FREETIME
® -
HEXAMOTION
®
High Efficiency Recovery Unit
OPERATING AND COMMISSIONING INSTRUCTIONS
MS-CDF-010
Ind F
Maj. 18/05/2017
Créé par : JC
Validé par : AR
Page 38/57
V.8.a.3.
BACNET IP Communication with BASC type
You will find the simplified BACNET at the end of the instructions and commissioning manual.
Accès : Configuration / Communication
BACNET IP must be activate [(7) chapter V.7]. Possibility to know DHCP adress or set IP fixe [(5)(6) chapter V.7].
Possibility to set ID / N°port… [(8) chapter V.7].
BACNET MSTP must be activate [(3) chapter V.7]. Possibility to set speed, ID, adress… [(4) chapter V.7]. Speed = 9600 /
MAC adress = 0 / Device ID = 2640 / Max master = 127
BACnet Type
10XXX = Read and write Binary
20XXX = Read binary
30XXX = Read and write analogue
40XXX = Read analogue
30XXX = Read and write multistate
40XXX = Read multistate
(XXX = MODBUS Adress)
AV = Analogue Value
BV = Binary Value
MSV = Multistate value
BMMD Adress : The BBMD adress is used for discovering devices taht are attached to different BACnet/IP subnets and
separates by an IP router. The address is entered as host:host can be the host’s name if DNS ins configures. If DNS is not
configured, the host address should be entered in the format xxx.xxx.xxx.xxx follwed by the port number (default settings
47808)
MAC : The MAC address of the device. This need to be unique only to the subnet.
Device ID : The ID of a device, used to identify it on the BACnet network. This number cannot be duplicated anywhere on the
BACnet network and must therefore be unique. To set an ID value of 34600, the low number would be set to 4600 and the high
number to 3
For more information see CORRIGO Pics via http://www.regin.se
V.8.a.4.
Communication LON (si CORRIGO avec option LON)
Set the LON function as below:
In Configuration menu/ Communication / Fonction port 2 = Activate the Port 2 function in extension unit.
Go on the right and activate extension unit. 1 en CORRIGO E28 LON
Button for the PIN service is at the back of the regulator.
Communication table is on http://www.regincontrols.com
V.8.a.5.
Fire function activation
Setting of the Paramétrage de l’entrée
Access : Configuration / Input Output / DI / DI8
Déclarer
l’input DI8 en « Al fire » « NO »
Paramétrage de la fonction
Access : Configuration / Fire function
Choose the required mode when activating the fire function
« Stop » : Complete stop of the unit
«Continuous operation »: Start or keeping of the unit in HS. Fire function will have priority on all others alarms.
«Normal operation»: keeps the unit in the same parameters chosen on site (stop/LS/HS)
« Exhaust fan only »: Start or keep in HS the exhaust fan (return is stopped)
« Return fan only »: Start or keeps in HS the return fan (exhaust stopped)