Chapter 2: System hardware
Lightning protection unit (LPU) and grounding kit
Page
2-48
ODU to grounding system ground cable,
bottom LPU ground cable (2pcs, M6 and M10
lugs), bolt and washers
4-pin connector kits (4 kits, one shown)
One LPU and grounding kit (
) is required for the PSU drop cable connection to the ODU. If the
ODU is to be connected to an auxiliary device, one additional LPU and grounding kit is required for the
Aux drop cable. Order the kits from Cambium Network (
.
Note
When installing LPUs, use only EMC cable glands supplied in the ODU and LPU kits (with
black caps). Do not use the non-EMC cable glands supplied in other kits (with silver caps),
as these may only be used in ODU installations without LPUs.
Caution
To provide adequate protection, all grounding cables must be a minimum size of 10 mm
2
csa (8AWG), preferably 16 mm
2
csa (6AWG), or 25 mm
2
csa (4AWG).
Table 56 DC LPU and grounding kit part number
Cambium description
Cambium part number
DC LPU and Grounding Kit
C000000L114A
Cable grounding kit
Copper drop cable shields must be bonded to the grounding system in order to prevent lightning-strike
arcing (resulting in fire risk and damage to equipment).
Содержание PMP 450 AP
Страница 79: ...Chapter 2 System hardware System Components Page 2 29 Figure 20 Gigabit Enet Capable power supply...
Страница 160: ...Chapter 3 System planning Radio Frequency planning Page 3 30 Figure 55 Sector Antenna...
Страница 161: ...Chapter 3 System planning Radio Frequency planning Page 3 31 Figure 56 cnMedusa Antenna...
Страница 189: ...Chapter 3 System planning Remote AP Deployment Page 3 59 Figure 65 Remote AP wired to SM that serves as a relay...