background image

6

E 05

inlet valve blocked 

alarm

inlet ball valve stem breakage

empty the device. Disconnect the electric supply. Isolate the 

system upstream from the strainer. Replace the inlet ball valve. 

Remake the electrical connections, switch on the electric 

supply and perform a device reset.

Check valve dirty or blocked

Isolate and empty the device. Check that P2 does not move 

downward, otherwise dismantle downstream from the check 

valve and clean 

drain problem identified as problem 

on the inlet valve

 check efficiency of the drain and that the cooling valve, if pres-

ent, is not creating back pressure during discharge

 inlet valve force to open

remove valve forcing and perform 

an alarms reset.

valves protection fuse has blown

 disconnect the device electric supply and check the cables for 

possible damage, humidity or other anomalous conditions that 

might have caused the fuse to blow. Change the valves fuse 

and reconnect the electric supply. Perform an alarms reset

E 07

drain valve blocked 

open alarm

valve blocked

close the inlet valve. Make sure the device is empty. Contact 

service to have the valve replaced after disconnecting the 
electric supply. Restart the system and clear the alarm by 

performing the alarms reset procedure.

faulty actuator

contact the service network to have the actuator replaced: 

isolate and empty the device, disconnect the electric supply, 

replace the motor, and return the system to operation. Perform 

the alarms reset.

fuses fault

 disconnect the electric supply and replace the valves 

protection fuse. Reconnect the electric supply and perform an 

alarms reset

complete pressure absence on 

domestic water.

check presence of pressure on domestic water system and 

restore correct operating conditions of the system before 

performing an alarms reset.

E 08

drain valve blocked 

closed alarm

valve blocked

close the inlet valve. Open the drain manually or remove the 

auxiliary drain cap. Contact service to have the valve replaced 

after disconnecting the electric supply. Restart the system and 

clear the alarm by performing the alarms reset procedure.

faulty actuator

contact the service network to have the actuator replaced: 

isolate and empty the device, disconnect the electric supply, 

replace the motor, and return the system to operation. Perform 

the alarms reset.

fuses fault

disconnect the electric supply and replace the valves 

protection fuse. Reconnect the electric supply and perform an 

alarms reset

drain blocked

inspect drain and remove any obstacles that prevent the water 

from flowing away.

inlet valve

blocked open

perform a check of the inlet valve and, if necessary, assess the 

possibility of replacing it, contacting technical service.

domestic water valve open

Perform a check of the domestic water valve and contact 

technical service.

E 10

error, communication 

with sensor 1 not 

possible

sensor disconnected

disconnect the controller electric supply and check correct 

connection of the terminal and sensor cables. Check that the 

sensor 1 cable is not damaged or severed. Reconnect the 

electric supply: the alarm is self-resetting.

E 12

error, communication 

with sensor 2 not 

possible

 sensor disconnected

disconnect the controller electric supply and check correct 

connection of the terminal and sensor cables. Check that the 

sensor 2 cable is not damaged or severed. Reconnect the 

electric supply: the alarm is self-resetting

E 13

domestic water low 

pressure alarm

domestic water shut-off valve closed

open the domestic water shut-off valve 

upstream from the device, if present

 complete absence of line pressure 

during filling in mode A

check line pressure.

Perform an alarm reset to clear the alarm.

cleaning nozzles clogged

device maintenance can be carried out only by expert person-

nel: contact Caleffi for instructions.

E 14

air vent blocked

air vent cap tightened in closing 

direction

unscrew and open the air vent cap. 

Perform an alarm reset to clear the alarm.

E 15

sensor 1 clip break 

alarm

sensor 1 erroneously removed during 

operation of the device

refit the sensor correctly and check correct sealing of the sys-

tem. Restart the system by means of an alarm reset

sudden drop of plant pressure due to 

a hose burst event or another fault

inspect the plant and check that there are no faults or 

anomalous behaviours such as to result in a drop of plant 

pressure. Restore the correct static pressure value and restart 

the system by performing the alarm reset procedure.

7

Содержание DIRTMAGCLEAN 579 Series

Страница 1: ...nel Display Operating principle Menu Forcing menu Parameters menu Historic data menu Communication Information Drainage temperature limitation Faults Alarm management 2 3 4 6 7 11 PROGRAMMING MANUAL C...

Страница 2: ...ay The following information normally appears on the display Day of the week Probe S1 pressure Operating status Measured p Time Probe S1 temperature B battery alarm I input relay IN1 energized Operati...

Страница 3: ...phase you can supply the necessary additives to the device 1 5 Automatic checks Use the UP or DOWN keys to select the submenu The regulator performs a periodic check on operation of the various strain...

Страница 4: ...selected based on the plant characteristics values lower than 10kPa cannot be selected Delayed Dp When Dp exceeds a specified value the same value used to start the instantaneous cleaning cycle cleani...

Страница 5: ...the alarm error code DATE and TIME show the exact moment when the alarm tripped 3 2 Faults Press OK to view the faults history The fault number is displayed with the associated code date and time of r...

Страница 6: ...llowing the corrective action an alarms reset is required to allow the device to perform a loading cycle and assume correct operating status during this phase check that there are no anomalous operati...

Страница 7: ...e network to have the actuator replaced isolate and empty the device disconnect the electric supply replace the motor and return the system to operation Perform the alarms reset fuses fault disconnect...

Страница 8: ...his the plant must be de energised and the device must be emptied Once the new sensor has been installed proceed with the alarm reset E 23 sensor 1 temperature measurement error sensor internal fault...

Страница 9: ...ARM 1 2 3 4 5 6 This connection can be made using a shielded twisted pair with minimum conductor size of 0 5 mm2 Maximum length of connections between one device and another is 2 95 m The cable must b...

Страница 10: ...A ADDRESS Function 0x06 Write Single Register Used to write a single parameter 16 bit The frame has the following structure dev Addr Address of the device on the RS485 net 1 250 Func Function code 6 R...

Страница 11: ...alve blocked closed alarm bit 8 measurement error alarm on sensor 1 alarm with automatic alarm reset bit 9 sensor 1 not correctly connected alarm with automatic alarm reset bit 10 measurement error al...

Страница 12: ...ak alarm 16 sensor 2 clip break alarm 20 sensor 1 pressure measurement error 21 sensor 1 pressure measurement over range error 22 sensor 1 pressure measurement under range error 23 sensor 1 temperatur...

Страница 13: ...onth enabled for cleaning 1 28 PA0009 1009 Cleaning start minute 1 1 0 59 59 PA0010 1010 Cleaning start hour 1 1 0 23 23 PA0013 1013 Maximum pressure delta in tenths of a KPa 1 1 100 150 5000 PA0017 1...

Страница 14: ...14...

Отзывы: