Installation

The following instructions must be read prior to the installation of a Caleffi SinkMixer thermostatic mixing 
valve. The installer should also be aware of his responsibility and duty of care to ensure that all aspects 
of the installation comply with current regulations and legislation. The Caleffi SinkMixer should be installed 
using the appropriate standard, code of practice and legislation applicable to each state and following the 
details in this manual. The Caleffi SinkMixer series must be installed by a licensed plumber.
Prior to the installation of the valve, the system must be checked to ensure that the 

system operating 

conditions fall within the recommended operating range of the valve, i.e. verify supply 
temperatures, supply pressures, risk assessments, etc.

The supply system into which the Caleffi SinkMixer is to be installed must be thoroughly flushed and 
cleaned to remove any debris which may accumulate during the installation. Failure to remove any debris 
will affect the performance and the manufacturer’s warranty on the product. In areas that are subject to 
high levels of aggressive water, provision must be made to treat the water prior to it entering the valve.

The valve is recommended to be installed in a position oriented with the cover to the right with cold inlet/
outlet on the right side (allowing direct connection to the sink’s cold water inlet fitting) resulting in the hot 
inlet/mix outlet on the left aligning direct to the hot water inlet sink fitting. It is essential that the access to 
the valve is not obstructed for future maintenance that may be required to the valve or associated fittings.

It is essential that when the installation is designed and/or installed, all current legislation is noted, e.g. the 
maximum distance from the outlet of the valve to any terminal fitting.

The connecting hot and cold water supplies must be connected to the valve strictly in accordance with 
the indications on the body of the valve. The inlets of the valves are clearly marked with the letter H (Hot) 
and C (Cold). The outlet is marked with the word MIX. The valve has male 3/8” compression threads for 
conection to standard 3/8” compression faucet connectors and stops. 

Where one or both the incoming supply pressures are excessive, a Caleffi pressure reducing valve should 
be installed to reduce the pressure(s) within the limits.

The Caleffi SinkMixer valve is supplied complete with the check valves at the hot and cold inlets.

Mount the SinkMixer valve to the wall underneath the sink with black plastic mounting bracket supplied 
with valve but not attached. Use mounting screw to attach the mounting bracket to the valve to meet 
the orientation described above. Break off the adjustment key for adjusting the termperature, see 
commisioning section. 

To ensure that the performance of the Caleffi SinkMixer valve is maintained (in the event of cold water 
failure), the temperature of the hot water supply at the point of entry to the valve must be a minimum of 
18°F higher than the set mixed water discharge temperature.

If the valve is not installed correctly, it will not function correctly and may put the user in danger.

For single-pipe fixtures (tempered water only), code 521201AP comes 

complete with a plug/nut for the valve cold outlet port. Code NA10741 is a 

5-pack of plugs/nuts to plug cold outlet port when installing code 521201A 

(unit coming without this plug/nut) in single pipe fixture undersink piping.

7

Содержание 521201AP

Страница 1: ...um flow rate for optimum operation 2 3 gpm 8 5 l min Certifications 1 ASSE 1070 CSA B125 3 2012 certified by ICC ES file PMG 1358 2 NSF ANSI 372 2011 Drinking Water Systems Components Lead Content Red...

Страница 2: ...t such temperatures do not endanger people Leave this manual for the user SAFETY INSTRUCTION This safety alert symbol will be used in this manual to draw attention to safety related instructions When...

Страница 3: ...tpasinstall mis en service et entretenu correctement selon les instructions contenues dans ce manuel il peut ne pas fonctionner correctement et peut mettre en danger l utilisateur ATTENTION S assurer...

Страница 4: ...water in such a way as to maintain constant set temperature of the mixed water at the outlet A thermostatic element is fully immersed into the mixed water This element then contracts or expands causin...

Страница 5: ...and under counter applications in accordance with installation rules and indications specified in ASSE 1070 standards The system must be sized taking into account the current legislation with regard...

Страница 6: ...ked at any need Hand changes are forbidden Questodocumentonon daritenersiimpegnativo Ciriserviamoildirittodimodificareinostriprodotti diapportaremiglioramentitecniciedisvilupparliulteriormente Attenzi...

Страница 7: ...or associated fittings It is essential that when the installation is designed and or installed all current legislation is noted e g the maximum distance from the outlet of the valve to any terminal fi...

Страница 8: ...Installation diagram COLD HOT 8 Point of use 521201A 521201AP...

Страница 9: ...to simultaneous demand 5 Once the supply temperatures are stabilized and the normal operating conditions are established the valve can be commissioned The temperature setting can be adjusted by with...

Страница 10: ...D C O L D H O T M I X Remove 1 4 hex key from mounting bracket Remove white cap Adjust temperature setting with 1 4 hex key After adjustment lock the temperature with locking nut Replace cap and store...

Страница 11: ...e following steps are checked to maintain optimum valve performance Use the folllowing recommended procedure 1 On the Caleffi SinkMixer valves the inlet strainers on both the hot and cold water inlet...

Страница 12: ...Starvation of the water supplies at the valve inlets c Incorrect commissioning of the valve Restore inlet conditions within the limits of the valve Erratic flow of water from the valve a Insufficient...

Отзывы: