Operation and maintenance instructions
Series PME proportional pressure regulator
5000044242
Ver. 01
18
•
For the electrical connection the following cable types are available:
CODE
DESCRIPTION
CS-LF05HB-D200 co-moulded connector M12 5 pole, female, straight with 2-metre cable shielded
CS-LF05HB-D500 co-moulded connector M12 5 pole, female, straight with 5-metre cable shielded
CS-LR05HB-D200 co-moulded connector M12 5 pole, female, bend with 2-metre cable shielded
CS-LR05HB-D500 co-moulded connector M12 5 pole, female, bend with 5-metre cable shielded
CS-LR03HB-C200 co-moulded connector M12 5 pole 3 wires, female, bend with 2-metre cable unshielded
CS-LR03HB-C500 co-moulded connector M12 5 pole 3 wires, female, bend with 5-metre cable unshielded
NOTE: in the cable versions with 3 wires, only pins 1 (24 VDC), 4 (GND) and 3 (IN +) are available.
Pin 5 (Dout) is not available.
PIN
ANALOG
1
24 VDC
Power supply
Connect to the positive pole (24VDC) and to the negative pole (GND) of the power supply
4
GND
3
IN+
Input of voltage (0-10V) or current (4-20mA) reference signal
Connect to the positive pole of the reference signal generator.
Internal resistance with voltage input:
>10kΩ.
Use reference signal generator with low
impedance and with output current >1mA@10V.
Internal resistance with current input:
100Ω.
It is mandatory to connect all negative poles of the power supply and the reference signal
generator together.
2
N.C.
NOT CONNECTED
5
Dout
Digital output signal (0-24V)
Connect to a digital input. If the input is of the NPN type, use pin 1 (24VDC) as reference of
digital input; otherwise if the input is of the PNP type, use pin 2 (GND) as reference of digital
input. Output resistance:
>15MΩ.
Max current: 50mA.