ZA3P:
QUICK START GUIDE
Should the gates not operate as suggested above,
call CAME helpline
0115 921 0430
for technical support.
Important!
Ensure the wiring is complete (refer to the wiring diagram) & any required physical stops are set before
commencing with programming
Tick
1. Power on the control panel.
2. Disable total stop – Permanent link wire between terminal
1
&
2
.
3. If no safety device has been connected to the
C1
terminal then disable the safety input
C1
-
Permanent link wire between terminal
2
&
C1
.
4. Disable safety input
CX
– Dip switch
8
on.
5. Set all other dip switches off.
6. Check the motor direction
Enable maintained action – Dip switch
6
on.
Hold a wire between terminal
2
&
3
.
The gate should open, if not reverse the motor cables for motor 2 (Connections X, Y)
Disable maintained action – Dip switch
6
off
7. Set the ATS microswitch end stops
Unlock the motor on the manual release
Adjust the TL potentiometer to the maximum clockwise position.
Set the gate to its closed position
Send a closing command pulse using a link wire
between terminal
2
&
4
.
While the motor is running, turn the rod marked
C
anticlockwise until the motor stops running.
Set the gates to its open positions
Send an opening command pulse using a link wire between
terminal
2
&
3
.
While the motor is running, turn the rod marked
A
clockwise until the motor stops running.
Note. 20 complete turns of the rod is equal to 10mm of movement of the micro switch. By default the motor run time is set to 120s, if the
motor times out before the micro switch has been reached an additional command will need to be sent to start the motor running again
so that the micro switch setup can be completed.
8. Set the TRM2 potentiometer all the way to minus (Anticlockwise).
9. Adjust the TL potentiometer to the 4 O’clock position
10. Check the gate operation by pulsing across connections
2
&
4
, the gate will close.
Safety inputs should now be configured and the gate force tested as required.
Please refer to the full manual to complete the commissioning.
Potentiometers Dip Switches
The installation must be carried out
by skilled and qualified personnel