SATK20 & SATK30

14

Operating Cycles SATK30

Domestic water generation:  This cycle always takes priority
over the heating cycle.

When a tap or shower is turned on (detected by the domestic
water flow meter) the DHW cycle is activated, the controller
pilots the modulating valve opening so as to adjust the
temperature detected by the domestic water probe to the
selected set point value.

When the tap or shower is turned off, the modulating valve is
fully closed.

The active domestic water cycle is signalled by the yellow DHW
LED which comes on.

The general domestic water cycle temperature set point can be
set using trimmer P1 and shown on the display.

Heating cycle:  Set point regulation

When space heating is requested by the room thermostat, the
circulation pump is powered while the modulating valve is
opened gradually until the set point temperature is reached.

At the end of the heating cycle, the circulation pump comes to
a stop and the modulating valve is closed.

The active heating cycle is signalled by the yellow CH LED
which comes on.

The heating cycle temperature set point can be set using
trimmer P2 and shown on the display.

Under floor heating function: LOW temperature setting

This cycle aids the drying of the underfloor heating screed at
low temperatures. This function can only be activated and
executed if there are no faults.

It can be activated by pressing and holding the RESET button
for 8 seconds.

The yellow CH LED blinks while the funder floor heating drying
function is in operation.

The function has a duration of 240 hours, and is carried out by
simulating a request to run in heating mode starting from a set
point of 25°˚C and rising in regular intervals to a temperature
of 45˚C.

Once the maximum set point has been reached, the function is
executed, following the same procedures, in reverse (from the
maximum set point to the minimum set point).

This function has priority over heating and hot water cycles,
and can be suspended at any time by pressing and holding the
RESET button for 8 seconds.

Optional functions

- to activate/deactivate the optional

functions the electric power supply must always be turned off.

Domestic water generation: DHW preheating function

The function is enabled by setting dip switch 5 to the ON
position.

During periods when the domestic water cycle is not used, if
the DHW probe detects a temperature 10°C below the SET
value, the controller partially opens the domestic water
modulating valve for the time required (max. 5 mins) to bring
the temperature detected up to a value 5˚C below the set point
value.

Operating Cycles SATK30

48

P2

P1

60

P2

P1

25

8 seconds

5

ON

48

Содержание Altecnic SATK20

Страница 1: ...SATK20 SATK30 heat interface unit Installation Operation Maintenance Instructions...

Страница 2: ...roduct range 1 Safety instructions 1 Dimensions and technical speci cation 3 Installation 4 First operation 5 Electronic controller 6 Safety and alarms 7 SATK20103 and SATK20203 components 8 SATK20303...

Страница 3: ...e operation of the device and or system NOTE Risk of electric shock Live parts Shut off the electric supply before opening the HIU cover 1 During installation and maintenance operations always avoid d...

Страница 4: ...Dimensions SATK30 A B C kg G B G B G B 16 A B C kg G B G B G B 19 550 A A B B 65 65 450 C C 59 101 160 65 190 195 430 15 490 46 10 245 110 265 110 85 A A B B 629 65 65 550 C C 159 101 160 65 290 195 5...

Страница 5: ...changer brazed stainless steel Installation The SATK series HIUs are designed for installation in a sheltered domestic environment or similar therefore cannot be installed or used outdoors i e in area...

Страница 6: ...ent Connection to the main supply The device is supplied with an electric supply cable plug not supplied The device should be electrically connected to a 230 V ac single phase earth mains supply using...

Страница 7: ...e cover close the isolating valves empty the HIU using the drain cocks provided remove the spacer piece A remove the blanking plug B install the ow probe in the 1 4 pocket B provided install the ow me...

Страница 8: ...vated the circulation pump shuts down and the and the regulating valve closes Heating cycle activation is indicated by a ashing fault LED on the electronic controller This fault does not affect the ge...

Страница 9: ...d Safety valve fault Error code 76 SATK20103 LOW temperature Removing a fault Normal operating conditions are restored automatically once the faulty safety valve is working correctly again Safety sett...

Страница 10: ...tic water preheating function Heating cycle modulating temperature regulation with compensated set point floor slab heating function Factory settings Components SATK20203 MEDIUM Temperature HIU Item C...

Страница 11: ...ds the drying of the under oor heating screed at low temperatures This function can only be activated and executed if there are no faults It can be activated by pressing and holding the RESET button f...

Страница 12: ...al load under control The thermal response time of the system is thus minimised Safety and alarms Error codes associated with faults signalled by the lighting up of the FAULT LED are also shown on the...

Страница 13: ...The function is enabled by setting dip switch 5 to the ON position During periods when the domestic water cycle is not used if the DHW probe detects a temperature 10 C below the SET value the control...

Страница 14: ...eturn temperature sensor 22 Pressure gauge 23 Filling loop isolation valve 24 Filling loop double check valve 25 Filling loop Not shown on Components illustration Functional characteristics SATK30103...

Страница 15: ...rying of the under oor heating screed at low temperatures This function can only be activated and executed if there are no faults It can be activated by pressing and holding the RESET button for 8 sec...

Страница 16: ...l maintenance procedures should be carried out by an authorised technician Regular maintenance guarantees better ef ciency and helps to save energy Before carrying out any maintenance repair or part r...

Страница 17: ...the new probe Reconnect the connector respecting the only possible way it can be inserted When carrying out maintenance on the electrical system for the connections follow the diagram on page 16 Afte...

Страница 18: ...HW production valve actuator x x x x Thermal safety relief valve x x Thermal safety thermostat x x Heating flow temperature probe x x x x x x x x x x x x x x x Electric supply 230 V ac x x x x x x x x...

Страница 19: ...artly clogged call quali ed personnel to have it serviced modulating valve actuator faulty call quali ed personnel to have it replaced valve obturator blocked in intermediate position call quali ed pe...

Страница 20: ...valves terminals closed open the valves centralised system temperature insuf cient contact person in charge of system electronic controller not working call quali ed personnel to have it replaced prim...

Отзывы: