Change mode

Change the function assigned to a specific user.

Manage users

Change mode

Use the arrows to choose the number associated with the user to be changed.
Alternatively, you can select a user by sending a command from the associated device.
Press ENTER to confirm.
Choose the command to associate with the user.

Step-by-step - The first command is to open and the second to close.
Sequential - The first command is to open, the second to STOP, the third to close and the 
fourth to STOP.
Open
Partial opening
B1-B2 output
BUS 1 module relay - Activate output 2 (relay output) on BUS 1 I/O module
BUS 2 module relay - Activate output 2 (relay output) on BUS 2 I/O module

Press ENTER to confirm.
Confirm? NO
Confirm? YES

FW version

Display the firmware version and the GUI installed.

Information

FW version

Use the < > arrows to show:
FW x.x.xx (firmware)
MOT x.x.xx (motor)
GUI x.x (graphics)

BUS device status

Show the status of all devices that can be connected to the BUS and managed by the firmware in use.

Information

BUS device status

Devices

Photocell BUS <n>

 <n> from 1 to 8

BUS selector <n>

 <n> from 1 to 7

BUS flashing beacon <n>

 <n> from 1 to 2

I/O module BUS <n>

 <n> from 1 to 2

Device statuses available

OK
Not communicating
Safety device active
BUS address conflict

Manoeuvre counter

View the number of total or partial operator manoeuvres (after maintenance).

Information

Manoeuvre counter

Total manoeuvres - Manoeuvres performed since the operator was installed.
Partial manoeuvres - Manoeuvres carried out after the last maintenance.

Configure maintenance

Set the number of manoeuvres the operator can perform before a maintenance warning signal is generated.

 The warning is displayed as an [Maintenance required] message and signalled by 3 + 3 flashes every hour on the device connected to the 10-5 output.

Information

Maintenance conf.

Deactivated (Default)
from 1 x100 to 500 x100

Maintenance reset

Reset the number of partial manoeuvres.

Information

Maintenance reset

Confirm? NO
Confirm? YES

Errors list

View the last 8 errors detected. The error list can be deleted.

Information

Errors list

Use the arrows to scroll through the list.
To cancel the error list, select [Delete errors]
Press ENTER to confirm.

Содержание BKX12AGF

Страница 1: ...Sliding gate operators BKX12AGF BKX12RGF INSTALLATION MANUAL FA01798 EN EN English...

Страница 2: ...Page 2 Manual FA01798 EN 01 2023 CAME S p A The contents of this manual may be changed at any time and without notice Translation of the original instructions...

Страница 3: ...the operator The electrical cables must pass through special pipes ducts and cable glands in order to guarantee adequate protection against mechanical damage The electrical cables must not touch any p...

Страница 4: ...imply follow these brief disposal guidelines DISPOSING OF THE PACKAGING The packaging materials cardboard plastic etc can be disposed of easily as solid urban waste separated for recycling Before dism...

Страница 5: ...eady CXN BUS B1 and B2 second radio channel output magnetic limit switch on board radio decoding movement and obstruction detecting device for gates weighing up to 1200 kg that are up to 20 m long RAL...

Страница 6: ...tment 3 Housing for SMA sensors 4 Gearmotor 5 Anchoring plate 6 Magnetic limit switch 7 Magnetic limit switch tabs 8 Board protection cover 9 Control board 10 Control board holder 11 Housing for two e...

Страница 7: ...the signalling devices 4 Terminal board for B1 B2 output 5 Connector for the RIOCN8WS module 6 Terminal board for BUS accessories 7 Memory Roll card connector 8 Terminal board for connecting the limit...

Страница 8: ...4 Operating temperature C 20 55 Storage temperature C 20 70 Thrust N 800 Maximum operating speed m min 20 Sound pressure level dB A 70 Protection rating IP 54 Insulation class I Reduction ratio i 1 32...

Страница 9: ...with 60227 IEC 53 IEC For power supplies up to 48 V use FROR 20 22 II cables compliant with standard EN 50267 2 1 CEI To connect the antenna use RG58 cable up to 5 m For paired connection and CRP use...

Страница 10: ...minary operations Dig a hole for the foundation frame Set up the corrugated tubes needed for the wiring coming out of the junction pit Use 40 mm corrugated tubes to connect the gearmotor to the access...

Страница 11: ...e in the iron cage The tubes must pass through the existing holes 2 UNI 5588 M12 M12x60 UNI 5739 Position the anchoring plate taking note of the measurements shown in the drawing If the gate does not...

Страница 12: ...ntil they protrude by about 600 mm Setting up the operator Remove the operator cover Place the operator on top of the anchoring plate The electrical cables must pass under the operator foundation fram...

Страница 13: ...3 Weld or fasten the rack to the gate along its entire length To assemble the rack modules use an extra piece and rest it under the join then fasten it in place using two clamps Adjusting the pinion...

Страница 14: ...k coupling Fasten the operator to the anchoring plate using stoppers and nuts The operator can also be fixed with 70 mm nuts code 88001 0273 Establishing the travel end points with magnetic limit swit...

Страница 15: ...t must be perpendicular to the magnetic sensor 6 Fasten the limit switch tab using the screw supplied 1 Close the gate 2 Insert the magnetic closing limit switch tab on the rack 3 The tab magnet must...

Страница 16: ...gland must be intended exclusively for the power supply cable Thread the cables through the holes in the control board holder A The cables need to sit perfectly flush to the side of the operator as sh...

Страница 17: ...US CXN system The CXN CAME system is a two wire non polarised communication BUS which allows you to connect up all compatible CAME devices Connection to the BUS can be in a chain star or mixed formati...

Страница 18: ...devices 1 STOP button NC contact This stops the operator and excludes automatic closing Use a control device to resume movement When the contact is being used it must be activated during programming S...

Страница 19: ...ator status See function Passage open warning light 10 11 E E3 5 Safety devices During programming configure the type of action that must be performed by the device connected to the input Connect the...

Страница 20: ...e Safety devices test function 10 2 TX C NC TX 2 RX TX 10 TS 2 CX CY CZ CK 3P 4 7 3P 4 7 10 2 TX C NC TX 2 RX TX 10 TS 2 CX CY CZ CK 3P 4 7 3P 4 7 DXR DLX photocells Standard connection DXR DLX photoc...

Страница 21: ...n Make sure that there are no obstacles in the way Power up the device and follow the instructions on the display Start programming following the wizard If this is not the first time the board is bein...

Страница 22: ...own speed Slowdown AST control Impact test Wired safety devices Total stop CX input CY input CZ input CK input Safety devices test RIO safety devices RIO ED T1 RIO ED T2 RIO PH T1 RIO PH T2 BUS Device...

Страница 23: ...output Light output I O module BUS 2 input I1 input I2 Light output Relay output BUS flashing beacon Opening colour Closing colour Auto cl colour Pre flashing colour Signal error BUS device lights Sig...

Страница 24: ...US device status Manoeuvre counter Maintenance conf Maintenance reset Errors list Timer management Show clock Set the clock Automatic DST Time format Create new timer Open Start time End time Days of...

Страница 25: ...tor installed Configuration Motor settings Motor type BKX12 Opening speed Set the opening speed percentage of maximum speed Configuration Gate travel settings Opening speed 20 to 100 Default 70 Closin...

Страница 26: ...eed The parameter is only used with the Opening slowdown point function active If the slowdown speed is incorrectly set to a value higher than the opening speed by mistake the parameter is corrected C...

Страница 27: ...avel calibration function Total stop Activate or deactivate input 2 1 If it is activated the input is used as a normally closed contact With the input open this function excludes all commands includin...

Страница 28: ...Reclose while opening RIO PH T1 and RIO PH T2 Associate one of the available functions with a wireless safety device The function only appears if the RIO CONN interface board is present Configuration...

Страница 29: ...s I O module BUS 1 I O module BUS 2 input I1 input I2 Deactivated Default Stop Stop the gate and exclude automatic closing Use a control device to resume movement If it is activated the input is used...

Страница 30: ...a BUS flashing beacon connected Configuration BUS Devices BUS flashing beacon Closing colour White Yellow Orange Red Default Purple Blue Light blue Green BUS flashing beacon Automatic closing time col...

Страница 31: ...a BUS selector connected Configuration BUS Devices BUS device lights Signal maintenance Deactivated Default White Yellow Orange Red Purple Blue Light blue Green Command 2 7 Associate a command to the...

Страница 32: ...if there is an error Configuration Times Automatic partial close Off 1 to 180 seconds Default 10 Passage open warning light It signals the gate status The device is connected to output terminal 5 Conf...

Страница 33: ...connection system communication speed on ports RSE1 and RSE2 Configuration RSE communication RSE1 speed RSE2 speed 4800 bps 9600 bps 14400 bps 19200 bps 38400 bps Default 57600 bps 115200 bps Save dat...

Страница 34: ...er code Send the code from the control device transmitter keypad or transponder Repeat the procedure to add other users Remove user Remove one of the registered users Manage users Remove user Use the...

Страница 35: ...f all devices that can be connected to the BUS and managed by the firmware in use Information BUS device status Devices Photocell BUS n n from 1 to 8 BUS selector n n from 1 to 7 BUS flashing beacon n...

Страница 36: ...format Timer management Time format 24 hour 12 hour Create new timer Time one or more types of activation chosen from those available Timer management Create new timer Use the arrows to choose the des...

Страница 37: ...s been enabled Password Remove password Confirm NO Confirm YES Change password Change the password protecting access to the main menu This option only shows if a password has been enabled Password Cha...

Страница 38: ...SUPPLY TO THE LINE 1 Insert the MEMORY ROLL card into the corresponding connector on the control board 2 Press the Enter button to access programming 3 Use the arrows to choose the desired function C...

Страница 39: ...MASTER For information on connecting the electrics for the devices and accessories please see the ELECTRICAL CONNECTIONS section UTP CAT 5 max 1000 m RSE A B GND A B GND RSE A B GND A B GND Programmin...

Страница 40: ...ening or partial opening any given radio command will always allow opening The wired commands continue to operate normally C n Wired safety device active The n value is associated with the selected pa...

Страница 41: ...error E7 Operating time error E8 Open release hatch error Limit switch input error or both limit switches open E9 Obstacle detected during closing E10 Obstacle detected during opening E11 The maximum...

Страница 42: ...onal closures disconnect the power supply When the power supply is reconnected check the system is working correctly For information on correct installation and adjustments please see the product inst...

Страница 43: ...Page 43 Manual FA01798 EN 01 2023 CAME S p A The contents of this manual may be changed at any time and without notice Translation of the original instructions...

Страница 44: ...ual may be changed at any time and without notice Translation of the original instructions AFFIX THE PRODUCT LABEL FROM THE BOX HERE CAME S p A Via Martiri della Libert 15 31030 Dosson di Casier Trevi...

Отзывы: