User and Programming Manual - Rev P
California Instruments
14.4.1. *CLS
This command clears the following registers (see chapter 16 for descriptions of all status
registers):
·
Standard Event Status
·
Status Byte
· Error
Queue
Command Syntax
*CLS
Parameters None
14.4.2. *ESE
This command programs the Standard Event Status Enable register bits. The programming
determines which events of the Standard Event Status Event register (see *ESR?) are
allowed to set the ESB (Event Summary Bit) of the Status Byte register. A "1" in the bit
position enables the corresponding event. All of the enabled events of the Standard Event
Status Enable Register are logically ORed to cause the Event Summary Bit (ESB) of the
Status Byte Register to be set. See Section 16 for descriptions of the Standard Event Status
registers.
The query reads the Standard Event Status Enable register.
Table 11: Bit configuration of standard event status enable register
Bit
Position
7 6 5 4 3 2 1 0
Bit Name
PON
not
used
CME EXE DDE QYE not
used
not
used
Bit Weight
128
32
16
8
4
CME
Command error
DDE
Device-dependent error
EXE
Execution error
QYE
Query error
PON Power-on
Command Syntax
*ESE <NRf>
Parameters
0 - 255
Power-On Value
128
Example *ESE
129
Query Syntax
*ESE?
Returned Parameters
<NR1>(Register value)
Related Commands
*ESR? *STB?
October 2005
RP Series