Camille Bauer SINEAX AM2000 Скачать руководство пользователя страница 72

PM 1001608 000 06  

Device handbook LINAX PQ3000-PQ5000

 

 

  72/90

 

 

Zero displacement voltage U

NE

  

Starting from the generating system with star point E 
(which is normally earthed), the star point (N) on load 
side is shifted in case of unbalanced load. The zero 
displacement voltage between E und N may be 
determined by a vectorial addition of the voltage vectors 
of the three phases: 

U

NE

 = - (U

1N

 + U

2N

 + U

3N

 ) / 3

 

A displacement voltage may also occur due to 
harmonics of order 3, 9, 15, 21 etc., because the 
dedicated currents add in the neutral wire.  

 

Earth fault monitoring in IT systems 

Via the determination of the zero displacement voltage it's possible to detect a first earth fault in an 
unearthed IT system. To do so, the device is configured for measurement in a 4-wire system with 
unbalanced load and the neutral connector is connected to earth. In case of a single phase earth fault 
there is a resulting zero displacement voltage of ULL

/ √3. The alarming may be done e.g. by means of a 

relay output.  

 

     Transformer, secondary side                                                                                                                     Load 

 

Because in case of a fault the voltage triangle formed by the three phases does not change, the voltage 
and current measurements as well as the system power values will still be measured and displayed 
correctly. Also the meters carry on to work as expected. 

The method is suited to detect a fault condition during normal operation. A declination of the isolation 
resistance may not be detected this way. This should be measured during a periodical control of the 
system using a mobile system.  

Another possibility to analyze fault conditions in a grid offers the method of the 

symmetrical components

 

as described in A3. 

Содержание SINEAX AM2000

Страница 1: ...NAX PQ3000 PQ5000 Operating Instructions LINAX PQ3000 PQ5000 2018 08 Camille Bauer Metrawatt AG Aargauerstrasse 7 CH 5610 Wohlen Switzerland Phone 41 56 618 21 11 Telefax 41 56 618 35 35 E Mail info cbmag com http www camillebauer com ...

Страница 2: ... are also able to understand and follow the given safety and warning notices Intended use The product described in this document may be used only for the application specified The maximum electrical supply data and ambient conditions specified in the technical data section must be adhered For the perfect and safe operation of the device proper transport and storage as well as professional assembly...

Страница 3: ...tection 22 5 11 Modbus interface RS485 24 5 12 Uninterruptible power supply UPS 24 5 13 GPS time synchronization 25 6 Commissioning 27 6 1 Parametrization of the device functionality 28 6 2 Operating LED PQ5000 only 28 6 3 Installation check 28 6 4 Ethernet installation 30 6 4 1 Settings 30 6 4 2 Connection of the Standard interface 32 6 4 3 Connection of the IEC61850 interface 33 6 4 4 MAC addres...

Страница 4: ... 8 Service maintenance and disposal 60 8 1 Calibration and new adjustment 60 8 2 Cleaning 60 8 3 Battery 60 8 4 Disposal 60 9 Technical data 61 10 Dimensional drawings 68 Annex 69 A Description of measured quantities 69 A1 Basic measurements 69 A2 Harmonic analysis 73 A3 System imbalance 74 A4 Mean values and trend 75 A5 Meters 76 B Display matrices 77 B0 Used abbreviations for the measurements 77...

Страница 5: ... knowledge in the field of electrical engineering is required For assembly and installation of the device knowledge of applicable national safety regulations and installation standard is required 1 2 Scope of supply Measurement device Safety instructions multiple languages Mounting set 2 mounting clamps PQ3000 only Battery pack optional for devices with UPS only 1 3 Further documents The following...

Страница 6: ...prehensive instrument for the universal measurement and monitoring in power systems A full parameterization of all functions of the device is possible directly at the device or via web browser The PQ3000 fulfills all requirements of a class A device in accordance with the power quality standard IEC 61000 4 30 Ed 3 Using additional optional components the opportunities of the device may be extended...

Страница 7: ...de the device into the cutout from the outside b From the side slide in the mounting clamps into the intended openings and pull them back about 2 mm c Tighten the fixation screws until the device is tightly fixed with the panel Demounting of the device The demounting of the device may be performed only if all connected wires are out of service Remove all plug in terminals and all connections of th...

Страница 8: ...PM 1001608 000 06 Device handbook LINAX PQ3000 PQ5000 8 90 4 2 LINAX PQ5000 The device can be clipped onto a top hat rail according to EN 60715 Dimensional drawing PQ5000 See section 10 ...

Страница 9: ...red to The national provisions have to be observed in the installation and material selection of electric lines e g in Germany VDE 0100 Conditions concerning the erection of heavy current facilities with rated voltages below 1000 V Nameplate of a PQ3000 with Ethernet interface Modbus RTU interface 4 relay outputs 4 analog outputs Data logger Nameplate of a PQ5000 with TFT display Ethernet interfac...

