SATK20 & SATK30

18

Fault Finding

Fault

Indications

Possible Cause of Fault

Operations to be Performed

The water is not

heating

 DHW LED on

primary circuit isolating valve closed

open the isolating valve

modulating valve actuator connector disconnected

re-connect actuator connector

modulating valve actuator disconnected from valve body

re-connect actuator

modulating valve actuator faulty

call qualified personnel to have it replaced

DHW temperature probe cable inverted with heating probe

restore correct connection

presence of air in the system

restore correct connection

electronic controller not working

call qualified personnel to have it replaced

valve obturator blocked in closed position

call qualified personnel to have it replaced

centralised system not working

contact person in charge of system

FAULT led lit + error

code 6 active

DHW temperature probe disconnected

re-connect probe

DHW temperature probe faulty

call qualified personnel to have it replaced

FAULT led lit + error

code 79 active

DHW temperature probe faulty

restore correct switch setting

DHW Led off

DHW priority flow meter disconnected

re-connect flow meter

DHW priority flow meter faulty

call qualified personnel to have it replaced

all LEDs are off

electricity power supply switched off

switch on electricity supply

protection fuse burnt out

call qualified personnel to have it replaced

The water is hot but

does not reach the

desired temperature

DHW led on

domestic water cycle temperature set point too low

increase set point

HIU strainer clogged

call qualified personnel to have it serviced

exchanger partly clogged

call qualified personnel to have it serviced

modulating valve actuator faulty

call qualified personnel to have it replaced

valve obturator blocked in intermediate position

call qualified personnel to have it replaced

modulating valve actuator connector disconnected

re-connect actuator connector

DHW temperature probe cable inverted with heating probe

restore correct connection

excessive demand for DHW

decrease demand

electronic controller not working

call qualified personnel to have it replaced

centralised system temperature insufficient

contact person in charge of system

primary circuit flow rate insufficient

contact person in charge of system

The hot water

temperature reached

is too high

DHW led on

domestic water cycle temperature set point too high

decrease set point

DHW temperature probe cable inverted with heating probe

restore correct connection

modulating valve actuator faulty

call qualified personnel to have it replaced

valve obturator blocked in intermediate or open position

call qualified personnel to have it replaced

electronic controller not working

call qualified personnel to have it replaced

Hot water flow rate

is insufficient

DHW led on

HIU strainer clogged

call qualified personnel to have it replaced

possible domestic water system shut-off valves

partly open

open the valves

centralised domestic circuit cold water flow rate insufficient

call qualified personnel to have it serviced

The is no hot water

flow

DHW led off

possible domestic water system shut-off valves closed

open the valves

no cold water in centralised domestic circuit

call qualified personnel to have it serviced

HIU strainer completely clogged

call qualified personnel to have it serviced

heat exchanger completely blocked

call qualified personnel to have it serviced

Содержание Altecnic SATK20

Страница 1: ...SATK20 SATK30 heat interface unit Installation Operation Maintenance Instructions...

Страница 2: ...roduct range 1 Safety instructions 1 Dimensions and technical speci cation 3 Installation 4 First operation 5 Electronic controller 6 Safety and alarms 7 SATK20103 and SATK20203 components 8 SATK20303...

Страница 3: ...e operation of the device and or system NOTE Risk of electric shock Live parts Shut off the electric supply before opening the HIU cover 1 During installation and maintenance operations always avoid d...

Страница 4: ...Dimensions SATK30 A B C kg G B G B G B 16 A B C kg G B G B G B 19 550 A A B B 65 65 450 C C 59 101 160 65 190 195 430 15 490 46 10 245 110 265 110 85 A A B B 629 65 65 550 C C 159 101 160 65 290 195 5...

Страница 5: ...changer brazed stainless steel Installation The SATK series HIUs are designed for installation in a sheltered domestic environment or similar therefore cannot be installed or used outdoors i e in area...

Страница 6: ...ent Connection to the main supply The device is supplied with an electric supply cable plug not supplied The device should be electrically connected to a 230 V ac single phase earth mains supply using...

Страница 7: ...e cover close the isolating valves empty the HIU using the drain cocks provided remove the spacer piece A remove the blanking plug B install the ow probe in the 1 4 pocket B provided install the ow me...

Страница 8: ...vated the circulation pump shuts down and the and the regulating valve closes Heating cycle activation is indicated by a ashing fault LED on the electronic controller This fault does not affect the ge...

Страница 9: ...d Safety valve fault Error code 76 SATK20103 LOW temperature Removing a fault Normal operating conditions are restored automatically once the faulty safety valve is working correctly again Safety sett...

Страница 10: ...tic water preheating function Heating cycle modulating temperature regulation with compensated set point floor slab heating function Factory settings Components SATK20203 MEDIUM Temperature HIU Item C...

Страница 11: ...ds the drying of the under oor heating screed at low temperatures This function can only be activated and executed if there are no faults It can be activated by pressing and holding the RESET button f...

Страница 12: ...al load under control The thermal response time of the system is thus minimised Safety and alarms Error codes associated with faults signalled by the lighting up of the FAULT LED are also shown on the...

Страница 13: ...The function is enabled by setting dip switch 5 to the ON position During periods when the domestic water cycle is not used if the DHW probe detects a temperature 10 C below the SET value the control...

Страница 14: ...eturn temperature sensor 22 Pressure gauge 23 Filling loop isolation valve 24 Filling loop double check valve 25 Filling loop Not shown on Components illustration Functional characteristics SATK30103...

Страница 15: ...rying of the under oor heating screed at low temperatures This function can only be activated and executed if there are no faults It can be activated by pressing and holding the RESET button for 8 sec...

Страница 16: ...l maintenance procedures should be carried out by an authorised technician Regular maintenance guarantees better ef ciency and helps to save energy Before carrying out any maintenance repair or part r...

Страница 17: ...the new probe Reconnect the connector respecting the only possible way it can be inserted When carrying out maintenance on the electrical system for the connections follow the diagram on page 16 Afte...

Страница 18: ...HW production valve actuator x x x x Thermal safety relief valve x x Thermal safety thermostat x x Heating flow temperature probe x x x x x x x x x x x x x x x Electric supply 230 V ac x x x x x x x x...

Страница 19: ...artly clogged call quali ed personnel to have it serviced modulating valve actuator faulty call quali ed personnel to have it replaced valve obturator blocked in intermediate position call quali ed pe...

Страница 20: ...valves terminals closed open the valves centralised system temperature insuf cient contact person in charge of system electronic controller not working call quali ed personnel to have it replaced prim...