background image

9

Actuation relays

The board features the auxiliary replay contacts used to control auxiliary equipment and alarms.

IN1  

  input relay for voltage free contact. When the contact is closed, strainer 
cleaning is inhibited

OUT1   relay output N.A. The contact closes when the strainer is in the cleaning 

phase (max 48V,1A)

ALARM  relay output N.A. for alarms indication (48V, 1A max)
G. OUT  output for control of cold water injection valve on drain (max 5(2)A 250V). 

The relay can drive a motorised diverter valve with 3-contact command.

MAINS LOSS

SIGNAL ACTIVE

OUT1

Open

Closed

ALARM

Open

Closed

Operation in parallel

Two or more strainers can be connected in parallel to increase the filtration capacity of the system, in cases in which there is no bypass provided 
and the application calls for continuous service. Make sure however, that the cleaning phase does not occur at the same time. For this reason, if it is 
detected that another device connected to the strainer is in the active phase, the system waits until the device in question is no longer operating. For 
simple hook-up of the parallel connection of multiple devices (up to a maximum of 10), the following wiring diagram can be used:

MAX10

IN1

OUT1

ALARM

IN1

OUT1

ALARM

1

2

3

4

5

6

1

2

3

4

5

6

IN1

OUT1

ALARM

1

2

3

4

5

6

This connection can be made using a shielded twisted pair with minimum conductor size of 0.5 mm

. Maximum length of connections between one 

device and another is 2.95 m. The cable must be routed through data trunking carrying only very low voltage cables. During operation, with a direct 
connection between OUT1 and IN1, when a controller performs a cleaning cycle, its display shows a flashing “I” message to indicate that contact 
IN1 is closed.

IMPORTANT!   Comply with the wiring diagram and do not invert connections 1 – 2 from one device to the next.
 

 Operation not recommended in the case of activation of the cleaning cycle by means of 

D

p. Enabling preferable via programmed 

cleaning; in the case of an electric supply loss of one of the strainers it is not possible to guarantee correct operation of the system: 
the other strainers will be inhibited.

Remote control via MODBUS

Make the connection using the “BUS” terminals:

BMS

RS485/MODBUS-RTU

A

B

BUS

SCH

-

2

1

+

S2

-

2

1

+

S1

Protocol type

BUS

Baud Rate

Data bit

Parity

Stop bit

Handshake

Unit Load

MODBUS-RTU

RS-485

9600

8

EVEN

1

None

1/8 UL

Transmission

Actuator relay status summary table:

With this connection, if one of the dirtmagclean 
units performs a cleaning cycle or assumes alarm 
status, a flashing "I" message will be shown on all 
the devices and cleaning of the other strainers is 
inhibited until the device, in cleaning status or alarm 
mode, resumes its normal operation or filtration.

Содержание DIRTMAGCLEAN 579 Series

Страница 1: ...nel Display Operating principle Menu Forcing menu Parameters menu Historic data menu Communication Information Drainage temperature limitation Faults Alarm management 2 3 4 6 7 11 PROGRAMMING MANUAL C...

Страница 2: ...ay The following information normally appears on the display Day of the week Probe S1 pressure Operating status Measured p Time Probe S1 temperature B battery alarm I input relay IN1 energized Operati...

Страница 3: ...phase you can supply the necessary additives to the device 1 5 Automatic checks Use the UP or DOWN keys to select the submenu The regulator performs a periodic check on operation of the various strain...

Страница 4: ...selected based on the plant characteristics values lower than 10kPa cannot be selected Delayed Dp When Dp exceeds a specified value the same value used to start the instantaneous cleaning cycle cleani...

Страница 5: ...the alarm error code DATE and TIME show the exact moment when the alarm tripped 3 2 Faults Press OK to view the faults history The fault number is displayed with the associated code date and time of r...

Страница 6: ...llowing the corrective action an alarms reset is required to allow the device to perform a loading cycle and assume correct operating status during this phase check that there are no anomalous operati...

Страница 7: ...e network to have the actuator replaced isolate and empty the device disconnect the electric supply replace the motor and return the system to operation Perform the alarms reset fuses fault disconnect...

Страница 8: ...his the plant must be de energised and the device must be emptied Once the new sensor has been installed proceed with the alarm reset E 23 sensor 1 temperature measurement error sensor internal fault...

Страница 9: ...ARM 1 2 3 4 5 6 This connection can be made using a shielded twisted pair with minimum conductor size of 0 5 mm2 Maximum length of connections between one device and another is 2 95 m The cable must b...

Страница 10: ...A ADDRESS Function 0x06 Write Single Register Used to write a single parameter 16 bit The frame has the following structure dev Addr Address of the device on the RS485 net 1 250 Func Function code 6 R...

Страница 11: ...alve blocked closed alarm bit 8 measurement error alarm on sensor 1 alarm with automatic alarm reset bit 9 sensor 1 not correctly connected alarm with automatic alarm reset bit 10 measurement error al...

Страница 12: ...ak alarm 16 sensor 2 clip break alarm 20 sensor 1 pressure measurement error 21 sensor 1 pressure measurement over range error 22 sensor 1 pressure measurement under range error 23 sensor 1 temperatur...

Страница 13: ...onth enabled for cleaning 1 28 PA0009 1009 Cleaning start minute 1 1 0 59 59 PA0010 1010 Cleaning start hour 1 1 0 23 23 PA0013 1013 Maximum pressure delta in tenths of a KPa 1 1 100 150 5000 PA0017 1...

Страница 14: ...14...

Отзывы: