Manual und Technical Details 

 

Analog Interface CON1 (Connector Model Weidmueller 1277320000 = included) 

Pin 

Name 

Type 

Function 

Signal 

Remarks 

AC OK-1 

Output 

Closers, Signal AC OK 

Relay 

Potential-free 

DC OK-1 

Output

 

Closers, Signal DC OK

 

Relay

 

Potential-free

 

AC OK-2 

Output

 

Center, Signal AC OK

 

Relay

 

Potential-free

 

DC OK-2 

Output

 

Center, Signal DC OK

 

Relay

 

Potential-free

 

AC OK-3 

Output

 

Break, Signal AC OK

 

Relay

 

Potential-free

 

DC OK-3 

Output

 

Break, Signal DC OK

 

Relay

 

Potential-free

 

SB 

Input 

Control Signal Standby

 

Switch / Open Collector 

 

SD 

Input 

Control Signal Shutdown 

Switch / Open Collector 

 

DGND 

Digital Ground 

 

10 

+12V AUX 

Output 

Auxiliary Voltage 

12Vdc/0,5A ±0,5V 30mVpp 

1000uF, O-Ring Diode 

11 

DGND 

Digital Ground 

 

12 

INH 

Input 

Control Signal Inhibit (Interlock) 

Switch 

 

Analog Interface CON2 (Connector Model Weidmueller 1277330000 = included) 

Pin 

Name 

Type 

Function 

Signal 

Remarks 

DGND 

Digital Ground 

 

TEMP 

Output 

Temperature Control

 

Voltage 10mV/°C 

 

DGND 

Digital Ground

 

 

NC 

NC

 

Not Connected

 

 

No Function 

DCF 

Output

 

Signal DC Failure

 

Open Collector 

 

ACF 

Output

 

Signal AC Failure

 

Open Collector 

 

FF 

Output

 

Signal Fan Failure

 

Open Collector 

 

INH 

Output

 

Signal Inhibit Active 

Open Collector 

 

OT 

Output

 

Signal Over Temperature 

Open Collector 

 

10 

TA 

Output

 

Signal Temperature Alarm 

Open Collector 

Early warning 

11 

OCP 

Output

 

Signal Over Current Protection 

Open Collector

 

 

12 

CC 

Output

 

Signal Constant Current Mode 

Open Collector

 

 

13 

OVP 

Output

 

Signal Over Voltage 

Open Collector

 

 

14 

CV 

Output

 

Signal Constant Voltage Mode 

Open Collector 

 

Analog Interface CON3 (Connector Model Weidmueller 1277340000 = included) 

Pin 

Name 

Type 

Function 

Signal 

Remarks 

AGND 

Analog Ground 

 

Imon 

Output

 

Current Monitor

 

0-5Vdc / 5mA 

 

NC 

NC

 

Not Connected

 

 

No Function 

Umon 

Output

 

Voltage Monitor

 

0-5Vdc / 5mA 

 

CS 

I/O

 

Current Share Bus (CSB)

 

Parallel Operation 

Bidirectional 

Ireg-OUT 

Output

 

Current Programming Slave

 

0-5V / 5mA 

 

AGND 

-

 

Analog Ground

 

 

Ureg-OUT 

Output

 

Voltage Programming Slave 

0-5V / 5mA 

 

AGND 

-

 

Analog Ground

 

 

10*

 

Iadj 

Output

 

Potentiometer Connection Current 

 

With external poti 

11 

Uref 

Output

 

Reference Voltage 

5,2Vdc / 5mA 

 

12*

 

Uadj 

Output

 

Potentiometer Connection Voltage 

 

With external poti 

13 

CS 

I/O

 

Current Share Bus (CSB) 

Parallel Operation 

Bidirectional

 

14 

Ireg-IN 

Input

 

Current Programming 

0-5V 

 

15 

AGND 

-

 

Analog Ground 

 

16 

Ureg-IN 

Input 

Voltage Programming 

0-5V 

 

Analoge Interface CON4 (Connector Model Weidmueller 1277290000 = included) 

Pin 

Name 

Type 

Function 

Signal 

Remarks 

Sense - 

Input 

Sense Connection 

2V / load line 
 

Sense - 

Input 

Sense Connection

 

-

 

3, 4 

 

 

NC 

Must not be connected

 

5, 6 

 

 

NC 

Sense + 

Input

 

Sense Connection

 

-

 

2V / load line 
 

Sense + 

Input

 

Sense Connection

 

-

 

PIN10/12*

 

when

 

no external control signal shall be used the device can be set with internal potentiometers. Please connect 

Pin10 with Pin14 and Pin12 with Pin16 to operate this mode. 

 

Содержание 3041110002CA

Страница 1: ... Heat Dissipation Real time I V programming Real time I V monitoring Reference voltage f autonomous programming CSB Current Share Bus Inhibit for safe interlocking Remote Shutdown Sense mode Power Good Relay DC ok Precise dynamics on load change Series parallel operation up to 100kW EMC conducted class B radiated class A Efficiency 92 94 PFC Powerfactor 0 99 Variable controlled fans from Papst Lon...

Страница 2: ...ghest standards of safety and interference suppression The device was developed in accordance with the requirements of EN61010 1 EN61010 2 201 EN62368 1 and the EMC standards EN55032 conducted Class B radiated Class A The mechanical design of the CPS EX2000 device series is unique It is the first power supply line in the world market which can be flexibly adapted to any installation situation The ...

Страница 3: ...ect load The lock can be controlled remotely or repeal by disconnection from the mains again Continuous Mode The unit can be operated in continuous mode In the continuous mode the power supply provides constant current mode in a continuous flow and no ticker operation Master Slave Mode Ureg OUT Ireg OUT The master slave mode can be defined in the parallel operation One device can be set as the mas...

Страница 4: ...over all Accuracy Ureg 0 5 Ireg 1 Umon 0 5 Imon 1 Uref 1 Temperature Control yes thermal shutdown autorecovery 70 C outside measuring point distance 10mm Hold Up Time 30ms 230Vac mains buffering at full load Inrush Current 14 6Aeff 20 7Apeak 230Vac active electronic inrush protection no simple NTC Startup Delay typ 1s Softstart typ 100ms Ambient Temperature 20 C 60 C operating derating 2 5 C 50 C ...

Страница 5: ...ailure Open Collector 8 INH Output Signal Inhibit Active Open Collector 9 OT Output Signal Over Temperature Open Collector 10 TA Output Signal Temperature Alarm Open Collector Early warning 11 OCP Output Signal Over Current Protection Open Collector 12 CC Output Signal Constant Current Mode Open Collector 13 OVP Output Signal Over Voltage Open Collector 14 CV Output Signal Constant Voltage Mode Op...

Страница 6: ...7 01 3 Tel 49 721 46596 0 Fax 49 721 46596 77 www camtec gmbh com info camtec gmbh com Subject to alterations This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death Schematic of the internal circuits CON1 4 NC NC ...

Страница 7: ...60 C 250Vac 20A Neutrik PowerCon 3x2 5 mm Neutrik NAC3FCA Copy of the original instruction http www neutrik com de powercon powercon 20 a nac3fca Interface pluggable Push Pull Connectors from Weidmueller included Input Power Connector Neutrik NAC3FCA included Output Power Connection M8 Powerbars Lock Pins snap into the 2U 3U 19 subrack WARNING OUTPUT CONNECTION INSTRUCTION Mount the cable lugs dir...

Страница 8: ...usted analog control signal The monitor signal is analog linear to the output voltage The monitor signal for current and voltage is the real value that is measured directly at the output of the power supply If a sense line is connected to compensate for the voltage drop across the load lines the monitor signal is exactly the value that is measured at the connection point of the sense line The desc...

Страница 9: ...y To avoid interference twist the sense lines To reduce inductive effects we recommend that the load lines position is close to each other To supply a pulsating load the use of an electrolytic capacitor and a cermic capacitor has proved The internal Over Voltage Protection OVP of the power supply controls the DC power directly to the DC output terminals In case of an error the OVP acts automatical...

Страница 10: ... message An uneven load and thus premature aging of the participating devices is prevented Connect CON3 contact 5 CS to contact 13 of the slave Are other devices involved in the parallel operation you may grind the CS bus through from unit to unit The current division between the devices will be performed automatically The accuracy of the current distribution is 5 at Iout 0 5 x Iout max Derate the...

Страница 11: ...uxiliary Voltage 12V AUX The power supply offers an auxiliary voltage 12V 500mA The accuracy is 500mV Ripple Noise 30mVpp The auxiliary voltage is not affected by the control signals Standby SB Shutdown SD and Inhibit INH and remains always active Between auxiliary voltage and the power output is a reinforced Isolation of max 400Vdc and a basic isolation of max 600Vdc working voltage DC OK Relay D...

Страница 12: ...en Collector IMAX 10mA VLOW 0 6V VMAX 30V When OVP INH SB SD FF OCP OT or defective PFC occur the mes sage signal CC is low because the power output is switched off The change between the CV and the CC mode is automatic Please pay attention to the DIP switch setting of the Fuse Mode to avoid provoking malfunction CC Mode Over Current Protection in the Fuse Mode OCP The alarm signal OCP is high whe...

Страница 13: ...r proportional to the control signal Ureg The desired control signal is selected via the DIP switcher 0 5V 0 10V 0 20mA oder 4 20mA Model Value UA1 V Value IA1 A Value UA2 V Value IA2 A Pmax IA1 IA2 CPS EX2000 024 30Vdc 66 7A 24Vdc 84A 2001 2016W CPS EX2000 036 45Vdc 44 4A 36Vdc 56A 1998 2016W CPS EX2000 048 58Vdc 34 5A 48Vdc 42A 2001 2016W CPS EX2000 072 90Vdc 22 2A 72Vdc 28A 1998 2016W CPS EX200...

Страница 14: ...internal components used only the models with an output voltage of 48Vdc and later are approved for series operation Other power supplies are not approved for series operation above 60Vdc If the units are remotely controlled via the analog interface it is compulsory to use a potential free control voltage Parallel Operation N 1 Decoupling To increase the overall power of the power supply up to 5 u...

Страница 15: ...l Germany P 15 21 07 2017 01 3 Tel 49 721 46596 0 Fax 49 721 46596 77 www camtec gmbh com info camtec gmbh com Subject to alterations This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death ...

Страница 16: ...ting damage can happen to the power supply unit For the field test owner follow the below instruction a Use suitable test equipment raising the voltage slowly b Short circuit L1 and N and all the DC output terminals c Use only test voltages of 50 60Hz The outputs are unearthed and therefore they have no resistance to GND PE d If the residual voltage is 60Vdc observe the safety standards Use only s...

Страница 17: ...result in injury or death Mechanics Aluminium housing IP20 Cooling is achieved via front to rear fans To ensure adequate heat dissipation 50mm to the front and 150mm blockade free distance from the device back wall must be guaranteed The harnesses are to be designed and installed to that the air outlet of the unit is not being blocked In a rack mounting of multiple subracks the rear distance of th...

Страница 18: ...ww camtec gmbh com info camtec gmbh com Subject to alterations This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death 19 Subrack 2U 3U 2U Subrack for 1 3 CPS EX2000 with up to 6kW continuous power 3U Subrack for 1 5 CPS EX2000 with up to 10kW continuous power ...

Страница 19: ...to custom design power supplies Steplessly hard mount of the CPS EX2000 3000 power supply modules in a 3D room In practice that means that one can mount the modules into every angle imaginable Our 3D Heat Dissipation 3D HD ensures optimal cooling in each mounting position you may consider All you may consider is to make sure that at least a distance of 5cm 2 Inch to the front cooling slots and 15c...

Страница 20: ...on Article Number CPS EX2000 024 R2 24Vdc model incl analogue interface 3041110002CA CPS EX2000 036 R2 36Vdc model incl analogue interface 3041110003CA CPS EX2000 048 R2 48Vdc model incl analogue interface 3041110004CA CPS EX2000 072 R2 72Vdc model incl analogue interface 3041110005CA CPS EX2000 110 R2 110Vdc model incl analogue interface 3041110006CA Certifcate Calibration Separate works certific...

Страница 21: ...bolts or operation outside the specified herein specification or in an unsuitable environment has the immediate loss of warranty to follow We disclaim any responsibility for any resulting damage to persons or things 4 Note The device must not be operated without an upstream circuit breaker CB We recommend the use of B Type 16A It is prohibited to use the unit without PE It may be necessary upstrea...

Отзывы: