Boiler
14 to 266
o
F
(-10
to 130
o
C)
Boiler Inlet
Temperature
Real-time Inlet Temperature to Boiler
14 to 266
o
F
(-10
to 130
o
C)
Boiler Delta
T
Real-time temperature difference
between the outlet sensor and the inlet
sensor.
-99 to 252
o
F
(-72 to 140
o
C)
Total Run
Time Since
Installation
Monitors the amount of operational
time since the unit was installed. The
two digits are the thousands of hours
and the three digit display shows the
hundreds of hours.
Press
simultaneously to reset
the counter
Alternates
between 00 and
999
Содержание MICOFLAME GRANDE Series
Страница 2: ......
Страница 4: ......
Страница 20: ...16 Figure 7 Typical Heating System ...
Страница 21: ...17 Figure 8 Typical Low Water Temperature System Figure 9 Typical Instantaneous Water System ...
Страница 47: ...43 ...
Страница 48: ...44 ...
Страница 49: ...45 16 EXPLODED VIEW MicoFlame Grande ...
Страница 50: ...46 EXPLODED VIEW MicoFlame Grande Outdoor and or Condensing ...
Страница 51: ...47 MicoFlame Grande Control Box ...