background image

Materials:     -Body:

low-lead brass (

<

0.25% lead content) 

-Shutter, seats and sliding guides:                                  PPO 
-Springs:                                                         stainless steel 
-Seals:                                                peroxide-cured EPDM 

Suitable fluids:

water, 30% max glycol solution     

Setting range (outlet temperature):

85–150

°

F (30–65

°

C) 

Tolerance:

           ±3

°

F

 

(±2

°

C) 

Max. working pressure (static):

200 psi (14 bar) 

Max. operating differential pressure (dynamic):

   75 psi (5 bar) 

Max. recommended differential pressure:

20 psi (1.5 bar) 

Max. hot water inlet temperature:      

200

°

F (93

°

C) 

Max.  inlet  pressure  ratio  (H/C  or  C/H)  for  optimum  performance:       

  2:1                                       

Min. temperature difference between hot water inlet and mixed 
  water outlet for optimum performance:

27ºF (15ºC) 

Min. flow rate to ensure optimal performance:           1.0 GPM (3.8 L/min)

Lay length, hot to cold inlet:    (½” &  ¾” press connection)

5

/

8

”         

(1” press connection) 

1

/

8

”       

Certified to:

Function

The Caleffi MixCal™ three-way thermostatic mixing valve is used in 

systems producing domestic hot water or in hydronic and radiant 

heating  systems.  With  the  unique  mixing  chamber  design,  MixCal 

produces very stable mixed water temperture as inlet temperatures 

and pressures vary. Scale formation is minimized with anti-scale 

polymer sliding surfaces, preventing siezing or erratic mixed 

temperatures. O-ring seals made from durable peroxide-cured EPDM 

resist wear from common water treatment  additives such as chlorine 

and chloramines.

Product range

521A Series Three-way thermostatic mixing valve: 
“C” models include inlet check valves. “419, 519, 619” models include 

outlet gauge adapter. Connections: union thread NPT male, sizes ½”, 

¾”, 1”; union sweat, sizes ½”, ¾”, 1”; union press, sizes ½” , ¾”, 1”; 

union  PEX crimp, sizes ½” , ¾”, 1”.

Technical Characteristics

MixCal™ Adjustable three-way thermostatic mixing valve

521 series 

© Copyright 20

20

 Caleffi

38476.1

3

www.caleffi.com

INSTALLATION AND COMMISSIONING MANUAL

1.

ASSE 1017/CSA B125.3, certified by ICC-ES, file

PMG-1357

2. Complies with 

NSF/ANSI 372-2011, Drinking

Water System

 

Components-Lead Content

Reduction of Lead in

 

Drinking Water Act,

California Health and Safety

 

Code 116875

S.3874, Reduction of Lead in

 

Drinking Water Act,

as 

certified by ICC-ES, file

 

PMG-1360.

1

Содержание MixCal 521410A

Страница 1: ...ems With the unique mixing chamber design MixCal produces very stable mixed water temperture as inlet temperatures and pressures vary Scale formation is minimized with anti scale polymer sliding surfa...

Страница 2: ...s do not endanger people CAUTION To prevent any damage which will cause the electronic mixing valve to not operate correctly treat highly aggressive water before entering the thermostatic mixing valve...

Страница 3: ...ns contenues dans ce manuel il peut ne pas fonctionner correctement et peut mettre en danger l utilisateur ATTENTION S assurer que tous les raccordements sont tanches ATTENTION Les temp ratures de l e...

Страница 4: ...hot or cold water for other uses or variations in the incoming temperature the thermostatic mixing valve automatically regulates the water flow to obtain the required temperature COLD HOT MIX Inlet po...

Страница 5: ...talling a Caleffi MixCal series 521 thermostatic mixing valve the system must be inspected to ensure that it s operating conditions are within the range of the thermostatic mixing valve checking for e...

Страница 6: ...9A and 521619A with integral outlet port temperature gauges provide a time saving temperature setting process to get close to the desired temperture Use of a digital thermometer is recommended for det...

Страница 7: ...with inlet check valves AC models can be used instead of separately installed check valves Refer to principle of operation on page 8 SUPPLY MIX 3 2 4 WATER HEATER Domestic hot water system without rec...

Страница 8: ...port of the mixing valve Ideally this flow should be adjusted so that the rate of heat transfer from the tank to the recirculating loop exactly balances the rate of heat loss from the recirculating l...

Страница 9: ...4A NA20669C 59906A NA20666 Press NA16266 NA20667 PEX crimp F61008 F0000521 NA20667A NA10486 Replacement parts Replacement body Complies to requirements of NSF ANSI 372 2016 low lead as certified by IC...

Страница 10: ...ixing valve will provide a very high level of performance However in some circumstances where the following maintenance schedule is not followed problems may arise Recommended maintenance schedule Tes...

Страница 11: ...2 61 2 4 25 8 521617AC 1 31 4 61 2 83 4 61 8 25 8 At minimum temperature position on adjusting knob Model with integral outlet temperature gauge Code A B C D E F Sweat connections 521409A 1 2 21 4 41...

Страница 12: ...the valve b Starvation of the water supplies at the inlets of the valve c Incorrect commissioning of the valve Restore inlet conditions within the limits of the valve Erratic flow of water from the va...

Отзывы: