11 - CONFIGURATION MENU (installer)
11.5.2 - Setting hysteresis for thermal differential ON-OFF
•
Through the path
then
Menu -> CONFIGUR SEt -> RULE SEt ->
On:OFF
select
,
press
.
OK
•
With the keys
enter the desired hysteresis value
(values may be set from 0.2 °C to 1.2 °C / from 0.3 °F to 2.1 °F - default 0.3 °C/0.4 °F).
•
Press
to confirm.
OK
•
Press the
key to exit.
back
11.5.3 - Setting period duration for modulating Proportional
•
Through the path
then
Menu -> CONFIGUR SEt -> RULE SEt ->
PrOP,
select
press
.
OK
•
With the
keys enter the duration of the desired period
(settable from 7 to 20 minutes, default 10 min.).
•
Press
to confirm.
OK
•Press the
key to exit.
back
11.6 - CHANGE UNIT OF MEASURE FOR TEMPERATURE READING
•
Through the path
then
Menu -> CONFIGUR SEt ->
UNIT SEt
select
press
.
OK
•
Select the desired unit of measure with the
keys: °C or °F, then press
to
OK
confirm.
•
Press the
key to exit.
back
The
thermostat is pre-set in the factory to display temperatures in
programmable
degrees Centigrade (Celsius), it is possible to switch to the Fahrenheit scale or vice
versa with the following procedure:
All temperature set points will be updated according to the new scale.
73
EN
Set
Menù
back
SetT
0
2
4
6
8
10
12
14
16
18
20
22
OK
OK
OK
OK
OK
Set
Menù
back
SetT
0
2
4
6
8
10
12
14
16
18
20
22
OK
1°
2°
Set
Menù
back
SetT
0
2
4
6
8
10
12
14
16
18
20
22
OK
1°
2°