Страница 10: ...2 Terminal assignments of the I O extensions 5 2 1 LINAX PQ3000 Function Option 1 Option 2 Option 3 2 relay outputs 1 1 51 52 53 1 2 55 56 57 2 1 61 62 63 2 2 65 66 67 3 1 41 42 43 3 2 45 46 47 2 analog outputs 1 1 56 57 1 2 55 57 2 1 66 67 2 2 65 67 3 1 46 47 3 2 45 47 4 analog outputs 1 1 56 57 1 2 55 57 1 3 52 53 1 4 51 53 2 1 66 67 2 2 65 67 2 3 62 63 2 4 61 63 3 1 46 47 3 2 45 47 3 3 42 43 3 ...

Страница 11: ...3 4 digital inputs passive 1 1 X1 1 X1 3 1 2 X1 2 X1 3 1 3 X2 1 X2 3 1 4 X2 2 X2 3 2 1 X3 1 X3 3 2 2 X3 2 X3 3 2 3 X4 1 X4 3 2 4 X4 2 X4 3 5 3 Possible cross sections and tightening torques Inputs L1 2 L2 5 L3 8 N 11 PE 16 I1 1 3 I2 4 6 I3 7 9 IN 10 12 power supply 13 14 Single wire 1 x 0 5 6 0mm 2 or 2 x 0 5 2 5mm 2 Multiwire with end splices 1 x 0 5 4 0mm 2 or 2 x 0 5 2 5mm 2 Tightening torque 0...

Страница 12: ...learly labeled circuit breaker or a fused disconnect switch When using voltage transformers you have to ensure that their secondary connections never will be short circuited No fuse may be connected upstream of the current measurement inputs When using current transformers their secondary connectors must be short circuited during installation and before removing the device Never open the secondary...

Страница 13: ...mitted If voltage UNE does not need to be measured connection of PE can be omitted With current and voltage transformer If current IN or voltage UNE does not need to be measured the corresponding transformers can be omitted L1 L2 L3 N I1 3 1 I2 4 I3 9 7 IN PE 6 10 12 16 11 2 5 8 L1 N 5 A UL listed PE L1 L2 L3 N I1 3 1 I2 4 I3 9 7 IN PE 6 10 12 16 11 2 5 8 L1 N 5 A UL listed K k L l K k L l PE L1 N...

Страница 14: ...following table Terminals 1 3 2 5 8 Current meas via L2 I2 k I2 l L2 L3 L1 Current meas via L3 I3 k I3 l L3 L1 L2 By rotating the voltage connections the measurements U12 U23 and U31 will be assigned interchanged L1 L2 L3 N I1 3 1 I2 4 I3 9 7 IN PE 6 10 12 16 11 2 5 8 L1 L2 L3 5 A UL listed L1 L2 L3 N I1 3 1 I2 4 I3 9 7 IN PE 6 10 12 16 11 2 5 8 L1 L2 L3 K k L l 5 A UL listed L1 L2 L3 N I1 3 1 I2 ...

Страница 15: ...oltage transformers L1 L2 L3 N I1 3 1 I2 4 I3 9 7 IN PE 6 10 12 16 11 2 5 8 L1 L2 L3 5 A UL listed L1 L2 L3 N I1 3 1 I2 4 I3 9 7 IN PE 6 10 12 16 11 2 5 8 L1 L2 L3 K k L l K k L l K k L l 5 A UL listed L1 L2 L3 N I1 3 1 I2 4 I3 9 7 IN PE 6 10 12 16 11 2 5 8 L1 L2 L3 K k L l K k L l K k L l L1 L2 L3 N I1 3 1 I2 4 I3 9 7 IN 6 10 12 16 11 2 5 8 x u X U X U X U x u x u 5 A UL listed ...

Страница 16: ... With current and 3 single pole isolated voltage transformers L1 L2 L3 N I1 3 1 I2 4 I3 9 7 IN PE 6 10 12 16 11 2 5 8 L1 L2 L3 5 A UL listed L1 L2 L3 N I1 3 1 I2 4 I3 9 7 IN PE 6 10 12 16 11 2 5 8 L1 L2 L3 K k L l K k L l 5 A UL listed L1 L2 L3 N I1 3 1 I2 4 I3 9 7 IN PE 6 10 12 16 11 2 5 8 L1 L2 L3 K k L l K k L l x u X U X U X U x u x u 5 A UL listed ...

Страница 17: ...not need to be measured the corresponding transformer can be omitted With current and voltage transformer If current IN does not need to be measured the corresponding transformer can be omitted L1 L2 L3 N I1 3 1 I2 4 I3 9 7 IN PE 6 10 12 16 11 2 5 8 L1 L2 L3 N 5 A UL listed PE L1 L2 L3 N I1 3 1 I2 4 I3 9 7 IN PE 6 10 12 16 11 2 5 8 L1 L2 L3 N K k L l K k L l K k L l 5 A UL listed PE K k L l L1 L2 ...

