CMX / CMX1 / CMX2:
Maximum collector temp.
Adjustment range:
150 ... 320 °F
[70 ... 160 °C]
in steps of 1 °F [1 °C]
Factory setting:
230 °F [110 °C]
Collector cooling function
When the collector cooling function is activated, the controller
aims to keep the collector at an operational temperature.
When the adjusted maximum tank temperature is reached,
solar loading stops. If the collector temperature increases
to the adjusted maximum collector temperature, the solar
pump is activated until the collector temperature falls at least
10 °Ra [5 K] below the maximum collector temperature. The
tank temperature may increase (subordinate active maximum
tank temperature), but only up to 200°F [95 °C] (emergency
shutdown of the tank).
If the collector cooling function is active,
and
(flashing)
is shown on the display.
OCC / OCC1 / OCC2:
Option collector cooling
Adjustment range: OFF / ON
Factory setting: OFF
Note:
This function will only be available if the system
cooling function (OSYC) is deactivated.
When the system cooling function is activated, the control-
ler aims to keep the solar system operational for a longer
time. The function overrides the maximum tank temperature
to provide thermal relief of the collector field and the heat
transfer fluid on hot days.
If the tank temperature is higher than the maximum tank
temperature (S MX / S1MX) and the switch-on tempera-
ture difference DTCO is reached, the solar system remains
activated. Solar loading is continued until either the tank
temperature reaches 200 °F [95 °C] (emergency shutdown
of the tank), the temperature difference falls below the ad-
justed value DTCF or the collector emergency shutdown
temperature EM is reached.
If the system cooling function is active,
and
(flashing)
is shown on the display.
System cooling function
OSYC:
Option system cooling
Adjustment range: OFF / ON
Factory setting: OFF
DTCO:
Switch-on temperature diff.
Adjustment range:
2.0 ... 60.0 °Ra
[1.0 ... 30.0 K]
in steps of 1 °Ra [0.5 K]
Factory setting:
40.0°Ra [20.0 K]
DTCF:
Switch-off temperature diff.
Adjustment range:
1.0 ... 59.0 °Ra
[0.5 ... 29.5 K]
in steps of 1 °Ra [0.5 K]
Factory setting:
30.0 °Ra [15.0 K]
Note:
This function will only be available if the collector
cooling function (OCC) is deactivated.
Note:
In 2-tank-systems, the cooling functions will only
affect tank 1, respectively the bottom area of the
tank (such as in Arr = 4).
Cooling functions
In the following the three cooling functions – collector
cooling, system cooling and tank cooling – are described
in detail. The following notes are valid for all three cooling
functions:
Note:
The cooling functions will not become active as
long as solar loading is possible.
Note:
In system layout 10, the parameter CMX is
available without the OCC function. In system
layout 10, CMX is used to set the activation tem-
perature for the heat dump function. No other
switch-on condition is needed in that case.