6.0 DEHUMIDIFIER TECHNICAL DATA SHEET
MODEL NUMBER
1Ø
DH150AX
N/A
N/A
3Ø
DH150BX
DH300BL(Y)
DH600BY
PERFORMANCE DATA
Dehumidification Rate
L/h
6·25
12·5
25
Output to Air Nett (DH model)
kW
5·5
15·5
25
Total Electrical Input (STD fan)
kW
2·3
6·7
10·0
Total Electrical Input ("F" Fan)
kW
N/A
7·3
10·4
ELECTRICAL DATA
Supply Details 1Ø
230V~1N 50Hz
N/A
N/A
Supply Details 3Ø
|--------------------- 400V ~3N 50Hz ----------------------------|
Fan Option Type
STD
"F"
Maximum Supply Fuse 1Ø
amps
32
N/A
N/A
N/A
Maximum Supply Fuse 3Ø
amps
16
32
35
35
Maximum Running Amps 1Ø
amps
23.3
N/A
N/A
N/A
Maximum Running Amps 3Ø
amps
10.2
19.4
26
27
Starting Current Amps 1Ø STD
amps
62
N/A
N/A
Starting Current Amps 1Ø "S"
amps
28
N/A
N/A
Starting Current Amps 3Ø STD
amps
30.5
66
135
Starting Current Amps 3Ø "S"
amps
19
29
55
AIR HEATER OPTION
If Turning Hood with Heater Fitted
Separate Supply for heaters
Maximum Power Output
kW
9
N/A
N/A
Maximum Full Load Amps 1Ø
amps
36
N/A
N/A
Maximum Full Load Amps 3Ø
amps
12
N/A
N/A
Maximum Supply Fuse 1Ø
amps
50
N/A
N/A
Maximum Supply Fuse 3Ø
amps
16
N/A
N/A
AIR FLOW DATA
Air Flow Nominal
m³/h
2500
5000
9000
Ducting Design Static Pressure STD
Pa
N/A
60
80
*Ducting Max Static Pressure
Pa
0-200
-
-
Ducting Max' Static Pressure "F" M/C
Pa
N/A
140
160
If Turning Hood with Heater fitted:
Ducting Design Static Pressure STD M/C
Pa
N/A
N/A
0
* Ducting Max Static Pressure
Pa
0-170
-
-
Ducting Max Design Static Pressure "F"
Pa
N/A
N/A
80
WATER FLOW DATA
Condensate Water Connection Size
¾"Domestic Waste
1½"BSPM
1½"BSPM
PHYSICAL DATA
Width (unpacked)
mm
660
980
1730
Depth (unpacked)
mm
660
720
1250
Height (unpacked)
mm
1313
1435
1600
Weight (unpacked)
kg
130
220
497
MISC' DATA
Hermetic System
Refrigeration charge R407c (STD DH)
kg
2·5
9.5
14
Refrigeration charge R407c (DH300BLY)
kg
10
Sound Pressure at 3m
db(A)
58
66
63
NOTES:-
1) Performance data based on air at 20ºC, 75%RH (Water at 26ºC).
2) Weight and dimensions nett.
3) Allow 500mm clearance to service panels.
4) Minimum air temperature 0ºC for "X" models and -15ºC for "Y" models.
5) Dantherm Ltd. reserves the right to change or modify models without prior notice.
6) R407c Global Warming Potential (GWP) 1774
*DH150 features a Control Flow fan at 2500m
3
/h
14
SD208050 ISSUE 44
DH150/300/600 OWNER INSTALLATION MANUAL