FREETIME
® -
HEXAMOTION
®
High Efficiency Recovery Unit
OPERATING AND COMMISSIONING INSTRUCTIONS
MS-CDF-010
Ind F
Maj. 18/05/2017
Créé par : JC
Validé par : AR
Page 27/57
IV.17.
MODBUS / WEB / BACNET wiring
(see parameters in chapters V.8)
MODBUS RS485 and BACNET MSTP: Use armoured cable 2 crossed pairs wire type BELDEN 8723 or similar to connect
BMS to controller (to connect to port 1 (BANE) / connect armour to N and don’t connect E)
WEB / MODBUS TCP/IP et BACNET IP: to connect to TCP/IP port
IV.18.
Repeater wiring
see parameters in chapter V.8
You need to use a repeater in case of you want to connect:
o
More than one unit on the same display (maximum 6)
o
A remote control at a distance higher than 100m
In this case you can move to 1 kilometer the remote control. Use 2 crossed wire type BELDEN 8723 or similar between
repeater and controller. Supply repeater in 230V single mono phase.
Connect on port 1 the wires as following instructions :
o
B of repetitor on B terminal of the regulation board (armour wire as in drawing under)
o
A of repetitor on A terminal of regulation board (armour wire as in drawing under)
o
N of repetitor on N terminal of regulation board (armour wire as in drawing under)
Plan a 230V single phase power supply on the repetitor.