Страница 18: ...out a primary neutral conductor a voltage transformer with a secondary center tap can also be used L1 L2 L3 N I1 3 1 I2 4 I3 9 7 IN PE 6 10 12 16 11 2 5 8 L1 L2 N 5 A UL listed PE L1 L2 L3 N I1 3 1 I2 4 I3 9 7 IN PE 6 10 12 16 11 2 5 8 L1 L2 N K k L l K k L l 5 A UL listed K k L l PE L1 L2 L3 N I1 3 1 I2 4 I3 9 7 IN PE 6 10 12 16 11 2 5 8 L1 L2 N K k L l K k L l 5 A UL listed K k L l u U v V u U v...

Страница 19: ...tension y x 1 5 2 6 3 4 4 3 5 7 Digital inputs The device provides a standard passive digital input In addition depending on the device version there may be 4 channel passive or active digital input modules available Usage of the standard digital input Status input Meter tariff switching Usage of the inputs of the optional input modules Counting input for pulses of meters for any kind of energy pu...

Страница 20: ...n external counter acc EN62053 31 Remote controlled output PQ3000 PQ5000 1 Recommended if input impedance of counter 100 kΩ Driving a counter mechanism The width of the energy pulses can be selected within a range of 30 up to 250ms but have to be adapted to the external counter mechanism Electro mechanical meters typically need a pulse width of 50 100ms Electronic meters are partly capable to dete...

Страница 21: ...urrent 50 mA 60 mA max Switching frequency S0 20 Hz Leakage current 0 01 mA Voltage drop 3 V Load capacity 400 Ω 1 MΩ 5 9 Analog outputs Analog outputs are available for devices with corresponding I O extensions only See nameplate Analog outputs may be remote controlled PQ3000 PQ5000 ...

Страница 22: ...Residual current transformer 500 1 up to 1000 1A Rated burden 100 Ω 0 025 VA up to 200 Ω 0 06 VA Use only transformers intended for this application according to our current transformer catalog or transformers that fulfill the above specification Using transformers with divergent specifications may damage the measurement inputs Connection PQ3000 PQ5000 Erweiterung y x 1 5 2 6 3 4 The current trans...

Страница 23: ...e mounted or installed close to strong magnetic fields Measurement lines should also not be laid in parallel to power lines 6 For measurement range 1A only The rated output of the transformer must be chosen that it is reached when the rated secondary current 1A flows Consider that the burden of the transformer is not only made up by the burden of the measurement input but also by the resistance of...

Страница 24: ...ommunication settings baud rate transmission format and unique Modbus addresses The bus system is operated half duplex and may be extended to a maximum length of 1200 m without repeater 5 12 Uninterruptible power supply UPS The battery pack for the uninterruptible power supply is supplied separately Please note that compared to the storage temperature range of the base unit the storage temperature...

Страница 25: ...Hz pulse accuracy 1μs Connector RJ45 Choosing a mounting location For a correct operation the GPS receiver requires data from at least 3 satellites at the same time Therefore position the receiver so that the clearest possible view of the sky and horizon in all direction is obtained This can be on the roof of a building at best without reception being restricted by other buildings or obstacles Avo...

Страница 26: ...sting or sharp kinking of the cable should be avoided Commissioning In the settings menu change time synchronization to NTP server GPS Check the time synchronization status The time synchronization can be restarted by switching the time synchronization off and on again Time synchronization via GPS and NTP server may work in parallel If both synchronization sources are available the system uses the...

Страница 27: ... power supply and the measurement inputs Measurement input Input voltage Input current System frequency 1 Works no 2 Test and conformity marks 3 Assignment voltage inputs 4 Assignment current inputs 5 Assignment power supply 6 Load capacity relay outputs Measurement input Input voltage Input current System frequency 1 Works no 2 Test and conformity marks 3 Assignment voltage inputs 4 Assignment cu...

Страница 28: ...uccessful or cancelled Booting of device Factory reset or reset of communication settings During reset Flashes red 1 Hz Then Booting of device 6 3 Installation check The correct connection of the current and voltage inputs can be checked in two ways a Sense of rotation check Using the sequence of the current and voltage phasors the sense of rotation is determined and compared to the configured one...

Страница 29: ...n Exchanging the connections of current I2 What s wrong Voltage sequence L1 L3 L2 L3 and L2 seem to be interchanged Current sequence L1 L2 L3 Angle U I Angle between UL2 and IL2 is approx 180 wrong Required correction Exchanging the connections of the voltages L2 and L3 What s wrong Voltage sequence L1 L3 L2 L3 and L2 seems to be exchanged Current sequence L1 L3 L2 Current L2 is out of the expecte...

Страница 30: ...twork only once Subnet mask Defines how many devices are directly addressable in the network This setting is equal for all the devices Examples Gateway address Is used to resolve addresses during communication between different networks It should contain a valid address within the directly addressable network DNS Server x Is used to resolve a domain name into an address if e g a name pool ntp org ...

Страница 31: ...iable range xx xxxxxxxx First address 192 168 56 0 11000000 10101000 00111000 00000000 Last address 192 168 59 255 11000000 10101000 00111011 11111111 The device 192 168 57 64 can access directly the devices 192 168 56 0 192 168 59 255 DHCP If a DHCP server is available alternatively the mode DHCP or DHCP addresses only can be selected for the Standard interface The device then gets all necessary ...

Страница 32: ...ining the type of communication As a standard Modbus TCP communication is performed via TCP port 502 NTP uses port 123 However the port for the Modbus TCP telegrams may be modified You may provide a unique port to each of the devices e g 503 504 505 etc for an easier analysis of the telegram traffic Independent of these setting a communication via port 502 is always supported The device allows at ...

Страница 33: ...0 MBit s full half duplex Auto negotiation Protocols IEC61850 NTP Functionality of the LED s PQ3000 PQ5000 LED green On if a network connection link exists flashes during communication 6 4 4 MAC addresses For uniquely identifying Ethernet connections in a network to each connection a unique MAC address is assigned Compared to the IP address which may be modified by the user at any time the MAC add...

Страница 34: ...erface are no longer known they can be reset to the default settings by pressing the sunk in reset button located below the operating LED for at least 3s During the reset the operating LED flashes red After the reset the device is rebooted 6 5 Simulation of analog digital outputs To check if subsequent circuits will work properly with output values provided by the device using the service menu Sim...

Страница 35: ... password input the access remains open until the user leaves the settings service menu or an input timeout occurs For activating the security system a password input is required The factory default is 1234 The password can be modified by the user Permitted characters are a z A Z and 0 9 length 4 12 characters ATTENTION A reset to factory default will reset also the password But for a factory rese...

Страница 36: ...000 the valid functionality of the keys is then shown in a help bar 7 2 Selecting the information to display PQ3000 PQ5000 For devices with display information selection is performed via menu Menu items may contain further sub menus Displaying the menu Press ESC Each time the key is pressed a change to a higher menu level is performed if present Displaying information The menu item chosen using ca...

Страница 37: ...s For displaying measurement information the device uses both numerical and numerical graphical measurement displays Examples Measurement information 2 measured quantities 4 measured quantities 2x4 measured quantities 2x4 measured quantities with min max Graphical measurement display Further examples ...

Страница 38: ... them or an appropriate graphical representation is used You can select your own point of view by selecting the reference arrow system load or generator in the settings of the measurement Used symbols For defining a measurement uniquely a short description e g U1N and a unit e g V are often not sufficient Some measurements need further information which is given by one of the following symbols or ...

Страница 39: ...nly for converting the measured secondary to primary values so e g 100 5 is equivalent to 20 1 The values do not have any influence on the display format of the measurements Nominal voltage Is used as the 100 reference for monitoring power quality events and corresponds to the declared input voltage Udin in accordance with IEC 61000 4 30 Nominal current Used for scaling the harmonic content TDD of...

Страница 40: ...ters Digital outputs Digital output State pulse or remote controlled digital output with source pulse width polarity number of pulses per unit Digital outputs Relay State or remote controlled relay output with source Analog outputs Type of output source transfer characteristic upper lower range limit Security system Definition of password and password protection active inactive Demo mode Activatio...

Страница 41: ...edure varies depending on the used browser Loading a configuration file from a storage media The configuration data of the selected file will be directly loaded into the device The values in the WEB GUI will be updated accordingly Normally devices differ in the settings of network resp Modbus parameters and device name Thus when loading the file you can choose whether the appropriate settings of t...

Страница 42: ...ue Voltage dip 90 2 Nominal voltage Voltage interruption 10 2 Voltage swell 110 2 Rapid voltage changes 6 50 1 1 Related to the respective threshold The device does not verify the user defined values If these values are not plausible events may be not recognized correctly or misclassified In particular the trigger threshold for RVC events should not be greater than half of the difference of the th...

Страница 43: ...1000 2 12 2003 public medium voltage systems User specific limit sets The assessment of the PQ statistic is shown in the chapter Data recording PQ statistic Recorded PQ parameter groups Measurement Averaging time Applied limits Power frequency 10 s The applied limits and time conditions of the preset standards can be seen via the device website They can be displayed via the following menu Settings...

Страница 44: ... It remains active until the associated measured quantity falls below the limit for OFF state again The limit value is inactive 0 if either the limit for ON is not yet reached or if following the activation of the limit value the associated measured quantity falls below the limit for OFF state again Lower limit Limit for ON Limit for OFF The limit value becomes active 1 as soon as the associated m...

Страница 45: ... Entry into the alarm list if the state of the alarm limits monitoring changes or when a breakage occurs 2mA input only Entry into the event list if the state of the prewarning limits monitoring changes the value of the individual fault currents can also be output via the analog outputs The present values of the monitored fault currents are visible via the menu of the instantaneous values Meaning ...

Страница 46: ...puts the function AND NAND OR NOR DIRECT and INVERT are available These logical functions are described in Appendix C Delay time on The time a condition must be present until it is forwarded Delay time off Time to be waited until a condition which is no longer present will be released again Description This text will be used for visualization in the alarm list List entry Alarm event Each state tra...

Страница 47: ...splayed locally or via web browser or if the alarm state no longer exists By acknowledging only the flashing of the alarm symbol stops the symbol itself remains statically displayed until none of the monitoring functions is in the alarm state Logic output The summary alarm can drive an output The assignment of a digital output relay to the summary alarm is done via the settings of the correspondin...

Страница 48: ... more Events Event and alarm list Operator list PQ events The occurrence of voltage events will be registered in the PQ event list By selecting the entries the course of the RMS values of all U I the curve shape of all U I during the disturbance will be recorded Events PQ events and Mains Signalling PQ statistic For a selectable weekly interval the evaluation of the PQ statistic acc EN50160 is sho...

Страница 49: ...l be shown independently of the real averaging time Weekly profile Table Listing of all acquired mean values in the sequence of the real averaging interval The graphical representation allows to compare directly the values of the previous day resp week By selecting the bars you may read the associated values Mean value Min RMS value within the interval Max RMS value within the interval Weekly disp...

Страница 50: ...ated time range can be determined Selection of the meter logger group Meter content readings in table form Displaying data locally The selection works in principle in the same way as with the WEB GUI There are the following differences The individual measured quantities are arranged in a display matrix and can be selected via navigation The number of displayable meter readings is limited to 25 The...

Страница 51: ...unctions and limit values for which state transitions need to be recorded the parameter list entry must be set to either events or alarms Displaying of event entries Event lists are a kind of loogbook The occurrence of monitored events is recorded in the appropriate list with the time of its occurrence There are the following lists Alarm and event list PQ events see 7 8 3 Operator list Example of ...

Страница 52: ... list Each detected event is entered into the PQ event list with the time of its occurrence the remaining voltage and the duration of the event By selecting a list entry the graphical display of the measured values during this event is entered The following presentations are available Half cycle RMS curves of all voltages all currents all voltages and currents Curve shapes of all voltages all curr...

Страница 53: ...setting window for the selection of the quantities to display is entered by pressing OK Voltage display Current display Mixed display Display of PQ events WEB GUI As with the local GUI recorded events are available in the form of a logbook By selecting a list entry the graphical display of the measured values during this event is entered List of disturbance recordings Graphical display of a distur...

Страница 54: ... Example for monitoring voltage variations Limit to be respected is marked with a red line 95 of the time range U1N Requirement fulfilled because green bar 95 U2N Requirement not fulfilled because green bar 95 U3N Requirement fulfilled because green bar 95 Display of PQ statistic WEB GUI Selection via the menu PQ statistic The PQ statistic is shown for a time range of one week The ened of the time...

Страница 55: ... statistic can be changed by selecting the entry Standard Display of PQ statistic details For the recorded PQ quantities details can be displayed on a daily basis On the local display this feature is limited to the past day Frequency Daily statistic U Harmonics U Interharmonics U Daily statistic I Harmonics I Interharmonics I Voltage Current Flicker Pst Imbalance I Flicker Plt Imbalance U THD U St...

Страница 56: ...e card press it slightly into the device to release the locking mechanism The card is pushed out of the device If the SD card is not removed within 20s the exchanging procedure is cancelled and the card will be mounted to the system again Data cannot be temporarily stored in the device If there is no SD card in the device no recordings can be done Data stored on the SD card can be accessed only as...

Страница 57: ...elow for 2017 October 3rd If PQ events of the current day are to be evaluated PQDIF files with data since midnight can be created manually via web interface 7 9 2 Accessing PQDIF files You may access PQDIF files in two ways a Manual download via the Service PQ data Download PQ data The desired file can be selected from the file structure according to chapter 7 9 1 b Automatic download using the Sm...

Страница 58: ...y such as the PQDiffractor from Electrotec Concepts http www pqview com pqdiffractor registration required can be used The SmartCollect PM20 allows a more detailed analysis of the PQ data Events can be graphically analyzed or displayed in an ITIC curve which contains all PQ events with their residual voltage and event duration You may also create conformity reports e g according to EN50150 Represe...

Страница 59: ...Configuration timeout After 5 min without interaction in a parameter selection or during entering a value in the settings menu the active configuration step is closed and the associated parameter remains unchanged The next step depends on what you have done before If the user did not change configuration parameters before the aborted step the main menu will be displayed and the device starts to mo...

Страница 60: ...accuracy of the device 8 2 Cleaning The display and the operating keys should be cleaned in regular intervals Use a dry or slightly moist cloth for this Damage due to detergents Detergents may not only affect the clearness of the display but also can damage the device Therefore do not use detergents 8 3 Battery The device contains a battery for buffering the internal clock It cannot be changed by ...

Страница 61: ...wire unbalanced load Nominal frequency 42 50 58Hz or 50 5 60 69 5Hz configurable Sampling rate 18 kHz Measurement uncertainty Reference conditions Acc IEC EN 60688 ambient 15 30 C sinusoidal input signals form factor 1 1107 no fixed frequency for sampling measurement time 200ms 10 cycles at 50Hz 12 cycles at 60Hz Voltage current 0 1 1 2 Neutral current 0 2 1 if calculated Power 0 2 1 2 Power facto...

Страница 62: ...A 5 5 Supply voltage interruptions A 5 7 Supply voltage unbalance A 5 8 Voltage harmonics A 5 9 Voltage inter harmonics A 5 10 Mains signalling voltage A 5 11 Rapid voltage change RVC A 5 12 Underdeviation and overdeviation A 5 13 Current magnitude harmonics inter harmonics unbalance A Zero suppression range limitations The measurement of specific quantities is related to a pre condition which mus...

Страница 63: ...extensions may be present in the device Only one module can be equipped with analog outputs PQ5000 Up to 2 extensions may be present in the device I O interface Analog outputs via plug in terminals Linearization Linear kinked Range 20 mA 24 mA max bipolar Uncertainty 0 2 of 20 mA Burden 500 Ω max 10 V 20 mA Burden influence 0 2 Residual ripple 0 4 Response time 220 420 ms Relays via plug in termin...

Страница 64: ...urement range IRated 2mA max 2 4mA crest factor 3 Overload 40mA continuous 200mA 5 x 1s interval 300s Self consumption I2 x 64 Ω Monitoring Alarm limit 0 03 1 A Further settings Alarm limit for OFF AUS IOFF 90 75 Prewarning limit IWARN 50 IOFF 1 Prewarning AUS IWARN 10 25 Response delay 1 10s separately for alarm and prewarning Dropout delay 1 300s separately for alarm and prewarning All percent v...

Страница 65: ... month 20 45 C 3 months 20 30 C 1 year Temperature influence 0 5 x measurement uncertainty per 10 K Long term drift 0 5 x measurement uncertainty per year Usage group II acc EN 60 688 Relative humidity 95 no condensation Altitude 2000 m max Device to be used indoor only Mechanical attributes Orientation Any Housing material Polycarbonate Makrolon Flammability class V 0 acc UL94 non dripping free o...

Страница 66: ...V AC power supply V1 V3 versus bus I O s 3000V AC power supply V2 versus bus I O s 880V DC inputs U versus inputs I 1800V AC inputs U versus bus I O s 1 3600V AC inputs I versus bus I O s 3000V AC inputs I versus inputs I 1500V AC 1 During type test only with all protective impedances removed The device uses the principle of protective impedance for the voltage inputs to ensure protection against ...

Страница 67: ...y heat 3 Damp heat 6 Vibration 27 Shock IEC EN 60529 Protection type by case IEC EN 61000 6 4 Electromagnetic compatibility EMC Emission standard for industrial environments IEC EN 61000 6 5 Electromagnetic compatibility EMC Immunity for equipment used in power station and substation environment IEC EN 61131 2 Programmable controllers equipment requirements and tests digital inputs outputs 12 24V ...

Страница 68: ... 000 06 Device handbook LINAX PQ3000 PQ5000 68 90 10 Dimensional drawings LINAX PQ3000 LINAX PQ5000 Dimensions Orientation 0 90 0 90 ______1 _______ 1 Not allowed for device versions with UPS All dimensions in mm ...

Страница 69: ...n volatile stored with timestamp These values may be reset by the user via display see resetting of measurements Measurement present max min 1L 2L 3Lb 3Lu 3Lu A 4Lu Voltage U Voltage U1N Voltage U2N Voltage U3N Voltage U12 Voltage U23 Voltage U31 Zero displacement voltage UNE Current I Current I1 Current I2 Current I3 Neutral current IN Earth current IPE calculated Active power P Active power P1 A...

Страница 70: ...active power factor QF1 Reactive power factor QF2 Reactive power factor QF3 Load factor LF Load factor LF1 Load factor LF2 Load factor LF3 cosφ H1 cosφ L1 H1 cosφ L2 H1 cosφ L3 H1 cosφ H1 quadrant I cosφ H1 quadrant II cosφ H1 quadrant III cosφ H1 quadrant IV tanφ H1 tanφ L1 H1 tanφ L2 H1 tanφ L3 H1 Umean U1N U2N 2 Umean U1N U2N U3N 3 Umean U12 U23 U31 3 Imean I1 I2 2 Imean I1 I2 I3 3 IMS Average ...

Страница 71: ...fundamental and a distortion component Only the fundamental reactive power may be compensated directly by means of the classical capacitive method The distortion components have to be combated using inductors or active harmonic conditioners The load factor PF is the relation between active power P and apparent power S including all possibly existing harmonic parts This factor is often called cosφ ...

Страница 72: ...onfigured for measurement in a 4 wire system with unbalanced load and the neutral connector is connected to earth In case of a single phase earth fault there is a resulting zero displacement voltage of ULL 3 The alarming may be done e g by means of a relay output Transformer secondary side Load Because in case of a fault the voltage triangle formed by the three phases does not change the voltage a...

Страница 73: ...cur such as additional thermal stress to operational resources or electrical mains which lead to an advanced aging or even damage Also the reliability of sensitive loads can be affected and unexplainable disturbances may occur In industrial networks the image of the harmonics gives good information about the kind of loads connected See also Increase of reactive power due to harmonic currents TDD T...

Страница 74: ...y means of the symmetrical components is ambitious and intensive to calculate The results may be used for disturbance analysis and for protection purposes in three phase systems The real existing system is divided in symmetrical system parts A positive sequence a negative sequence and for systems with neutral conductor a zero sequence system The approach is easiest to understand for rotating machi...

Страница 75: ...al input may be used In case of an external synchronization the interval should be within the given range of one second up to one hour The synchronization is important for making e g the mean value of power quantities on generating and demand side comparable Trend The estimated final value trend of mean values is determined by weighted addition of measurements of the past and the present interval ...

Страница 76: ...ured meter 3 User configured meter 4 User configured meter 5 User configured meter 6 User configured meter 7 User configured meter 8 User configured meter 9 User configured meter 10 User configured meter 11 User configured meter 12 Standard meters The meters for active and reactive energy of the system are always active User configured meters To each of these meters the user can freely assign a ba...

Страница 77: ...RMS var Reactive power phase L2 Q3 Q 3 TRMS var Reactive power phase L3 S S TRMS VA Apparent power system S1 S 1 TRMS VA Apparent power phase L1 S2 S 2 TRMS VA Apparent power phase L2 S3 S 3 TRMS VA Apparent power phase L3 F F TRMS Hz System frequency PF PF TRMS Active power factor P S PF1 PF 1 TRMS Active power factor P1 S1 PF2 PF 2 TRMS Active power factor P2 S2 PF3 PF 3 TRMS Active power factor...

Страница 78: ... term flicker U31 Averaging time 10min UD U 1N TRMS V Underdeviation system voltage UD1N U 1N TRMS V Underdeviation voltage U1N UD2N U 2N TRMS V Underdeviation voltage U2N UD3N U 3N TRMS V Underdeviation voltage U3N UD12 U 12 TRMS V Underdeviation voltage U12 UD23 U 23 TRMS V Underdeviation voltage U23 UD31 U 31 TRMS V Underdeviation voltage U31 OD U 1N TRMS V Overdeviation system voltage OD1N U 1...

Страница 79: ...lue of P3 Q_MAX Q TRMS var Maximum value of Q Q1_MAX Q 1 TRMS var Maximum value of Q1 Q2_MAX Q 2 TRMS var Maximum value of Q2 Q3_MAX Q 3 TRMS var Maximum value of Q3 S_MAX S TRMS VA Maximum value of S S1_MAX S 1 TRMS VA Maximum value of S1 S2_MAX S 2 TRMS VA Maximum value of S2 S3_MAX S 3 TRMS VA Maximum value of S3 F_MM F TRMS Hz Minimum and maximum value of F UR21_MAX U neg pos UNB Maximum value...

Страница 80: ... Maximum bimetal current system IB1_MAX IB 1 t3 A Maximum Bimetal current phase L1 IB2_MAX IB 2 t3 A Maximum Bimetal current phase L2 IB3_MAX IB 3 t3 A Maximum Bimetal current phase L3 Meters Name Measurement identification Unit Description ΣP_I_IV_HT P ΣHT Wh Meter P I IV high tariff ΣP_II_III_HT P ΣHT Wh Meter P II III high tariff ΣQ_I_II_HT Q ΣHT varh Meter Q I II high tariff ΣQ_III_IV _HT Q ΣH...

Страница 81: ...nd maximum MT_Q_III_IV as MT_P_I_IV Graphic mean value Q III IV Trend last 5 interval values minimum and maximum MT_S as MT_P_I_IV Graphic mean value S Trend last 5 interval values minimum and maximum HO_IX Graphic Odd harmonics 3rd up to 49th Total Harmonic Distortion of all currents HO_UX as HO_IX Graphic Odd harmonics 3rd up to 49th Total Harmonic Distortion of all voltages HE_IX as HO_IX Graph...

Страница 82: ..._HT ΣP_I_IV_NT ΣP_II_III _NT ΣP_II_III_HT ΣQ_I_II_HT ΣQ_I_II _NT ΣQ_III_IV _HT ΣQ_I_II _NT ΣMETER1 ΣMETER2 ΣMETER3 ΣMETER4 ΣMETER5 ΣMETER6 ΣMETER7 ΣMETER8 ΣMETER9 ΣMETER10 ΣMETER11 ΣMETER12 MT_P_I_IV MT_P_II_III MT_Q_I_II MT_Q_III_IV MT_S M1 TR_M1 M1_MM M2 TR_M2 M2_MM M3 TR_M3 M3_MM M4 TR_M4 M4_MM M5 TR_M5 M5_MM M6 TR_M6 M6_MM For PQ5000 M7 TR_M7 M7_MM divided into M8 TR_M8 M8_MM 2 images each M9 ...

Страница 83: ...MIN Cφ_MIN I 1 1 1 2 I 2 1 2 2 I 3 1 3 2 ΣP_I_IV_HT ΣP_I_IV_NT ΣP_II_III _NT ΣP_II_III_HT ΣQ_I_II_HT ΣQ_I_II _NT ΣQ_III_IV _HT ΣQ_I_II _NT ΣMETER1 ΣMETER2 ΣMETER3 ΣMETER4 ΣMETER5 ΣMETER6 ΣMETER7 ΣMETER8 ΣMETER9 ΣMETER10 ΣMETER11 ΣMETER12 MT_P_I_IV MT_P_II_III MT_Q_I_II MT_Q_III_IV MT_S M1 TR_M1 M1_MM M2 TR_M2 M2_MM M3 TR_M3 M3_MM M4 TR_M4 M4_MM M5 TR_M5 M5_MM M6 TR_M6 M6_MM For PQ5000 M7 TR_M7 M7_...

