Failing to keep supply and distribution containers closed, except when in use, can 
result in contamination of the IPA cleaning solution. 

 

2.4.4

 

Nitrogen 

CALIENT recommends using small, disposable cylinders of 99.9% pure compressed nitrogen gas 
when cleaning S320 OCS optical fiber connectors. Attention should be given to the information 
provided in the cylinder supplier’s Material Safety Data Sheet (MSDS). 

 

 

Nitrogen cylinders contain gas under high pressure that can cause rapid suffocation 
when released. Nitrogen gas acts as a simple asphyxiant by displacing air necessary 
for life. If symptoms of asphyxiation occur—such as rapid respiration, loss of muscular 
coordination, fatigue, dizziness or nausea—move immediately to fresh air. Also, 

never

 

puncture or incinerate nitrogen cylinders. 

 

2.4.5

 

Nitrogen Cylinder Precautions 

Be sure to observe the following precautions when using an industrial-size compressed nitrogen 
gas cylinder: 

 

Keep it from falling over or rolling around to avoid damaging the cylinder valve. 

 

Open the valve a little at a time. If it cannot be opened by hand, return the cylinder to 
the supplier. Never use force (e.g., a wrench) when opening or closing a cylinder valve. 

 

Never heat a cylinder containing liquefied gas to increase the gas flow or the required 
rate. 

 

Only use connectors designed specifically for compressed-gas cylinders. Never use 
intermediate connectors. 

 

Always check the condition of couplings before use. 

Содержание S320

Страница 1: ...S320 Optical Circuit Switch OCS Hardware User Guide...

Страница 2: ...hat is protected under one or more pending or issued United States and foreign patents This manual may not be copied wholly or in part without prior written permission from CALIENT Technologies To obt...

Страница 3: ...ay 27 2015 Rev B7 Page 3 of 46 Revision History Date Version Description Author s 01 21 2013 A Legacy doc describing S320 Photonic Switch hardware T Douglas 04 14 2015 B6 Update doc to reflect OCS har...

Страница 4: ...ectors Clean 14 2 3 2 Optical Fiber Bend Radius 14 2 4 Cleaning Substance Hazards 15 2 4 1 Isopropyl Alcohol 15 2 4 2 Leakage and Spill Disposal 16 2 4 3 Decanting 16 2 4 4 Nitrogen 17 2 4 5 Nitrogen...

Страница 5: ...s 34 5 1 2 Safety Requirements 35 5 1 3 Required Tools 35 5 1 4 Installing the S320 OCS in a Rack 36 5 2 Connecting Communication Interfaces 36 5 2 1 Connecting the Serial Cable 36 5 2 1 1 Serial Port...

Страница 6: ...e Doc Part No 460167 00 May 27 2015 Rev B7 Page 6 of 46 A 3 Optical Specifications 43 A 4 Environmental Requirements 44 B ORDERING INFORMATION 45 B 1 System Part Numbers 45 B 2 Spare Part Numbers 45 B...

Страница 7: ...OCS Version 2 Front Panel 24 Figure 7 S320 OCS Version 2 Rear Panel 24 Figure 8 S320 OCS Version 1 Front Panel Close Up 25 Figure 9 S320 OCS Version 2 Front Panel Close Up 25 Figure 10 S320 OCS Power...

Страница 8: ...Alarm Interface Pinout 27 Table 4 Power Supply Input Voltage Tolerances 29 Table 5 S320 OCS Environmental Requirements 33 Table 6 DB9 Serial Interface Pinout 37 Table 7 RJ45 Serial Interface Pinout 3...

Страница 9: ...0 Optical Circuit Switch OCS Hardware User Guide provides detailed information about the physical form and functionality of the CALIENT S320 fiber optic switch AUDIENCE This guide is written for both...

Страница 10: ...he switch an overview of OCS functionality and physical architecture including precise descriptions of the LEDs and physical interfaces located on the front and rear of the OCS chassis and step by ste...

Страница 11: ...ecting and applying electrical power Make sure to implement all electrostatic discharge ESD prevention measures when handling the S320 OCS Inspect the installation site for sources of laser light and...

Страница 12: ...losed optical system All service to this device that requires removal of the chassis panel must be performed by the manufacturer or its authorized agent s Personnel working near or in the vicinity of...

Страница 13: ...cted to the S320 OCS Although the S320 OCS has no laser sources higher than Class 1 the total optical power through the equipment and potentially available at any one of the fiber terminations split o...

Страница 14: ...connectors require special handling to mitigate contamination from dust and debris that could increase insertion loss Contamination during connection of the connector surface perpendicular to the lig...

Страница 15: ...ectors The recommended solvent for cleaning optical fiber connectors is isopropyl alcohol IPA that is 99 8 pure DOT Hazard Classification Flammable Liquid Always observe the following precautions when...

Страница 16: ...spiratory protection from vapors Dispose of contaminated clean up materials only at an approved facility in accordance with local requirements for hazardous waste 2 4 3 Decanting When decanting isopro...

Страница 17: ...r life If symptoms of asphyxiation occur such as rapid respiration loss of muscular coordination fatigue dizziness or nausea move immediately to fresh air Also never puncture or incinerate nitrogen cy...

Страница 18: ...f 46 Use only materials compatible with the gas Never allow any substance gas or liquid to get into a cylinder that is in use If there is a risk this could happen mount an anti return valve If a forei...

Страница 19: ...rk core to access allowing any optical input fiber to be connected at the photonic level to any output fiber regardless of the data rate or protocol of the signals being carried by the fiber 3 2 Archi...

Страница 20: ...e light paths The light path within the MSM architecture is illustrated in Figure 2 Figure 2 Light Path within the MSM Fibers mounted in a Fiber Block Fibers mounted in a Fiber Block Fibers mounted in...

Страница 21: ...m each output mirror back into its output fiber High quality mirrors and collimators coupled with precise electrostatic control of the position of each mirror enable switch times of less than 20 ms an...

Страница 22: ...e Control Processor CP which is the brain of the S320 OCS The CP establishes and maintains connections and coordinates system management Because of the vital role of the Control Processor the S320 OCS...

Страница 23: ...S320 OCS Hardware User Guide Doc Part No 460167 00 May 27 2015 Rev B7 Page 23 of 46 Figure 4 S320 OCS Version 1 Front Panel Figure 5 S320 OCS Version 1 Rear Panel...

Страница 24: ...S320 OCS Hardware User Guide Doc Part No 460167 00 May 27 2015 Rev B7 Page 24 of 46 Figure 6 S320 OCS Version 2 Front Panel Figure 7 S320 OCS Version 2 Rear Panel...

Страница 25: ...ray of 320 input and 320 output LC UPC bulkhead connectors 3 3 2 Operational Status LEDs The operational status LEDs for both versions of the S320 OCS are located in the lower right corner of the fron...

Страница 26: ...more alarms critical major or minor are occurring A PWR B PWR Power status Green The system is receiving power from the indicated power source Source A is the primary power source source B is the bac...

Страница 27: ...MINV_NO Minor Alarm Visual Normally Open 3 3 4 Management Interfaces The management interfaces on the S320 OCS provide Ethernet and serial connectivity two 2 Ethernet connections are used to control t...

Страница 28: ...Interfaces The S320 OCS is powered by redundant power source inputs Power Source A and Power Source B Each input holds a single 48 VDC power module If Power Source A fails the system automatically dra...

Страница 29: ...other particulate matter Figure 4 and Figure 5 show a version 1 switch configured with front patch panels and rear power source inputs populated with power modules Figure 6 and Figure 7 show a simila...

Страница 30: ...e S320 OCS The S320 OCS is shipped from the factory in a single package consisting of two containers an inner container and an outer container For added protection the S320 OCS is first packed inside...

Страница 31: ...ntaining the cables version 2 only mounting screws and ESD grounding strap 4 Carefully lift the chassis out of the inner container 5 Remove the anti ESD bag from the chassis and keep it for future shi...

Страница 32: ...g the shipping lockdown baseplate Performing this task requires two people The following procedure describes how to remove the shipping lockdown baseplate Figure 12 1 Person 1 presses down firmly on t...

Страница 33: ...flat Packaged for shipping ATSM composite Truck Rail Air 5Hz 20Hz at 0 01g 2 Hz 20 200Hz 3dB octave Shock2 Operating IEC 60068 2 27 3 5G 11 msec half sine shocks in the x y and z axes run pre and pos...

Страница 34: ...ling the switch in a rack Connecting the configuration interfaces i e serial cable and Ethernet cables of the switch Connecting the power interfaces of the switch Booting up the switch Installing the...

Страница 35: ...t room temperature Make sure the ambient operating temperature of racked equipment does not exceed the specified maximum operating temperature of the S320 OCS by having adequate ventilation cooling in...

Страница 36: ...unting the S320 OCS in a rack The following procedure describes how to install the S320 OCS in a rack 1 Attach a shelf to the rack one screw hole below the desired location of the switch This shelf wi...

Страница 37: ...or which requires a combination USB to DB9 RJ45 to DB9 adapter cable Figure 14 Version 1 does not come with a serial cable it must be provided by the customer Version 2 comes with the required combina...

Страница 38: ...to DB9 serial cable to the RJ45 to DB9 adapter cable Figure 13 Figure 13 USB to DB9 Cable L and RJ45 to DB9 Adapter Cable R 2 Connect the RJ45 end of the assembled serial cable Figure 14 to the seria...

Страница 39: ...hernet GbE RJ45 connectors on the front of the switch These connectors are labeled NMS LAN A and B on version 1 of the switch Figure 4 and Figure 8 and LAN A and B on version 2 of the switch Figure 6...

Страница 40: ...r supply cabling CALIENT recommends using 18 gauge wire for this cabling 2 Insert one exposed end of each wire into the appropriate receptacle of the cam over terminal connector located at the left si...

Страница 41: ...e to the appropriate terminal on the power supply 5 Activate both power sources A primary and B backup to deliver electrical power to the S320 OCS To avoid possible injury to personnel and or damage t...

Страница 42: ...0 OCS is compliant A 1 1 Safety The S320 OCS has been tested and found compliant with the following safety standards UL 60945 UL CSA IEC EN 60950 1 IEC EN 60825 FDA CFR 21 1040 A 1 2 Electromagnetic C...

Страница 43: ...ty The physical characteristics of the S320 OCS affecting accessibility and serviceability are listed in Table 8 Table 8 S320 OCS Physical Dimensions Feature Description Dimensions 17 5 W x 13 9 H x 1...

Страница 44: ...g Accuracy 1 dB Insertion Loss Reporting Accuracy 2 dB Switch lifetime 10 12 Cycles 1 Using an MTP12 connector instead of an LC connector will increase the maximum insertion loss 0 5 dB 2 Bulk reconfi...

Страница 45: ...figuration 5 to 20 dBm DR LC APC Connectors 48 VDC Rear Power CT S320 2S LU0 48TR 01 00 S320 Optical Circuit Switch 320 x 320 Standard Shelf Configuration 5 to 20 dBm DR LC UPC Connectors 48 VDC Rear...

Страница 46: ...2 S320 OCS Software Part Numbers CALIENT Part Number Product Description CT SW S 6 X 000 00 00 S Series Software Release 6 X LC Connectors Standard Shelf Configuration CT SW S 6 X 100 00 00 S Series S...

Отзывы: