background image

1.  Product zone temperature too high.

1. Control Setting Too High - Reset Control
2. Inadequate Air Circulation - Rearrange Product Load To Improve Air Circulation And Flow. Keep Empty Trays in Position.
3. Unit May Need To Be Manually Defrosted. (Refer to Page 5.)
4. Unit May Be In Defrost Cycle. See Indicator Light. Close Door And Wait 20 Minutes for Defrost Cycle To Finish.
5. Clean the Condenser (Refer to Page 11.)

2.  Air Screen unit fails to start - no hum.

1. Power Cord is Disconnected - Reconnect
2. Fuse - Replace Fuse
3. Circuit Breaker has Tripped. Reset Breaker in Electrical Box.
4. Overload Protection - Determine Reason & Correct, Replace If Necessary
5. Unit may need to be defrosted or has tripped off due to overload. Wait 30 minutes: Unit will self-reset.

3.  Condensing unit fails to start - hums but trips on overload protector.

1. Unit may need to be defrosted or has tripped off due to overload. Wait 30 minutes: Unit will self-reset.
2. Improperly Wired - Check Wiring Against Diagram
3. Low Voltage - Determine Reason & Correct
4. Starting Capacitor Defective - Determine Reason & Replace
5. Relay Not Closing - Determine Reason & Correct, Replace If Necessary
6. Compressor Motor Has Winding Open Or Shorted - Replace Compressor
7. Internal Mechanical Trouble In Compressor - Replace Compressor

4.  Condensing unit starts, but fails to switch.

1. Improperly Wired - Check Wiring Against Diagram off of “start” winding.
2. Low Voltage - Determine Reason & Correct
3. Relay Failing To Open - Determine Reason & Correct, Replace If Necessary
4. Run Capacitor Defective - Determine Reason & Replace

5. Excessively High Discharge Pressure - Check Discharge Shut-Off Valve, Or Insufficient Cooling On Condenser

6. Compressor Motor Has Winding Open Or Shorted - Replace Compressor
7. Internal Mechanical Trouble In Compressor - Replace Compressor

5.  Condensing unit starts and runs, but short cycles on overload protector.

1. Additional Current Passing Through Overload Protector - Check Wiring Diagram. Check For Added Fan Motors, Pumps, etc., Connected To Wrong Side Of 
    Protector
2. Low Voltage To Unit (or unbalanced if three phase) - Determine Reason & Correct
3. Overload Protector Defective - Check Current - Replace Protector
4. Run Capacitor Defective - Determine Reason & Replace
5. Excessive Discharge Pressure - Check Ventilation, Restrictions In Cooling Medium, Restrictions in Refrigeration System
6. Suction Pressure Too High - Check For Possibility Of Misapplication. Use Stronger Unit

7. Compressor Too Hot (return gas) - Check Refrigerant Charge (fix leak) Add If Necessary

8. Compressor Motor Has Winding Shorted - Replace Compressor

6.  Condensing unit runs but short cycles on.

1. Overload Protector - See #3 Above
2. Thermostat - Differential Set Too Close
3. High Pressure “Cut-Out” Due To:

a) Insufficient Air or Water Supply - Check Air or Water Supply To Condenser, Correct

b) Overcharge - Reduce Refrigerant Charge
c) Air In System - Purge

4. Low Pressure “Cut-Out” Due To:

a) Liquid Line Solenoid Leaking - Replace
b) Compressor Valve Leak - Replace
c) Undercharge - Fix Leak, Add Refrigerant
d) Restriction In Expansion Device - Replace Device

7.  Condensing unit operates for prolonged periods or continuously.

1. Unit may need to be defrosted
2. Shortage Of Refrigerant - Fix Leak, Add Charge
3. Control Contacts Stuck or Frozen Closed - Clean Contacts or Replace Control

4. Excessive Heat Load Placed Into Cabinet - Allow Unit Sufficient Time For Removal Of Latent Heat

5. Prolonged or Too Frequent Door Openings - Plan or Organize Schedule To Correct Condition
6. Evaporator Coil Iced - Defrost
7. Restriction In Refrigeration System - Determine Locations & Remove
8. Dirty Condenser - Clean Condenser
9. Filter Dirty - Clean or Replace

XII - Troubleshooting Guide

Содержание AIR CURTAIN ULTRA

Страница 1: ...OWNER S MANUAL CAMBRO AIR CURTAIN ULTRA This owner s manual applies to all models that begin with the prefix ACU www cambro com...

Страница 2: ...nderstand the contents of this manual and operation Delivery Inspection All Cambro Air Curtain Ultra Refrigerators are shipped in containers to prevent damage Upon delivery of your new Air Curtain Ult...

Страница 3: ...ert them to the situation 5 Receiver must call the carrier to schedule an inspection of the damaged merchandise within 15 days Electrical 1 Check SERIAL PLATE to be sure the unit is installed on the p...

Страница 4: ...ush down to seat The supports can be installed in a horizontal plane of can be mounted in a slightly sloped orientation to cause the product to slide forward on the sheet pans 4 The LED digital temper...

Страница 5: ...rovided standard at 4 1 2 spacing Each tray slide can accommodate one 1 18 x26 pan tray Side Grips Rear Handle For easy mobility and maneuvering stainless steel recessed hand grips are provided on the...

Страница 6: ...d defrost time interval This will allow you to select defrost time intervals that work best for your operation You can select unit defrost time intervals from every 4 hours to every 12 hours in one ho...

Страница 7: ...tes cabinet is cooling down H Clean Condenser Reminder Your unit comes with a clean condenser reminder light located next to the up and down arrow temperature control buttons The most important thing...

Страница 8: ...ve unit plugged in with door closed after use A recommendation would be to defrost after use as well to free coil from ice build up formed during use 5 Your unit is equipped with a smart controller Du...

Страница 9: ...ng solutions Check for warnings about use on stainless steel products Repeated use of chlorinated solvents may cause a chemical reaction with the stainless steel which will damage the surface and caus...

Страница 10: ...the condenser fins use brush or compressed air to blow this clear NOTE Care should be taken not to bend any of the condenser fins as this will reduce performance and compressor life Replace louver ass...

Страница 11: ...7 Internal Mechanical Trouble In Compressor Replace Compressor 5 Condensing unit starts and runs but short cycles on overload protector 1 Additional Current Passing Through Overload Protector Check Wi...

Страница 12: ...ycling Determine Reason see 6 previous page Correct 5 Relay Being Influenced By Loose Vibrating Mounting Remount Rigidly 6 Incorrect Run Capacitor Replace With Proper Capacitor 11 Suction line frosted...

Страница 13: ...XIII Wiring Diagram...

Страница 14: ...and FITNESS FOR A PARTICULAR PURPOSE null and void including any responsibility for damage costs and legal actions resulting from use or installation of product s in any Non commercial setting This st...

Страница 15: ..._____________________________________________________________________________________ __________________________________________________________________________________________________________________...

Страница 16: ...Telephone 714 848 1555 Toll Free 800 854 7631 Customer Service 800 833 3003 Cambro Manufacturing Company 5801 Skylab Road Huntington Beach California 92647 2056 Printed in USA 12 19...

Отзывы: