background image

3-way installed on the supply 
in diverting configuration 

3-way installed on the return 

3-way valve with normally closed actuator 

(Note: 3-way uses only normally closed actuator)

 

Operation of Normally Closed Valve 

2-way 

3-way 

N.C.   without power 

Port “A” closed 

Port “A” closed 

Port “B” opened 

Port “AB” opened 

N.C. opened with power 

Port “A” opened 

Port “A” opened 

Port “B” closed 

Port “AB” opened 

N.C. manually opened 

Port “A” opened 

Port “A” opened 
Port “B” opened 

Port “AB” opened 

Manual Open (NC act only)

 

Wiring Diagram

 

(NC)

 A 

(NO)

 

AB 

The  manual  opening  is 
achieved  by  moving  the 
manual  opening  lever  to 
the  locked  position.  When 
power  is  applied,  the 
manual 

lever 

unlocks 

automatically.

Содержание Z-one Z1 Series

Страница 1: ...acteristics of Body Material body forged brass optional lead free brass see page 6 for certification statement seat machined brass stem stainless steel two o ring seals EPDM paddle EPDM Medium water a...

Страница 2: ...non condensing Approvals UL873 cUL Listed CE UL 1995 sec 18 air plenum ducts NormallyOpenActuatorsmustbepowereddownduringoff season Flow Characteristics Connection size Flow Coefficient Max Close off...

Страница 3: ...is from A to B see diagram below and must be installed so the paddle closes against the direction of flow as indicated in the following diagrams The 2 way valves can be installed on the supply or on t...

Страница 4: ...ithout power Port A closed Port A closed Port B opened Port AB opened N C opened with power Port A opened Port A opened Port B closed Port AB opened N C manually opened Port A opened Port A opened Por...

Страница 5: ...ll the actuator up Installing the Actuator 1 Move the manual open lever to the lock open position 3 Verify the correct position of the valve stem into the mating actuator hole Rotate stem if required...

Страница 6: ...e the pressure has been reduced to zero and the system temperature is below 100 F 38 C Failure to follow these instructions could result in property damage and or personal injury CAUTION Avoid locatio...

Страница 7: ...ION Syst me fluides sont sous pression ou de temp rature peut s av rer dangereuse Veillez ce que la pression a t r duite z ro et la temp rature du syst me est inf rieure 100 F 38 c De suivre ces instr...

Страница 8: ...___________________________________________ Caleffi North America Inc 3883 W Milwaukee Road Milwaukee WI 53208 Tel 414 238 2360 Fax 414 238 2366 www caleffi com Copyright 2018 Caleffi North America In...

Отзывы: