28
Differential
Temperature
To provide a modulation rate above
and below the Boiler Target
temperature. For example, if the
value is 10
o
F and the Boiler Target is
160
o
F the boiler will begin to
modulate at 150
o
F and shut off at
170
o
F.
Au, 2 to 42
o
F
(Au, -16 to 5
o
C)
Default = 10
o
F
Stage
Differential
Dictates the staging of the boiler and
each stage is iterative. For example,
if the value is 3
o
F. Stage 1 will be
active 3
o
F below setpoint, Stage 1 &
2 will be active 6
o
F below setpoint.
Au, 2 to 42
o
F
(Au, -17 to 6
o
C)
Default = 10
o
F
On Delay
Interstage delay to activate the next
stage
0:10 to 8:00
minutes
Default = 1:00
minute
Minimum On
Time
Minimum on time for each stage
0:10 to 5:00
minutes
Default = 0:30
minute
Minimum Off
Time
Minimum off time for each stage
0:10 to 5:00
minutes
Default = 0:50
minutes
Pump Delay
Boiler post pump time after burner
has shut off, in seconds.
OFF, 0:20 to 9:55
min, On
Default = 1:00
min
Warm
Weather
Shutdown
Temperature
Warm weather shutdown
temperature using outdoor reset.
35 to 105
o
F, OFF
(2 to 41
o
C, OFF)
Default = 0:20
min
Temperature
Units
Select the desired unit of
measurement
o
F,
o
C
Default =
o
F
Содержание MICOFLAME GRANDE Series
Страница 2: ......
Страница 4: ......
Страница 20: ...16 Figure 7 Typical Heating System ...
Страница 21: ...17 Figure 8 Typical Low Water Temperature System Figure 9 Typical Instantaneous Water System ...
Страница 47: ...43 ...
Страница 48: ...44 ...
Страница 49: ...45 16 EXPLODED VIEW MicoFlame Grande ...
Страница 50: ...46 EXPLODED VIEW MicoFlame Grande Outdoor and or Condensing ...
Страница 51: ...47 MicoFlame Grande Control Box ...