Operating Instructions
Transducer for AC voltage SINEAX U 543
3. Technical data
Measuring input
Nominal frequency:
50/60 Hz
Nominal input voltage: Please note the max. input voltage
on the type label!
0 - 20 to 0 - 600 V
Own consumption
at nominal
frequency 50 Hz:
2.0 VA with 20 mA output
1.6 VA with 10 mA output
1.4 VA with 5 mA output
1.2 VA with 1 mA output
Safety precautions to be strictly observed are marked
with following symbols in the Operating Instructions:
Contents
1. Read first and then … ................................................. 6
2. Brief description ......................................................... 6
3. Technical data ............................................................ 6
4. Mounting ..................................................................... 6
5. Electrical connections ................................................. 7
6. Commissioning and maintenance .............................. 7
7. Releasing the transducer ............................................ 7
8. Instruments admissions .............................................. 7
9. Dimensional drawing .................................................. 8
1. Read first and then …
The proper and safe operation of the device
assumes that the Operating Instructions is
read carefully
and the safety warnings given
in the various Sections
4. Mounting
5. Electrical connections
are
observed
.
The device should only be handled by appropriately
trained personnel who are familiar with it and authorised
to work in electrical installations.
2. Brief description
The transducer SINEAX U 543 is designed to convert a
sinusoidal AC voltage into a DC current or voltage signal
proportional to the measured value. It does
not
require a
separate power supply.
4. Mounting
The SINEAX U 543 can be mounted on a top-hat rail.
Note
“Environmental conditions”
in Section
“3. Technical data” when determining the place
of installation!
Setting
(special feature):
Admissible alteration of full scale
output, variable sensitivity, adjus-
table with potentiometer (voir fig. 3)
Setting range
approx. 0.9 - 1.1 · U
N
(approx.
±
10%)
100%
0
0.9
1.1
0
Output
Meas. input
1
U
N
Measuring output
DC current
:
0-1, 0-5, 0-10 or 0-20 mA
Burden voltage:
15 V
External resistance:
See Section “5. Electrical
connections”
DC voltage output
not superimposed
:
0 - 1 to 0 - 10 V
External resistance:
See Section “5. Electrical
connections”
Time response:
≤
300 ms
Accuracy
(acc. to IEC 688)
Reference value:
Input end value
Basic accuracy:
Class 0.5
Input:
20 - 100%
Temperature influence
(– 10 to + 55
°
C):
0.2% / 10 K
Safety
Pollution degree:
2
Installation category:
III (at
≤
300 V)
II (at > 300 V)
Environmental conditions
Operating temperature: – 10 to + 55
°
C
Storage temperature:
– 40 to + 70
°
C
Relative humidity
of annual mean:
≤
75 %