S-ECM driver has a possibility to be connected to integrated Building Management System (BMS).
Connection must be made using 3-poliges wire to connectors:
IN-A; IN-B; GND (SIGNAL GROUND).
S-ECM Parameters:
Name
Description
Physical layer
RS485
Protocol
MODBUS-RTU
Baud rate
38400 [bps]
Parity
Even
Data bits
8
STOP bits
1
S-TOUCH Parameters:
Name
Description
Physical layer
RS485
Protocol
MODBUS-RTU
Baud rate
9600-230400 [bps]
Parity
Even
Data bits
8
STOP bits
1
NOTE :
In last appliance in line, dipswitch SW2 has
to be switched to the right
–
T120.
NOTE:
In last S-ECM in line, dipswitch SW2 has to be switched to the right
–
T120. The maximum length
of the connecting cable 50 m (
LIYCY-P 2x2x0,5mm
2
)
.
It is possible to connect up to 31modules S-ECM and control them with one S-TOUCH controller.