5
Replace any damaged gasket. Note that the burner is
supplied with two gaskets; a high temperature ceramic
paper gasket under the burner flange and a stamped
silicon gasket between the burner flange and fan
flange. Tighten fan flange mounting nuts to 20 ft-lb.
6. Restore electrical power and gas supply to appliance.
7. Place appliance in operation using lighting instructions
provided.
8. Confirm proper operation of all safety devices
9. Check for gas leaks and proper vent operation.
NOTE:
Experience has shown that improper installation or
system design, rather than faulty equipment, is the
cause of most operating problems
1.9
BOILER ROOM OPERATING CONDITION
•
Due to low jacket losses from the appliance,
temperatures in typical boiler room may drops
significantly; supplemental heat is required to maintain
ambient temperature at minimum of 50ºF.
•
Cold fresh air intakes must be located to minimize the
effects on venting and subsequent condensation in the
flue of Category I installations. When necessary,
consider the use of insulation or corrosion resistant
venting material.
1.10
INSTALLATION PROCEDURE LOCATION
OF UNIT
Install this appliance in a clean, dry location with adequate
air supply and close to a good vent connection.
•
Do not locate this appliance in an area where it will be
subject to freezing unless precautions are taken.
Radiant losses from the DynaFlame are minimal and
should not be relied on to keep the appliance room
warm. If the appliance is installed in a cold room and/or
on a cold floor, isolating the appliance from the cold
floor and heating the room is recommended.
•
The appliance
must not
be installed on carpeting and
should be located close to a floor drain in an area
where leakage from the appliance or connections will
not result in damage to the adjacent area or to lower
floors in the structure,
it is recommended that a
suitable drain pan, adequately drained, be installed
under the unit. Under no circumstances is the
manufacturer to be held responsible for water damage
in connection with this unit, or any of its components.
•
If the appliance is installed above the level of the
building’s radiation system, a low water cut-off device
must be installed in the appliance outlet at a minimum
of 3 ft (1M) above the heat exchanger inlet/outlet
connections. Some local codes require the installation
of a low water cut-off on all systems
•
When placing the appliance be aware that a minimum
clearance of 24” must be provided at the front to allow
easy access to the primary heat exchanger. Non-
condensing units do not require access through both
sides and could be placed adjacent to each other with
zero clearance. For condensing units a minimum
clearance of 12” must be provided on the right side for
access to the Condensing Heat Recovery Module.
•
The appliance must be installed so that the ignition
system components are protected from water
(dripping, spraying, etc.) during appliance operation
and service (circulator replacement, control
replacement, etc.)
•
Appliances located in a residential garage and in
adjacent spaces that open to the garage and are not
part of the living space of a dwelling unit must be
installed so that all burners and burner ignition devices
have a minimum clearance of not less than 18" (46cm)
above the floor. The appliance must be located or
protected so that it is not subject to physical damage
by a moving vehicle.
•
DO NOT
install this appliance in any location where
gasoline or flammable vapors are likely to be present.
•
Appliance must be installed on a level floor. Maintain
required clearances from combustible surfaces.
•
The appliance designed for indoor installation (Indoor
Models) must be installed indoors where it is protected
from exposure to wind, rain and weather.
•
The appliance designed for outdoor installation
(Outdoor Models) must be installed outdoors. For
outdoor installations, always consider the use of a
shelter such as a garden shed in lieu of direct
exposure of the appliance to the elements. The
additional protection afforded by the shelter will help to
minimize nuisance problems with electrical
connections and will allow easier servicing of the
appliance under severe weather conditions.
1.11
Clearance from Combustible Material
This appliance is suitable for alcove (a closet without a
door) installation with minimum clearances to combustibles
as follows:
Table 1
Clearances from Combustibles
TOP: 12”
SIDES: 12”
REAR: 12”
VENT: 6”
When placing the appliance be aware that a minimum
clearance of 24” (60cm) must be provided at the front to
allow easy access to the primary heat exchanger.
NOTE:
Clearances from combustible construction are
noted on the appliance rating plate
Maintain minimum specified clearances for adequate
operation. All installations must allow sufficient space for
servicing the vent connections, water pipe connections,
circulating pump, bypass piping and other auxiliary
equipment, as well as the appliance
Содержание DFH500
Страница 31: ...28 PART 9 TROUBLE SHOOTING ...
Страница 32: ...29 ...
Страница 39: ...36 PART 12 EXPLODED VIEW ...
Страница 40: ...37 ...
Страница 41: ...38 ...
Страница 46: ...43 PART 13 ELECTRICAL DIAGRAMS ...
Страница 47: ...44 ...
Страница 48: ...45 ...
Страница 49: ...46 ...
Страница 50: ...47 ...
Страница 51: ...48 ...