background image

E 16

 sensor 2 clip break 

alarm

sensor 2 erroneously removed during 

operation of the device

refit the sensor correctly and check correct sealing of the sys-

tem. Restart the system by means of an alarm reset.

sudden drop of plant pressure due to 

a hose burst event or another fault

inspect the plant and check that there are no faults or 

anomalous behaviours such as to result in a drop of plant 

pressure. Restore the correct static pressure value and restart 

the system by performing the alarm reset procedure.

E 20

sensor 1 pressure 

measurement error

 sensor internal fault

contact the service network and replace the sensor: to do 

this, the plant must be de-energised and the device must be 

emptied. Once the new sensor has been installed, proceed 

with the alarm reset.

E 21

sensor 1 pressure 

measurement over 

range error

surpassing sensor maximum pres-

sure

check correct operation of the plant, of the expansion vessels 

and of the safety relief valves. Surpassing the sensor maximum 

pressure values is a very hazardous condition for the plant and 

for persons: carry out a general check of the plant.

E 22

sensor 1 pressure 

measurement under 

range error

sensor internal fault

contact the service network and replace the sensor: to do 

this, the plant must be de-energised and the device must be 

emptied. Once the new sensor has been installed, proceed 

with the alarm reset.

E 26

sensor 2 pressure 

measurement error

sensor internal fault

contact the service network and replace the sensor: to do 

this, the plant must be de-energised and the device must be 

emptied. Once the new sensor has been installed, proceed 

with the alarm reset.

E 27

sensor 2 pressure 

measurement over 

range error

 surpassing sensor maximum 

pressure

check correct operation of the plant, of the expansion vessels 

and of the safety relief valves. Surpassing the sensor maximum 

pressure values is a very hazardous condition for the plant and 

for persons: carry out a general check of the plant

E 28

sensor 2 pressure 

measurement under 

range error

sensor internal fault

contact the service network and replace the sensor: to do 

this, the plant must be de-energised and the device must be 

emptied. Once the new sensor has been installed, proceed 

with the alarm reset.

E 23

 sensor 1 temperature 

measurement error

sensor internal fault

contact the service network and replace the sensor: to do 

this, the plant must be de-energised and the device must be 

emptied. Once the new sensor has been installed, proceed 

with the alarm reset.

E 24

sensor 1 temperature 

measurement over 

range error

surpassing of maximum temperature 

of sensor 1 (e.g. device internal 

temperature above 100°C)

reduce system temperature and perform the plant safety shut-

down procedure, checking the adjustment systems and plant 

safety systems. Excessively high temperatures can damage the 

device and other components of the plant. Restart the plant 

after having performed the foregoing checks and corrective 

actions to guarantee that the maximum temperatures are 

within the admissible values.

E 25

 sensor 1 temperature 

measurement under 

range error

sensor internal fault

contact the service network and replace the sensor: to do 

this, the plant must be de-energised and the device must be 

emptied. Once the new sensor has been installed, proceed 

with the alarm reset

E 29

  sensor 2 temperature 

measurement error

sensor internal fault

contact the service network and replace the sensor: to do this, 

the plant must be de-energised and the device and the plant 

must be emptied. Once the new sensor has been installed, 

proceed with the alarm reset.

E 30

  sensor 2 temperature 

measurement over 

range error

surpassing of maximum tempera-

ture of sensor 1 (e.g. device internal 

temperature above 100°C)

reduce system temperature and perform the plant safety shut-

down procedure, checking the adjustment systems and plant 

safety systems. Excessively high temperatures can damage the 

device and other components of the plant. Restart the plant 

after having performed the foregoing checks and corrective 

actions to guarantee that the maximum temperatures are 

within the admissible values.

E 31

sensor 2 temperature 

measurement under 

range error

sensor internal fault

contact the service network and replace the sensor: to do this, 

the plant must be de-energised and the device and the plant 

must be emptied. Once the new sensor has been installed, 

proceed with the alarm reset.

8

Содержание DIRTMAGCLEAN 579 Series

Страница 1: ...nel Display Operating principle Menu Forcing menu Parameters menu Historic data menu Communication Information Drainage temperature limitation Faults Alarm management 2 3 4 6 7 11 PROGRAMMING MANUAL C...

Страница 2: ...ay The following information normally appears on the display Day of the week Probe S1 pressure Operating status Measured p Time Probe S1 temperature B battery alarm I input relay IN1 energized Operati...

Страница 3: ...phase you can supply the necessary additives to the device 1 5 Automatic checks Use the UP or DOWN keys to select the submenu The regulator performs a periodic check on operation of the various strain...

Страница 4: ...selected based on the plant characteristics values lower than 10kPa cannot be selected Delayed Dp When Dp exceeds a specified value the same value used to start the instantaneous cleaning cycle cleani...

Страница 5: ...the alarm error code DATE and TIME show the exact moment when the alarm tripped 3 2 Faults Press OK to view the faults history The fault number is displayed with the associated code date and time of r...

Страница 6: ...llowing the corrective action an alarms reset is required to allow the device to perform a loading cycle and assume correct operating status during this phase check that there are no anomalous operati...

Страница 7: ...e network to have the actuator replaced isolate and empty the device disconnect the electric supply replace the motor and return the system to operation Perform the alarms reset fuses fault disconnect...

Страница 8: ...his the plant must be de energised and the device must be emptied Once the new sensor has been installed proceed with the alarm reset E 23 sensor 1 temperature measurement error sensor internal fault...

Страница 9: ...ARM 1 2 3 4 5 6 This connection can be made using a shielded twisted pair with minimum conductor size of 0 5 mm2 Maximum length of connections between one device and another is 2 95 m The cable must b...

Страница 10: ...A ADDRESS Function 0x06 Write Single Register Used to write a single parameter 16 bit The frame has the following structure dev Addr Address of the device on the RS485 net 1 250 Func Function code 6 R...

Страница 11: ...alve blocked closed alarm bit 8 measurement error alarm on sensor 1 alarm with automatic alarm reset bit 9 sensor 1 not correctly connected alarm with automatic alarm reset bit 10 measurement error al...

Страница 12: ...ak alarm 16 sensor 2 clip break alarm 20 sensor 1 pressure measurement error 21 sensor 1 pressure measurement over range error 22 sensor 1 pressure measurement under range error 23 sensor 1 temperatur...

Страница 13: ...onth enabled for cleaning 1 28 PA0009 1009 Cleaning start minute 1 1 0 59 59 PA0010 1010 Cleaning start hour 1 1 0 23 23 PA0013 1013 Maximum pressure delta in tenths of a KPa 1 1 100 150 5000 PA0017 1...

Страница 14: ...14...

Отзывы: