19/52 User Instructions
CAIROX
15/12/2021
❶
Power supply:
3N
400V/50Hz:
EASY PRO E-100 (min. 5x2,5mm
2
;
Protection B10)
EASY PRO E-150 (min. 5x2,5mm
2
;
Protection B16)
EASY PRO E-200 (min. 5x4,0mm
2
;
Protection B20)
❷
Power supply:
1N
230V/50Hz:
EASY PRO E-100 (min. 3x1,5mm
2
;
Protection B10)
EASY PRO E-150 (min. 3x1,5mm
2
;
Protection B16)
EASY PRO E-200 (min. 3x2,5mm
2
;
Protection B20)
In the event of a hazard arising from the unintentional reset of the thermal
switch, this equipment should not be powered by an external connecting device,
such as a time switch, or a disconnector connected to the circuit, which is
regularly switched OFF and ON during use.
15
CONTROLS
–
OPTIONAL ELEMENTS
S-C
FAN AUTO - fan operation depends on
the temperature.
FAN CONT - continuous fan operation
HEAT - heating function
FAN - deactivate the thermostat for FAN
CONT
COOL - reversal of the operation logic of
the thermostat
S-TOUCH + S-ECM
S-Touch:
Temperature setting range: +5 ... + 35
o
C
Operating temperature range: -10 ... +
60
o
C Protection degree: IP30
Supply voltage: 24 VDC
S-ECM:
Operating temperature range: -10 ... +
60
o
C Protection degree: IP54
Supply voltage: 230 V / 50 Hz
PIC. 15.1 3-step regulator with built in
thermostat.
PIC. 15.2 Touch screen cont control
system.