Страница 84: ...HT ΣP_I_IV_NT ΣP_II_III _NT ΣP_II_III_HT ΣQ_I_II_HT ΣQ_I_II _NT ΣQ_III_IV _HT ΣQ_I_II _NT ΣMETER1 ΣMETER2 ΣMETER3 ΣMETER4 ΣMETER5 ΣMETER6 ΣMETER7 ΣMETER8 ΣMETER9 ΣMETER10 ΣMETER11 ΣMETER12 MT_P_I_IV MT_P_II_III MT_Q_I_II MT_Q_III_IV MT_S M1 TR_M1 M1_MM M2 TR_M2 M2_MM M3 TR_M3 M3_MM M4 TR_M4 M4_MM M5 TR_M5 M5_MM M6 TR_M6 M6_MM For PQ5000 M7 TR_M7 M7_MM divided into M8 TR_M8 M8_MM 2 images each M9 T...

Страница 85: ...ANGLE PF_MIN Cφ_MIN I 1 1 1 2 I 2 1 2 2 I 3 1 3 2 ΣP_I_IV_HT ΣP_I_IV_NT ΣP_II_III _NT ΣP_II_III_HT ΣQ_I_II_HT ΣQ_I_II _NT ΣQ_III_IV _HT ΣQ_I_II _NT ΣMETER1 ΣMETER2 ΣMETER3 ΣMETER4 ΣMETER5 ΣMETER6 ΣMETER7 ΣMETER8 ΣMETER9 ΣMETER10 ΣMETER11 ΣMETER12 MT_P_I_IV MT_P_II_III MT_Q_I_II MT_Q_III_IV MT_S M1 TR_M1 M1_MM M2 TR_M2 M2_MM M3 TR_M3 M3_MM M4 TR_M4 M4_MM M5 TR_M5 M5_MM M6 TR_M6 M6_MM For PQ5000 M7 ...

Страница 86: ...Cφ_MIN I 1 1 1 2 I 2 1 2 2 I 3 1 3 2 ΣP_I_IV_HT ΣP_I_IV_NT ΣP_II_III _NT ΣP_II_III_HT ΣQ_I_II_HT ΣQ_I_II _NT ΣQ_III_IV _HT ΣQ_I_II _NT ΣMETER1 ΣMETER2 ΣMETER3 ΣMETER4 ΣMETER5 ΣMETER6 ΣMETER7 ΣMETER8 ΣMETER9 ΣMETER10 ΣMETER11 ΣMETER12 MT_P_I_IV MT_P_II_III MT_Q_I_II MT_Q_III_IV MT_S M1 TR_M1 M1_MM M2 TR_M2 M2_MM M3 TR_M3 M3_MM M4 TR_M4 M4_MM M5 TR_M5 M5_MM M6 TR_M6 M6_MM For PQ5000 M7 TR_M7 M7_MM d...

Страница 87: ...MAX Q P2 Q2 S2 P2_MAX Q2_MAX S2_MAX S P3 Q3 S3 P3_MAX Q3_MAX S3_MAX PF P Q S P_MAX Q_MAX S_MAX P_TRIANGLE P1_TRIANGLE P2_TRIANGLE P3_TRIANGLE PF_MIN Cφ_MIN I 1 1 1 2 I 2 1 2 2 I 3 1 3 2 ΣP_I_IV_HT ΣP_I_IV_NT ΣP_II_III _NT ΣP_II_III_HT ΣQ_I_II_HT ΣQ_I_II _NT ΣQ_III_IV _HT ΣQ_I_II _NT ΣMETER1 ΣMETER2 ΣMETER3 ΣMETER4 ΣMETER5 ΣMETER6 ΣMETER7 ΣMETER8 ΣMETER9 ΣMETER10 ΣMETER11 ΣMETER12 MT_P_I_IV MT_P_II...

Страница 88: ...ditions is not fulfilled OR A B Y 0 0 0 0 1 1 1 0 1 1 1 1 Function is true if at least one of the input conditions is fulfilled NOR A B Y 0 0 1 0 1 0 1 0 0 1 1 0 Function is true if none of the input conditions is fulfilled Using DIRECT or INVERT the input is directly connected to the output of a monitoring function without need for a logical combination For these functions only one input is used ...

Страница 89: ... communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increas...

Страница 90: ...88 INVERT 88 NAND 88 NOR 88 OR 88 Logic functions 88 M Measured quantities 69 Basic measurements 69 Bimetal current 75 earth fault monitoring 72 harmonic analysis 73 Load factors 71 mean values and trend 75 meters 76 system imbalance 74 zero displacement voltage 72 Measurement displays 37 Measurements reset 39 Mechanical mounting 7 Menu operation 36 Mounting 7 N NTP 32 O Operating elements 36 P PQ...

Отзывы: