Electrical Safety (Factory-Test / Field-Test Owner)
¹)
≥
48Vdc= 2800Vdc
Type and factory test are the manufacturer. While repeating damage can
happen to the power supply unit. For the field test (owner) follow the below instruction:
a)
Use suitable test equipment, raising the voltage slowly
b)
Short circuit L1 and N, and all the DC output terminals.
c)
Use only test voltages of 50/60Hz. The outputs are unearthed and
therefore they have no resistance to GND/PE.
d)
If the residual voltage is
≥
60Vdc, observe the safety standards.
Use only specially insulated screwdriver to trim the Ua/Ia.
ANALOGUE INTERFACE
T
A
B
C
1
)
D
E
Type Test
60s
2500Vac
3000Vac
500Vdc
3000Vac
500Vdc
Factory Test
5s
2000Vac
2000Vac
500Vdc
1000Vdc
500Vdc
Field Test
2s
2000Vac
2000Vac
500Vdc
1000Vdc
500Vdc
Cut-off current setting >25mA
>25mA
>1mA
>1mA
>1mA