Function
Connection
Measuring input AC current
IL1
1 / 3
IL2
4 / 6
IL3
7 / 9
AC voltage
UL1
2
UL2
5
UL3
8
N
11
RS 485
VP
15
(PROFIBUS DP)
RxD/TxD -P
16
RxD/TxD
-N
17
Shield
18
RxD/TxD
-P’
19
RxD/TxD
-N’
20
DGND
21
Power supply AC
~
13
~
14
DC
+
13
–
14
Measuring inputs
System /
application
Terminals
Single-phase
AC system
(A11)
Front
IL1
IL2
IL3
Measuring input
If power supply is taken from the measured voltage
internal connections are as follow:
Application (system)
Internal connection
Terminal / System
Single-phase AC current
2 / 11 (L1 – N)
4-wire, 3-phase
2 / 11 (L1 – N)
symmetric load
All other (apart from
2 / 5
(L1 – L2)
A15 / A16 / A24)
Bus Cable Termination
Both ends of the bus cable must be fitted with bus
terminators. This ensures that:
– the conductor has a fixed rest voltage,
– reflections in the cable are minimized and
– the bus has an almost constant load.
–
RxD/TxD -P
RxD/TxD -N
Shield
RxD/TxD -P’
RxD/TxD -N’
VP
DGND
Reset
BF
BA
BD
GND
BF = Bus Failure LED
The slave is in the state “Baud Search” and does not
receive valid telegrams
BA = Bus Aktive
The slave is exchanging data cyclically
BD = Bus Diagnosis LED
Lit: Parameter
error
Flashing: Configuration
error
L1
N
v
V
u
U
k
l
K
L
2
11
3
1
L1
N
k
l
K
L
2
11
3
1
L1
N
11
3
1
2
7. Electrical connections