© Caleffi 11236_iSolar_Plus.mon
us.ind
d
11
|
Maximum temperature limitation
MX3O / MX3F:
Maximum temperature limitation
Adjustment range:
30.0 ... 200.0 °F
[0.0 ... 95.0 °C]
in steps of 1 °C [0.5 °F]
Factory setting:
MX3O: 140.0 °F [60.0 °C]
MX3F: 136.0 °F [58.0 °C]
Minimum temperature limitation
MN3O / MN3F:
Minimum temperature limitation
Adjustment range:
30.0 ... 190.0 °F
[0.0 ... 90.0 °C]
in steps of 1 °C [0.5 °F]
Factory setting (Arr = 2 only):
MN3O: 40.0 °F [5.0 °C]
MN3F: 50.0 °F [10.0 °C]
Minimum and maximum temperature limits can be set for
the heat exchange function.
The maximum temperature limitation uses sensor 4 as
reference sensor.
The maximum temperature limitation function provides
a maximum tem perature setting, usually to reduce scald
risk in a storage tank. If MX3O is exceeded, relay 2 is
switched off until the temperature at sensor 4 falls below
MX3F.
The minimum temperature limitation uses sensor 3 as
reference sensor.
The minimum temperature limitation function provides
a minimum tem perature setting for the heat source in
system layout 2. If the temperature at sensor 3 falls below
MN3O, relay 2 is switched off until the temperature at
sensor 3 exceeds MN3F.
Both switch-on and switch-off temperature differences
DT3O and DT3F are valid for the maximum and minimum
temperature limitation.