Default text message
Customised
text message
Confirmation text message
from TH450GSM
Setting the date and time of the programmable thermostat
# 10 <TIME> = HH.MM,
DD.MM.YY
# 10 <…> = HH.MM,
DD.MM.YY
ORA = HH.MM, DD.MM.YY
By setting a valid date, the change to/from daylight savings time will take place auto-
matically.
Set the temperatures T1, T2, T3 in summer (E) and winter (I) mode
# T1E = xx.x, T2E = xx.x,
T3E = xx.x
T1E = xx.x T2E = xx.x T3E = xx.x.
(cooling)
# T1I = xx.x, T2I = xx.x,
T3I = xx.x
T1I = xx.x T2I = xx.x T3I = xx.x.
(heating)
Setting the UPP T and LOW T alarm thresholds
Via text message, you can determine the minimum (LOWT) and maximum (UPPT) temperature
thresholds, on exceeding which the programmable thermostat will send a notification mes-
sage "threshold exceeded" to the numbers enabled in the phonebook (marked with "R").
# T SUP = xx.x, T INF = xx.x,
TSUP (R)= SI/NO,
TINF (R)= SI/NO
TSUP = xx.x T INF = xx.x
If
TSUP (R)= SI, TINF (R)= SI
there is also a notification when the level goes back under/
over the alarm threshold.
If you enter the message
# TSUP = NO, TINF = NO
the alarm threshold message will be
disabled.
Request set threshold value
#SOGLIE?
TSUP = xx.x T INF = xx.x
Setting the frost protection temperature
# ANTIGELO = xx.x
ANTIGELO = xx.x
Programmable thermostat operating test
#12 <TEST>
#12 <…>
TEST OK