18

Drill 2 holes in the wall or panel as shown in the drilling pat-
tern (Fig. 7). Now secure the power pack to the wall or panel 
using two 4 mm diameter screws.

120

Fig. 7. Drilling plan.

10. Electrical connections

The electrical connections are made to screw terminals which 
are easily accessible from the front of the power pack and 
can accommodate wire gauges up to max. 2.5 mm

2

.

Make sure that the cables are not live when 
making the connections!

The 230 V power supply is potentially 
dangerous!

Note that, …

…    the data required to perform the electrical insu-

lation task agree with the data on the nameplate 
of the SINEAX TV 808 (

 input E, 

 output 

A and 

 power supply H!)

… the total loop resistance connected to the 

output (receiver plus leads) 

does not

 exceed 

the maximum permissible value R

ext

 max. see 

“Measuring output” 

in Section “6. Technical 

data” for the maximum values of R

ext

!

…  the input and output cables should be twisted 

pairs and run as far as possible away from 
heavy current cables!

In all other respects, observe all local regulations 
when selecting the type of electrical cable and 
installing them!

3

8

4

9

5 10

1

11

6

2

12

7

3

8

4

9

5 10

1

11

6

2

12

7

Green LED for
device standing by

Space e.g.
for MSK designation

ON

Front

4

9

+

A1

Without
transparent cover

With
transparent cover

Camille Bauer AG

CH-5610 Wohlen

Switzerland

Span

Zero

1

Span

Zero

2

5

10

+

H

3

8

+

A2

E2

2

7

I2+

12

U2+

E1

1

6

I1+

11

U1+

ON

E1 = Input 1 

E2 = Input 2

A1 = Output 1 

A2 = Output 2

H  = Power supply

Notes

10.1 Connecting the measuring input leads

Measurement/
Application

Input 1

Input 2

DC current 
measurement

1 (–),   6 (I1+)

2 (–),   7 (I2+)

DC voltage 
measurement

1 (–), 11 (U1+) 2 (–), 12 (U2+)

10.2 Connecting the measuring output leads

Connect the measuring output leads A1 to terminals 4 (–) 
and 9 (+), the leads A2 to terminals 3 (–) and 8 (+).

Note:  Take care that the amplifi er’s maximum permissible 

external burden R

ext

 is not exceeded (see Section 

“6. Technical data”).

Содержание SINEAX TV 808-12

Страница 1: ...ur S parateur SINEAX TV 808 12 Operating Instructions Isolating ampli er SINEAX TV 808 12 TV 808 12 B d f e 129 975 03 11 11 Camille Bauer Metrawatt AG Aargauerstrasse 7 CH 5610 Wohlen Switzerland Pho...

Страница 2: ...Betriebsanleitung mit folgenden Symbolen markiert Les conseils de s curit qui doivent imp rative ment tre observ s sont marqu s des symboles ci contre dans le pr sent mode d emploi The following symb...

Страница 3: ...mille Bauer AG Aargauerstrasse 7 CH 5610 Wohlen Switzerland Telefon 41 56 618 21 11 Telefax 41 56 618 24 58 e mail info camillebauer com http www camillebauer com 3 ON ON 2 Bild 1 Trennverst rker 1 2...

Страница 4: ...nearit tsfehler und Reproduzier barkeit eingeschlossen Einbauangaben Elektrische Anschlussklemmen DIN VDE 0609 Schraubklemmen mit indirekter Drahtpressung f r max 2 0 75 mm2 oder 1 2 5 mm2 leichte PVC...

Страница 5: ...nsetzen Dazu Klarsicht abdeckung zuerst unter die untere Halterung f hren und mit Finger Bild 3 rechts durch Druck zum Einrasten bringen ON Bild 3 Links Herausnehmen der Klarsichtabdeckung Rechts Eins...

Страница 6: ...Kabel und m glichst r umlich getrennt von Starkstromleitungen verlegt werden Im brigen landes bliche Vorschriften z B f r Deutschland DIN VDE 0100 Bestimmungen f r das Errichten von Starkstromanlagen...

Страница 7: ...0 2 0 0 2 1 3 7 9 13 14 16 0 5 0 0 5 1 4 7 10 11 13 14 16 1 0 1 1 4 8 11 13 14 16 2 0 2 1 4 6 9 13 14 16 5 0 5 1 5 10 11 13 14 16 10 0 10 1 5 6 11 13 14 16 20 0 20 1 5 6 7 13 14 16 Spannung V L tbr ck...

Страница 8: ...nder Europ ischer Richtlinien berein nachgewiesen durch die Einhaltung folgender Normen The above mentioned product has been manufactured according to the regulations of the fol lowing European direct...

Страница 9: ...7 CH 5610 Wohlen Switzerland Telefon 41 56 618 21 11 Telefax 41 56 618 24 58 e mail info camillebauer com http www camillebauer com 3 ON ON 2 Fig 1 Ampli cateur de s paration 1 2 Etriers 2 pour ouvri...

Страница 10: ...d erreur 0 2 Erreurs types de lin arit et de reproductibilit comprises Pr sentation montage raccordement Connexions lectriques DIN VDE 0609 Bornes vis pression indirecte des ls pour max 2 0 75 mm2 ou...

Страница 11: ...du doigt Fig 3 droite ON Fig 3 A gauche Enlever le capot transparent A droite Remettre en place le capot transparent 8 Ouvrir et fermer l appareil ON 2 9 Fig 4 Introduirel trier 2 danslesfentes 9 etl...

Страница 12: ...ues que les lignes des signaux d entr e et des sor ties soient r alis es par des c bles torsad s et dispos es une certaine distance des lignes courant fort Au reste respecter les prescriptions nationa...

Страница 13: ...13 14 16 0 2 0 0 2 1 3 7 9 13 14 16 0 5 0 0 5 1 4 7 10 11 13 14 16 1 0 1 1 4 8 11 13 14 16 2 0 2 1 4 6 9 13 14 16 5 0 5 1 5 10 11 13 14 16 10 0 10 1 5 6 11 13 14 16 20 0 20 1 5 6 7 13 14 16 Tension V...

Страница 14: ...amplifier Typ Type SINEAX TV 808 Das bezeichnete Produkt stimmt mit den Vorschriften folgender Europ ischer Richtlinien berein nachgewiesen durch die Einhaltung folgender Normen The above mentioned p...

Страница 15: ...er SINEAX TV 808 12 Camille Bauer AG Aargauerstrasse 7 CH 5610 Wohlen Switzerland Telefon 41 56 618 21 11 Telefax 41 56 618 24 58 e mail info camillebauer com http www camillebauer com 3 ON ON 2 Fig...

Страница 16: ...uracy Limit error 0 2 Including linearity and reproduci bility errors Installation data Terminals DIN VDE 0609 Screw terminals with wire guards for light PVC wiring and max 2 0 75 mm2 or 1 2 5 mm2 Per...

Страница 17: ...own and to the rear with the nger until it snaps into place right side of Fig 3 ON Fig 3 Left Removing the transparent cover Right Inserting the transparent cover 8 Withdrawing and inserting the devic...

Страница 18: ...m values of Rext the input and output cables should be twisted pairs and run as far as possible away from heavy current cables In all other respects observe all local regulations when selecting the ty...

Страница 19: ...0 5 1 4 7 10 11 13 14 16 1 0 1 1 4 8 11 13 14 16 2 0 2 1 4 6 9 13 14 16 5 0 5 1 5 10 11 13 14 16 10 0 10 1 5 6 11 13 14 16 20 0 20 1 5 6 7 13 14 16 Voltage V Soldered jumpers 0 0 06 6 9 10 11 0 0 1 7...

Страница 20: ...iften folgender Europ ischer Richtlinien berein nachgewiesen durch die Einhaltung folgender Normen The above mentioned product has been manufactured according to the regulations of the fol lowing Euro...

Отзывы: