Function 

The Z-one, a two-position spring return zone valve, 
is  used  in  heating  and  air-conditioning  systems. 
The  Z-one  series consist  of  a  Z1 actuator  which  is 
easily attached to a Z2 (2-way) or Z3 (3-way) valve 
body.  Z1  actuator  is  equipped  with  or  without 
auxiliary switch.  

The  Z-one  actuator  has  a  synchronous  motor  that 
winds the return spring and moves the valve paddle 
to the desired position. When power is removed the 
actuator  spring  returns  the  valve  paddle.

 

24V 

actuators  use  a  sealed  reed  switch  for  end  switch, 
requiring no minimum current load. 

US Patent 7,048,251 

Technical Characteristics of Body 

Material:   - body: 

forged brass   (optional lead-free brass, see page

 6

 for

cert

ification

 statement)

- seat:

machined brass 

- stem:

stainless steel 

- two o-ring seals

EPDM 

- paddle

EPDM 

Medium:    

water and glycol  

Maximum percent of glycol: 

50% 

Temperature range:  

32 to 240°F (0 

– 115°C) 

Max. static pressure: 

15 psi (1 bar) steam 
300 psi (20 bar) 

Connection:  -press  (lay length: 3-5/8

”; overall length 5-5/8”) 

½”, ¾” 1” 

-sweat

½”, ¾” 1” & 1 ¼” 

- NPT

½”, ¾” & 1” 

- SAE flare

½” 

- inverted flare

 

½”, ¾” & 1” sweat, fittings separate 

Lay length (press connections): 

size ½ inch: 3 ½

” 

size ¾ inch: 3 

5

/

8

” 

size ¾ inch (PL): 5

” 

size 1 inch: 4 

1

/

8

” 

Technical Characteristics of Actuator

 

Material:  - base and cover: 

polycarbonate 

- base plate:

aluminum 

Motor: 

- voltage:

24 VAC 50/60 Hz Class 2 
120 VAC 50/60 Hz 
208 VAC 50/60 Hz 
230 VAC 50/60 Hz 
277 VAC 50/60 Hz 

- current draw:

24 VAC 

– 300 mA 

120 VAC 

– 55 mA 

208 VAC 

– 30 mA 

230 VAC 

– 25 mA 

277 VAC 

– 20 mA 

Содержание Z-one Z1 Series

Страница 1: ...acteristics of Body Material body forged brass optional lead free brass see page 6 for certification statement seat machined brass stem stainless steel two o ring seals EPDM paddle EPDM Medium water a...

Страница 2: ...non condensing Approvals UL873 cUL Listed CE UL 1995 sec 18 air plenum ducts NormallyOpenActuatorsmustbepowereddownduringoff season Flow Characteristics Connection size Flow Coefficient Max Close off...

Страница 3: ...is from A to B see diagram below and must be installed so the paddle closes against the direction of flow as indicated in the following diagrams The 2 way valves can be installed on the supply or on t...

Страница 4: ...ithout power Port A closed Port A closed Port B opened Port AB opened N C opened with power Port A opened Port A opened Port B closed Port AB opened N C manually opened Port A opened Port A opened Por...

Страница 5: ...ll the actuator up Installing the Actuator 1 Move the manual open lever to the lock open position 3 Verify the correct position of the valve stem into the mating actuator hole Rotate stem if required...

Страница 6: ...e the pressure has been reduced to zero and the system temperature is below 100 F 38 C Failure to follow these instructions could result in property damage and or personal injury CAUTION Avoid locatio...

Страница 7: ...ION Syst me fluides sont sous pression ou de temp rature peut s av rer dangereuse Veillez ce que la pression a t r duite z ro et la temp rature du syst me est inf rieure 100 F 38 c De suivre ces instr...

Страница 8: ...___________________________________________ Caleffi North America Inc 3883 W Milwaukee Road Milwaukee WI 53208 Tel 414 238 2360 Fax 414 238 2366 www caleffi com Copyright 2018 Caleffi North America In...

Отзывы: