CPS-i2000(R2) MANUAL
C/V Chart and Operating Point
The output voltage set Vout is always linear proportional to the control signal
Ureg.
The desired control signal is selected via the DIP switcher:
0-5V, 0-10V, 0-20mA oder 4-20mA.
Model
Value UA1 (V)
Value IA1 (A)
Value UA2 (V)
Value IA2 (A)
Pmax (IA1/IA2)
CPS-i2000.018
18Vdc
110A
12Vdc
165A
1980/1980W
CPS-i2000.030
30Vdc
66,7A
20Vdc
100A
2001/2000W
CPS-i2000.060
60Vdc
33,3A
40Vdc
50A
1998/2000W
CPS-i2000.090
90Vdc
22,2A
60Vdc
33A
1998/1980W
CPS-i2000.150
150Vdc
13,3A
100Vdc
20A
1995/2000W
Inrush Current Limiter (electronic)
The power supply unit has an electronic current
limiter (230Vac=14,6A
rms
/20,7A
peak
).
It is a precisely working circuit instead of a usual
simple NTC solution. The accuracy is ±10%,
regardless of the operating temperature and the
duty cycles (interval
≥
10s). We recommend the
smallest circuit breaker a characteristic B with 16A.
Temperature Monitoring & Derating
The maximum ambient temperature during
operation is + 60°C. If the overtemperature
protection is activated, the power supply but
not the fan is switched off.
The measuring point is 50mm outside the
power supply at the front side (fan/blower
input). The power supply unit starts
automatically when it has cooled down.