PM 1001608 000 06
Device handbook LINAX PQ3000-PQ5000
20/90
Active inputs
(no external power supply required)
Technical data (
acc. EN62053-31, class B)
Open circuit voltage
≤ 15 V
Short circuit current
< 15 mA
Current at R
ON
=800
Ω ≥ 2 mA
PQ3000
PQ5000
Example with meter pulse and status inputs
5.8 Digital outputs
The device has two standard digital outputs for which an external 12 / 24 VDC power supply is required.
The power supply shall not exceed 30V DC!
Usage as digital output
► Alarm output
► State reporting
► Pulse output to an external counter (acc. EN62053-31)
► Remote controlled output
PQ3000
PQ5000
1)
Recommended if input impedance of counter > 100 kΩ
Driving a counter mechanism
The width of the energy pulses can be selected within a range of 30 up to 250ms, but have to be adapted
to the external counter mechanism.
Electro mechanical meters
typically need a pulse width of 50...100ms.
Electronic meters
are partly capable to detect pulses in the kHz range. There are two types: NPN (active
negative edge) and PNP (active positive edge). For this device a PNP is required. The pulse width has to
be
≥ 30ms (acc. EN62053-31). The delay between two pulses has to be at least the pulse width. The
smaller the pulse width, the higher the sensitivity to disturbances.