© Caleffi 11236_iSolar_Plus.mon
us.ind
d
|
46
For control and service work, the operating mode of the
controller can be manually adjusted. For this purpose, select
the adjustment value MAN1, MAN2 in which the following
adjustments can be made:
Operating mode
• MAN1 / MAN2
Operating mode
OFF
:
relay off
(flashing) +
Auto :
relay in automatic operation
ON
:
relay on
(flashing) +
+ /
MAN1 / MAN2:
Operating mode
Adjustment range:
OFF, Auto, ON
Factory setting: Auto
Language
The menu language can be adjusted in this channel.
• dE : German
• En : English
• Fr : French
LANG:
Language selection
Selection: dE, En, Fr
Factory setting: En
Unit
In this adjustment channel, the display unit for temperatures
and temperature differences can be chosen. The unit can be
switched between °C / K and °F / °Ra during operation.
Temperatures and temperature differences in °F and °Ra
are displayed without units. If the indication is set to °C, the
units are displayed with the values.
UNIT:
Temperature unit selection
Selection: °F, °C
Factory setting: °C
Note:
Always adjust the operating mode back to
“Auto” when the control and service work is
completed. Normal operation is not possible in
manual mode.
Reset
By using the reset function, all adjustments will be set back
to the factory settings.
Î
To initiate a reset, press button 3
Any previous adjustments will be lost. Therefore, initi-
ating the reset function is always followed by a security
enquiry.
Only confirm the security enquiry if you are sure
that you wish to reset all adjustments to the factory
settings!
RESE
Reset function
Security enquiry:
Î
To confirm the security enquiry, press button 3
Note:
Whenever a reset has been completed, the
controller runs the commissioning menu again
(see chap. 3).
HE pump control
This option is used for controlling high-efficiency pumps via
a VBus
®
/ PWM adaptor. The power supply of the pump(s)
takes place via the semiconductor relay(s). For pump speed
control with activated ADA1 / ADA2 option, the relay is swit-
ched on or off (no pulse packets). Temperature dependent
speed information is transmitted via the VBus
®
. The relay will
remain deactivated for 1 hour after its switch-off conditions
have been fulfilled (pump protection).
ADA1 / ADA2:
HE pump control
Adjustment range: ON / OFF
Factory setting: OFF
Note:
The parameter ADA1 refers to relay 1 and is
available in all system layouts. The parameter
ADA2 refers to relay 2 and is available in the
system layouts 2, 6, 7, 8.