CS115 Barometric Pressure Sensor

5

4.  Wiring

The CS115 wiring instructions for the example programs are shown in
Table 4-1.  For dataloggers CR500, CR510, CR10(X), CR23X, and CR5000,
analog channel is used for period averaging measurement.  For CR7, 21X and
CR9000 pulse channel is used for pulse count measurement.

TABLE 4-1.  Wiring for Example Programs

Wire Color

Description

CR10(X)

CR23X

21X

CR5000

Green

Frequency Out

SE6

SE24

P1

SE33

Red

Supply  (12Vdc)

12V

12V

12V

12V

Black

Power Ground

G

G

G

Yellow

Signal Ground

AG

Blue

External Trigger

C8

C1

C6

C1

Clear

Shield

G

G

G

5.  Programming

There are two ways to measure the output of the CS115.  The preferred way is
to use the period averaging instruction available with the CR500, CR510,
CR10(X), CR23X and CR5000 dataloggers.  This instruction determines the
period of the output signal averaged over a user-specified number of cycles and
outputs it in kHz.

If you have a datalogger that does not support the period averaging instruction
(e.g., 21X, CR7 or CR9000), a pulse count instruction can be used to measure
the CS115.

Atmospheric pressure changes little with time.  In most weather station
applications measuring pressure once an hour is adequate.

In Example 1, the datalogger turns on the CS115 one minute before the top of
the hour with a control port.  As in the example, the execution interval 

must

 be

one minute or less.  The datalogger measures the CS115 on the hour, and then it
turns the CS115 off.

In Example 2, the CS115 is measured every execution interval.  The datalogger
turns the CS115 on and waits two seconds for it to warm up before the
measurement is made.  The execution interval 

must

 be long enough to

accommodate the two-second warm-up delay plus all the other measurements
and processing instructions in the program.

Example 3 resembles Example 1 in every way, but it is for the CR23X.

In Example 4, the CR5000 measures the CS115 once an hour in a program that
runs at 10 Hz.  With the CR5000, the period averaging instruction has to be
executed every scan and cannot be inside the “If” statement.  The measured
value, therefore, is first written into a temporary variable called "CS115_Freq".

Содержание CS115

Страница 1: ...INSTRUCTION MANUAL CS115 Barometric Pressure Sensor 3 03 C o p y r i g h t c 2 0 0 2 2 0 0 3 C a m p b e l l S c i e n t i f i c I n c...

Страница 2: ...l other warranties expressed or implied including warranties of merchantability or fitness for a particular purpose CAMPBELL SCIENTIFIC INC is not liable for special indirect incidental or consequenti...

Страница 3: ...Period Averaging Measurement Example for CR10 X 7 5 1 2 Period Averaging Measurement Example for CR10 X in a Slow Executing Program 8 5 1 3 Period Averaging Measurement Example for CR23X 9 5 1 4 Perio...

Страница 4: ...This is a blank page...

Страница 5: ...cting as a pressure sensitive diaphragm and the other acting as a resonator Pressure variations deflect the sensitive diaphragm and change the sensor s resonant frequency The resonant frequency is mea...

Страница 6: ...rnal Trigger Voltages ON 1 to 24 VDC OFF 0 VDC Warm up Time 2 seconds 40 C to 60 C EMC Compatibility Emissions BS EN50081 1 Immunity BS EN61000 6 2 2 3 Physical Dimensions Main Box 2 36 x 2 36 x 1 15...

Страница 7: ...rmanent damage If it is necessary to make a vent hole on the outer wall of an enclosure do not make the hole on one of the vertical side walls as wind blowing around it can cause transient changes in...

Страница 8: ...atalogger s control port In this mode power consumption is minimized but the sensor is subject to a 2 second warm up delay after it is turned on You can also configure the unit for the continuous mode...

Страница 9: ...truction e g 21X CR7 or CR9000 a pulse count instruction can be used to measure the CS115 Atmospheric pressure changes little with time In most weather station applications measuring pressure once an...

Страница 10: ...accumulator Therefore Pulse Input channel 2 cannot be used You can also choose to use Pulse Input channel 3 in which case Pulse Input channels 4 will be combined with Pulse Input channel 3 to form a 1...

Страница 11: ...et Port 8 High Measure CS115 at the top of the hour 2 If time is P92 1 0 Minutes Seconds into a 2 60 Interval same units as above 3 30 Then Do 3 Period Average SE P27 1 1 Reps 2 14 200 kHz Max Freq 2...

Страница 12: ...0 X in a Slow Executing Program EXAMPLE 2 Sample Program for CR10 X CR10X Table 1 Program 01 10 Execution Interval seconds Turn on CS115 1 Do P86 1 48 Set Port 8 High Give 2 second delay for CS115 to...

Страница 13: ...utines End Program Input Locations 1 P_mb Proper entries will vary with program and datalogger channel and input location assignments 5 1 3 Period Averaging Measurement Example for CR23X EXAMPLE 3 Sam...

Страница 14: ...Do P86 1 51 Set Port 1 Low 5 End P95 6 If time is P92 1 0 Minutes Seconds into a 2 60 Interval same units as above 3 10 Set Output Flag High Flag 0 7 Real Time P77 1 0110 Day Hour Minute midnight 000...

Страница 15: ...r If IfTime 59 60 min Then WriteIO 1 1 Period Avgeraging instruction must be executed every scan and cannot be inside the If statement The measured value therefore is first written into a temporary va...

Страница 16: ...If time is P92 1 0 Minutes into a 2 60 Minute Interval 3 30 Then Do 3 Pulse P3 1 1 Reps 2 1 Pulse Input Channel 3 24 Low Level AC 16 Bit Output Hz 4 1 Loc P_mb 5 1 Mult 6 0 0 Offset 4 Do P86 1 56 Set...

Страница 17: ...1 mb resolution you either need to deduct a fixed offset from the reading before it is stored to avoid exceeding the 699 9 or 799 9 threshold or output the barometric reading in high resolution forma...

Страница 18: ...connection and pipe are secure and undamaged The external case can be cleaned with a damp lint free cloth and a mild detergent solution Druck recommends recalibrating the CS115 every year Contact Cam...

Страница 19: ...This is a blank page...

Страница 20: ...campbellsci com br suporte campbellsci com br Campbell Scientific Canada Corp CSC 11564 149th Street NW Edmonton Alberta T5M 1W7 CANADA www campbellsci ca dataloggers campbellsci ca Campbell Scientifi...

Отзывы: