Maintenance

In service tests should be conducted regularly to monitor and record the performance of the valve. 
Deterioration in performance can indicate the need for servicing of the valve and/or water supply. 
If, during these tests, the mixed water temperature has changed significantly from the previous 
test results, record the change before re-adjusting the mixed water temperature. If the final mixed 
water temperature is greater than the permitted values, Verify details quoted in the Installation and 
Commissioning sections of this manual and that service work is required.

The following actions are recommended at least every 12 months, or more frequently if the need 
arises, and that the following steps are checked to maintain optimum valve performance.

With reference to the exploded diagram on page 6:
1) On the Caleffi 5213 series valves, the inlet conic filters (12) on both the hot and cold water 
  supplies can be removed for cleaning by unscrewing the inlet union nuts and carefully 
  pulling apart the connecting piping.
2) The built in check valves (11) on the Caleffi 5213 series valves can be accessed in a similar 
  way to 1) to ensure freedom of operation and correct operation.
3) If service is required, the internal components of the valve can be disassembled for 
  cleaning and de-scaling:

a)  Remove the cap of the valve (1) and the locking nut (2).
b)  Remove the upper body (3) using a suitable spanner.
c)  Remove parts 5-7 noting the correct orientation.
d)  Remove all signs of scale and dirt from the internal part using a suitable de-scaling 
 solution.
e)  Re-assemble all the components.

Once the above servicing is performed follow the commissioning details in the  previous section 
ensuring that a suitably accurate thermometer is used.

Should the valve still not function correctly, it may be necessary to replace the thermal element 
or other components. Refer to spare part kits and contact Caleffi Technical Support for details 
and advice.

Spare parts

With reference to the exploded diagram, the spare parts are available on request for Caleffi 5213 
series valves, see table on page 7.

13

Содержание 521352A

Страница 1: ...ater inlet to ensure stable operation 9 F 5 C Minimum flow rate for stable operation 0 5 gpm 2 l min Certifications 1 ASSE 1070 CSA B125 3 2012 certified by ICC ES file PMG 1357 2 NSF ANSI 372 2011 Dr...

Страница 2: ...at such temperatures do not endanger people Leave this manual for the user SAFETY INSTRUCTION This safety alert symbol will be used in this manual to draw attention to safety related instructions When...

Страница 3: ...stpasinstall mis en service et entretenu correctement selon les instructions contenues dans ce manuel il peut ne pas fonctionner correctement et peut mettre en danger l utilisateur ATTENTION S assurer...

Страница 4: ...way as to maintain constant set temperature of the the mixed water at the outlet A thermostatic element is fully immersed into the mixed water This element then contracts or expands causing movement o...

Страница 5: ...ffi 5213 series is a thermostatic mixing valve suitable for single or multiple point of use applications in accordance with installation rules and indications specified in ASSE 1070 standards The syst...

Страница 6: ...5 Thermostatic element 6 Flow conveyor 7 Lower spring 8 Valve body 9 Union washer quantity 3 per valve 10 Union nut quantity 3 per valve 11 Inlet port male tailpiece with integral check valve quantit...

Страница 7: ...F0000520 NA20657C NA10485 1 NA20660 1 inch NPT male incl w tailpc 59817A NA20660C 59894A 1 NA20669 Sweat 59834A NA20669C 59906A 1 NA20667 PEX crimp F61008 C F0000521 NA20667C NA10486 1 1 C check valve...

Страница 8: ...ation is designed and or installed all current legislation is noted e g the maximum distance from the outlet of the valve to any terminal fitting The connecting hot and cold water supplies must be con...

Страница 9: ...lve Isolating valve Strainer check valve Strainer check valve T Pressure reducing valve if required Temperature limiting valve if required HOT SUPPLY COLD SUPPLY MIXED OUTLET MIX MIX HOT COLD MIX MIX...

Страница 10: ...e 2 15 16 5 7 8 5 3 16 3 1 15 16 2 0 521347A PEX crimp 3 6 5 3 5 8 1 15 16 2 0 521357A PEX crimp 3 6 5 3 5 8 1 15 16 2 0 521367A 1 PEX crimp 3 1 16 6 1 8 5 9 16 3 11 16 1 15 16 2 0 521349A sweat 2 11...

Страница 11: ...ign of the cap the temperature setting can be adjusted by removing the cap from the valve body and reversing the cap onto the temperature adjustment spindle Use the following sequence when commissioni...

Страница 12: ...Temperature adjustment View of temperature adjustment Attaching temperature adjustment cap Temperature adjustment cap in place Locking adjustment spindle with locking nut 1 2 3 4 12...

Страница 13: ...by unscrewing the inlet union nuts and carefully pulling apart the connecting piping 2 The built in check valves 11 on the Caleffi 5213 series valves can be accessed in a similar way to 1 to ensure fr...

Страница 14: ...of the valve Restore inlet conditions within the limits of the valve Erratic flow of water from the valve a Insufficient water supplies b Fluctuations in supply pressure and or temperatures c Adverse...

Страница 15: ...15 this page left blank intentionally...

Страница 16: ...Caleffi North America Inc 3883 West Milwaukee Road Milwaukee WI 53208 T 414 238 2360 F 414 238 2366 4 30 18 16...

Отзывы: